Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutWQCS00128_Compliance Evaluation Inspection_20230331ROY COOPER
Go,ernor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Angela Mettlen
Laurinburg-Maxton Airport Commission
909 Market St
Wilmington, NC 28401-4732
C oa. SfATE'q,
NORTH CAROLINA
Environmental Quality
March 23, 2023
SUBJECT: Compliance Inspection Report
Laurinburg-Maxton Airport Commission Collection System
Collection System Permit No. WQCS00128
Scotland County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Laurinburg-Maxton
Airport Commission Collection System on 3/16/2023. This inspection was conducted to verify that the
facility is operating in compliance with the conditions and limitations specified in Collection System Permit
No. WQCS00128. The findings and comments noted during this inspection are provided in the enclosed
copy of the inspection report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
All three pump stations within the system were inspected. SCADA communication system was functional
when tested during the inspection, in addition to operating audio and visual alarms. The pump stations
were well -maintained with good housekeeping and secured with restrictive access. Logs were thorough
and included all maintenance done at the pump station. Documents such as spill response action plan,
CIP, maps, and FOG information were all available for review at the time of inspection.
D Naf11 Carolina 11ep 0-1 of Fnvlronmrnlal-111, 1 DIvls1m of Water R,s ms
Fayettev&Aegiv 1Wl 127SGrt n3treet51ute714 I FaycfteA1k.Nwth Camhna2M1
910.433a300
If you should have any questions, please do not hesitate to contact Danielle Simpson with the Water
Quality Regional Operations Section in the Fayetteville Regional Office at 910-433-3300 or via email at
danielle.simpson@ncdenr.gov.
Sincerely,
DocuSignedd by: Q
5189C2D3DD5C42B...
J. Trent Allen, Regional Supervisor
Water Quality Regional Operations Section
Fayetteville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Fayetteville Regional Office (DS)
PERCS Compliance/Enforcement Unit
DNvrfh Carolina Department of Envlronmernal4aau[y I Dlvlslon of Water Reno ms
!!�qFayetteville Regional Offu 12. Green 1141 FayetteNlk. Worth CaroBna 2MI
—°' 910.433MM
Compliance Inspection Report
Permit: WQCS00128
SOC:
County: Scotland
Region: Fayetteville
Effective: 05/25/17 Expiration: 03/31/25 Owner: Laurinburg-Maxton Airport Commission
Effective: Expiration: Facility: Laurinburg-Maxton Airport Commission Collecti
PO Box 31
Contact Person: Angela Mettlen
Directions to Facility:
System Classifications: CS1,
Primary ORC: Mickey Lee Oxendine
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Title: Program Mgr.
Certification: 985202
Phone: 843-540-1015
Phone: 910-844-5081
NC0044725 Laurinburg-Maxton Airport Commission - Laurinburg Industrial WWTP
Inspection Date: 03/16/2023 Entry Time 10:OOAM Exit Time: 12:30PM
DocuSigned
by
Primary Inspector: Danielle Simpson 118C7638281DAB46D
� ��VU 3/23/2023 Phone: 910-433-3334
ry Ins (s)
Secondary : .
pector
DocuSigned by:
),,t oij 3/28/2023
Reason for Inspection: Routine 5189c2 =5C42B... Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Collection system management and operation
Facility Status: 0 Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions
Capital Improvement Plan
Inspections
Lines
(See attachment summary)
General Sewer & FOG Ordinances
Map Reporting Requirements
Spill Response Plan Spills
Manholes Pump Stations
Page 1 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
There are three pump stations within this system, all three are equipped with SCADA. This communication system was
functional when tested during the inspection, in addition to operating audio and visual alarms. The pump stations were
well -maintained with good housekeeping and secured with restrictive access. Logs were thorough and included all
maintenance done at the pump station.
Documents such as spill response action plan, CIP, maps, and FOG information were all available for review at the time of
inspection.
Page 2 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General Yes No NA NE
Is there a properly designated primary ORC and at least one back-up of proper grade? 0 ❑ ❑ ❑
Are logs being reviewed by the system management or owner on a regular basis? 0 ❑ ❑ ❑
# What is that frequency? weekly.
# Are there any issues being addressed currently or any in the planning stages? 0 ❑ ❑ ❑
Is there a specific pump failure plan available for all pump stations? 0 ❑ ❑ ❑
Does plan indicate if pump parts/new pumps are in spare parts/equipment inventory? ❑ ❑ ❑
Are new/significantly upgraded pump stations equipped with anti -corrosion materials? ❑ ❑ ❑
Does the permittee have a copy of their permit? ❑ ❑ ❑
# Is permit expiring within the next 6 months? ❑ ❑ ❑
If Yes, has the Permittee applied for renewal? ❑ ❑ 0 ❑
Comment: Currently in process of slip lining about 3,000' of lines.
Sewer and FOG Ordinances
Yes No NA NE
Is Sewer Use Ordinance (SUO) or other Legal Authority available?
0
❑ ❑ ❑
Does it appear that the Sewer Use Ordinance is enforced?
0
❑ ❑ ❑
Is there a Grease Control Program that legally requires grease control devices?
❑
❑ 0 ❑
What is the standard grease trap cleaning requirement in the FOG ordinance?
No current
applicable
locations.
Is Grease Control Program enforced via periodic inspections/records review?
0
❑ ❑ ❑
Is action taken against violators?
0
❑ ❑ ❑
# Have satellite systems adopted an equivalent or more stringent ordinance?
❑
❑ 0 ❑
Is grease/sewer education program documented with req'd customer distribution?
0
❑ ❑ ❑
# Are other types of education tools used like websites, booths, special meetings, etc?
0
❑ ❑ ❑
If Yes, what are they? (This can reduce mailing to annual.)
Comment:
Capital Improvement Plan Yes No NA NE
Has a Capital (CIP) or System Improvement Plan been developed and adopted? ❑ ❑ ❑
Is it designated for wastewater only or does it have a dedicated section? ❑ ❑ ❑
Does CIP cover three to five year period of earmarked improvements? ❑ ❑ ❑
Does CIP include description of project area? ❑ ❑ ❑
Does CIP include description of existing facilities? ❑ ❑ ❑
Does CIP include known deficiencies? ❑ ❑ ❑
Does CIP include forecasted future needs? 0 ❑ ❑ ❑
Comment:
Page 3 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
Map
Yes No NA NE
Is there a overall sewer system map?
0
❑ ❑ ❑
Does the map include:
Pipe Type (GS/FM)
0
❑ ❑ ❑
Pipe sizes
0
❑ ❑ ❑
Pipe materials (PVC, DIP, etc)
0
❑ ❑ ❑
Pipe location
0
❑ ❑ ❑
Flow direction
❑
0 ❑ ❑
Approximate pipe age
❑
0 ❑ ❑
Pump station ID, location and capacity
0
❑ ❑ ❑
# Force main air release valve location & type
0
❑ ❑ ❑
# Location of satellite connections
0
❑ ❑ ❑
Is the map being updated for changes/additions within 1 year of activation?
M
❑ ❑ ❑
Comment: CAD and physical copies of system maps.
Reporting Requirements Yes No NA NE
# Have there been any sewer spills in the past 3 years? ❑ ❑ ❑
If Yes, were they reported to the Division if meeting the reportable criteria? ❑ ❑ ❑
If applicable, is there documentation of press releases and public notices issued? ❑ ❑ ❑
Is an Annual Wastewater Performance Report being filed with the Division, if required? ❑ ❑ ❑
Is the report being made available to all its sewer customers? ❑ ❑ ❑
# How is it being made available?
Comment: No spills in the past three years.
Inspections
Yes No NA NE
Are adequate maintenance records maintained?
0
❑ ❑ ❑
Are pump stations being inspected at the required frequency?
0
❑ ❑ ❑
# Is at least one complete functionality test conducted weekly per pump station?
0
❑ ❑ ❑
Is there a system or plan in place to observe the entire system annually?
0
❑ ❑ ❑
Is the annual inspection documented?
0
❑ ❑ ❑
# Does the system have any high -priority lines/locations?
❑ ❑ ❑
Are inspections of HPL documented at least every 6 months?
❑ ❑ ❑
Are new lines being added to the HPL list when found or created?
❑
❑ ❑
Comment:
Spill Response Action Plan Yes No NA NE
Is a Spill Response Action Plan available? 0 ❑ ❑ ❑
Is a Spill Response Action Plan available for all personnel? 0 ❑ ❑ ❑
Page 4 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
Does the plan include:
24-hour contact numbers
❑ ❑ ❑
Response time
❑ ❑ ❑
Equipment list and spare parts inventory
❑ ❑ ❑
Access to cleaning equipment
❑ ❑ ❑
Access to construction crews, contractors, and/or engineers
❑ ❑ ❑
Source of emergency funds
❑
❑ ❑
Site sanitation and cleanup materials
❑ ❑ ❑
Post-overflow/spill assessment
❑ ❑ ❑
Does the Permittee appear to respond within 2 hours of first knowledge of a spill?
❑ ❑ ❑
Comment: Plan for all situations including plane crash.
$pills Yes No NA NE
Is system free of known points of bypass? ❑ ❑ ❑
If No, describe type of bypass and location
Are all spills or sewer related issues/complaints documented? ❑ ❑ ❑
# Are there repeated overflows/problems (2 or more in 12 months) at same location? ❑ ❑ ❑
# If Yes, is there a corrective action plan? ❑ ❑ 0 ❑
Comment: Industry park, no residential customers.
Lines/Right-of-Ways/Aerial Lines Yes No NA NE
Please list the Lines/Right of Ways/Aerial Lines Inspected:
Are right-of-ways/easements maintained for full width for access by staff/equipment? ❑ ❑ ❑
If No, give details on temporary access:
Is maintenance documented? ❑ ❑ ❑
Are gravity sewer cleaning records available? ❑ ❑ ❑
Has at least 10% of lines older than 5 yrs been cleaned annually? ❑ ❑ ❑
Were all areas/lines inspected free of issues? 0 ❑ ❑ ❑
Comment:
Manholes
Yes No NA NE
Please list the Manholes Inspected:
Are manholes accessible?
❑ ❑ ❑
# Are manhole covers/vents above grade?
❑ ❑ ❑
Are manholes free of visible signs of overflow?
❑ ❑ ❑
Are manholes free of sinkholes and depressions?
❑ ❑ ❑
Are manhole covers present?
❑ ❑ ❑
# Are manholes properly seated?
❑ ❑ ❑
Page 5 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
# Are manholes in good condition?
0
❑ ❑ ❑
# Are inverts in good condition?
0
❑ ❑ ❑
Is flow unrestricted in manholes?
0
❑ ❑ ❑
Are manholes free of excessive amounts of grease?
0
❑ ❑ ❑
Are manholes free of excessive roots?
0
❑ ❑ ❑
Are manholes free of excessive sand?
0
❑ ❑ ❑
Are manhole vents screened?
❑
❑ ❑
Are vents free of submergence?
❑
❑ ❑
Are manholes free of bypass structures or pipes?
0
❑ ❑ ❑
Comment:
Pump Stations
Yes No NA NE
Please list the Pump Stations Inspected:
Burch, 401, and Embrex.
# Number of duplex or larger pump stations in system
2
# Number of vacuum stations in system
0
# Number of simplex pump stations in system
1
# Number of simplex pump stations in system serving more than one building
0
How many pump/vacuum stations have:
# A two-way "auto polling" communication system (SCADA) installed?
3
# A simple one-way telemetry/communication system (auto -dialer) installed?
0
For pump stations inspected:
Are they secure with restricted access?
❑ ❑ ❑
Were they free of by-pass structures/pipes?
❑ ❑ ❑
Were wet wells free of excessive grease/debris?
❑ ❑ ❑
# Do they all have telemetry installed?
❑ ❑ ❑
Is the communication system functional?
❑ ❑ ❑
Is a 24-hour notification sign posted ?
❑ ❑ ❑
Does the sign include:
Owner Name?
❑ ❑ ❑
Pump station identifier?
❑ ❑ ❑
# Address?
❑ ❑ ❑
Instructions for notification?
❑ ❑ ❑
24-hour emergency contact numbers?
❑ ❑ ❑
Are audio and visual alarms present?
❑ ❑ ❑
Are audio and visual alarms operable?
❑ ❑ ❑
# Is there a backup generator or bypass pump connected?
❑
❑ ❑
Page 6 of 7
Permit: WQCS00128 Owner - Facility: Laurinburg-Maxton Airport Commission
Inspection Date: 03/16/2023 Inspection Type : Collection System Inspect Non Sampling
Reason for Visit: Routine
If tested during inspection, did it function properly?
❑
❑ 0 ❑
Is the back-up system tested at least bi-annually under normal operating conditions?
0
❑ ❑ ❑
# Does it have a dedicated connection for a portable generator?
0
❑ ❑ ❑
# Is the owner relying on portable units in the event of a power outage?
0
❑ ❑ ❑
# If Yes, is there a distribution plan?
0
❑ ❑ ❑
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
Two portable generators and a permanent generator at the highest flow station.
# Does Permittee have the approved percentage of replacement simplex pumps?
0
❑ ❑ ❑
Is recordkeeping of pump station inspection and maintenance program adequate?
0
❑ ❑ ❑
Do pump station logs include at a minimum
Inside and outside cleaning and debris removal? 0 ❑ ❑ ❑
Inspecting and exercising all valves? 0 ❑ ❑ ❑
Inspecting and lubricating pumps and other equipment? 0 ❑ ❑ ❑
Inspecting alarms, telemetry and auxiliary equipment? 0 ❑ ❑ ❑
Comment: SCADA was functional when tested during the inspection, in addition to operating audio and
visual alarms.
The pump stations were well -maintained with good housekeeping and secured with restrictive
access.
Logs were thorough and included all maintenance done at the pump station.
Page 7 of 7