HomeMy WebLinkAboutNC0031836_Compliance Evaluation Inspection_20230317ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Andy Smith
City of Statesville
Post Office Box I I I I
Statesville, NC 28677
NORTH CAROLINA
Environmental Quality
March 17, 2023
SUBJECT: Compliance Evaluation Inspection
City of Statesville/Fourth Creek WWTP
NPDES Permit No. NCO031836
Iredell County
Dear Mr. Smith:
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on March 7, 2023, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge (ORC)
of our findings by forwarding the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr. gov.
Sincerely,
DocuSigned by:
A wNN,uft
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
Enclosure:Inspection Report
Cc: NPDES Program Files - Laserfiche
DEQ�
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
Form Approved.
EPA Washington, D.C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO031836 111 121 23/03/10 I17 18 LC] I 19 I s I 20L]
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
2.0 701d I 71 I„ I 72 I r., I 71 I 74 79 I I I I I I I80
L—I ty L-1 I I
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
09:20AM 23/03/10
19/03/01
Fourth Creek WWTP
693 Bell Farm Rd
Exit Time/Date
Permit Expiration Date
Statesville NC 28687
01:OOPM 23/03/10
23/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Kenneth Andrew Galloway/ORC//
Stephen E Littlejohn///
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Ron Smith,PO Box 1111 Statesville NC 286871111//704-878-3584/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Doc uSigned by:
Wes Bell D"� DWR/MRO WQ/704-663-1699 Ext.2192/ 3/16/2023
E
A:c,96D90=437...
Signature of Man a49aA�viewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitn r AP'�'' ' H P41WR/MRO WQ/704-663-1699 Ext.2180/ 3/16/2023
F161 FB69A2D84A3.,.
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
NCO031836 I11 12I 23/03/10 117 18 i c i
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page#
Permit: NCO031836 Owner -Facility: Fourth Creek WWTP
Inspection Date: 03/10/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
0
❑
❑
❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
M
❑
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
0
❑
❑
❑
Comment: The City implements a Division -approved Industrial Pretreatment Program.
The Division received the City's permit renewal package on 9/20/2022.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 1 /28/2021.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ❑ ■
Page# 3
Permit: NCO031836
Inspection Date: 03/10/2023
Owner -Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed durinq the inspection were organized and well maintained.
Effluent permit limit violations were reported in April 2022 (ammonia — monthly
average), May 2022 (ammonia — monthly average) and July 2022 (copper — daily
maximum). The Division has separately addressed these limit violations through the
issuances of either a Notice of Violation (NOV) or NOV/civil penalty assessment. The
Permittee must ensure that the annual WWTP performance report is submitted no later
than sixty (60) days following the selected time period (calendar or fiscal year).
Laboratory
Yes
No
NA
NE
Are field parameters performed by certified personnel or laboratory?
■
❑
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
■
❑
❑
❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
❑
❑
❑
■
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
■
Comment: Influent and effluent (including field) analyses are performed under the
City's on -site
certified laboratory (Certification #181). Pace Analytical Services, Meritech Labs and
Statesville Analytical have all been contracted to provide analytical support.
Influent Sampling
Yes
No
NA
NE
# Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
■
❑
❑
❑
Is the tubing clean?
■
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
0
❑
❑
❑
degrees Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: The subject permit requires influent BOD and TSS composite samples.
The sampler tubing should be cleaned and/or replaced within the near future.
The ORC and staff must ensure that the maximum amount of flow in between
composite samples (aliquots) does not exceed 1/24th of the total expected flow for
that
sampling day.
Effluent Sampling
Yes
No
NA NE
Is composite sampling flow proportional?
0
❑
❑
❑
Is sample collected below all treatment units?
M
❑
❑
❑
Is proper volume collected?
0
❑
❑
❑
Is the tubing clean?
0
❑
❑
❑
Page# 4
Permit: NCO031836
Inspection Date: 03/10/2023
Owner -Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: The subject permit requires composite and grab effluent samples.
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
Comment: The Division has conditionally waived the instream monitoring requirements due to the
City's participation in the Yadkin -Pee Dee River Basin Association.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facilitv appeared to be properly operated and well
maintained. The facility staff incorporate a comprehensive process control program
with all measurements being documented and maintained on -site. Detailed operation
& maintenance records are also maintained on -site.
The facility is also equipped with a SCADA system to assist the wastewater staff in
treatment plant operations.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Screenings are disposed at a permitted landfill.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NCO031836
Inspection Date: 03/10/2023
Owner -Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Pump Station - Influent
Yes
No
NA
NE
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
0
❑
❑
❑
Is SCADA telemetry available and operational?
0
❑
❑
❑
Is audible and visual alarm available and operational?
❑
❑
0
❑
Comment:
Aeration Basins
Yes
No
NA NE
Mode of operation
Ext. Air
Type of aeration system
Surface
Is the basin free of dead spots?
0
❑
❑
❑
Are surface aerators and mixers operational?
■
❑
❑
❑
Are the diffusers operational?
❑
❑
0
❑
Is the foam the proper color for the treatment process?
0
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Comment: Both aeration basin trains were in service. Each aeration basin is equipped with six
platform aerators.
Secondary Clarifier
Yes
No
NA
NE
Is the clarifier free of black and odorous wastewater?
0
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
0
❑
❑
❑
Are weirs level?
0
❑
❑
❑
Is the site free of weir blockage?
0
❑
❑
❑
Is the site free of evidence of short-circuiting?
0
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
0
❑
❑
❑
Is the return rate acceptable (low turbulence)?
0
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
0
❑
❑
❑
Comment: All three secondary clarifiers were in service.
Page# 6
Permit: NCO031836
Inspection Date: 03/10/2023
Owner -Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Pumps-RAS-WAS
Yes
No
NA
NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
■
❑
❑
❑
Comment:
Disinfection -Liquid
Yes
No
NA
NE
Is there adequate reserve supply of disinfectant?
■
❑
❑
❑
(Sodium Hypochlorite) Is pump feed system operational?
0
❑
❑
❑
Is bulk storage tank containment area adequate? (free of leaks/open drains)
0
❑
❑
❑
Is the level of chlorine residual acceptable?
0
❑
❑
❑
Is the contact chamber free of growth, or sludge buildup?
■
❑
❑
❑
Is there chlorine residual prior to de -chlorination?
0
❑
❑
❑
Comment:
De -chlorination
Yes
No
NA
NE
Type of system ?
Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)?
M
❑
❑
❑
Is storage appropriate for cylinders?
❑
❑
0
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
■
❑
Comment: Aqueous sodium bisulfite is used for dechlorination.
Are tablet de -chlorinators operational?
❑
❑
0
❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
Yes
No
NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
0
❑
❑
❑
Is the flow meter operational?
0
❑
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: The flow meter is calibrated twice per year and was last calibrated on 10/26/2022 by
Diversified Integration, Inc.
Page# 7
Permit: NCO031836 Owner -Facility: Fourth Creek WWTP
Inspection Date: 03/10/2023 Inspection Type: Compliance Evaluation
Effluent Pipe
Yes
No
NA
NE
Is right of way to the outfall properly maintained?
0
❑
❑
❑
Are the receiving water free of foam other than trace amounts and other debris?
❑
❑
❑
If effluent (diffuser pipes are required) are they operating properly?
❑
❑
■
❑
Comment: The effluent appeared clear with trace suspended solids and no foam.
Aerobic Digester
Yes
No
NA
NE
Is the capacity adequate?
■
❑
❑
❑
Is the mixing adequate?
0
❑
❑
❑
Is the site free of excessive foaming in the tank?
0
❑
❑
❑
# Is the odor acceptable?
0
❑
❑
❑
# Is tankage available for properly waste sludge?
■
❑
❑
❑
Comment: The aerobic digester is equipped with three platform aerators.
Solids Handling Equipment
Yes
No
NA
NE
Is the equipment operational?
0
❑
❑
❑
Is the chemical feed equipment operational?
■
❑
❑
❑
Is storage adequate?
0
❑
❑
❑
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
0
❑
❑
❑
Is the site free of sludge buildup on belts and/or rollers of filter press?
■
❑
❑
❑
Is the site free of excessive moisture in belt filter press sludge cake?
■
❑
❑
❑
The facility has an approved sludge management plan?
0
❑
❑
❑
Comment: The belt filter press was operational and in service. Dewatered bio-solids are either
lime stabilized and distributed to the public under Permit No. WQ0006245 or land
applied (Class B product) under Permit No. WQ0014543.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Page# 8
Permit: NCO031836
Inspection Date: 03/10/2023
Standby Power
Owner -Facility: Fourth Creek WWTP
Inspection Type: Compliance Evaluation
Yes No NA NE
Comment: The backup generator is tested under load every ten (10) days and serviced quarterly
by Power Generation & Control. The City also participates in a Load Management
Program.
Page#