Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN 1 2 u 3 I NCO021709 111 121 23/02/23 I17 18 LC] I 19 I s I 201
21111I I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I I I I r6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------------- Reserved -------------------
67
I 72 I n, I 71 I 74 79 I I I I I I I80
701 I 71 I LL -1 I I
LJ
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES Dermit Number)
10:30AM 23/02/23
18/02/01
Jefferson WWTP
1233 NC Hwy 16 S
Exit Time/Date
Permit Expiration Date
Jefferson NC 28640
12:40PM 23/02/23
22/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Timothy Church/ORC/336-246-2165/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Timothy Church,PO Box 67 Jefferson NC 286400067//336-246-2165/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran 0 Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Patricia Lowery DWR/WSRO WQ/336-776-9691/
DocuSigned by: 3/3/2023
til.Ct.(A. �i9�.t9
0
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
by:
3/3/2023
FDocuSigned
ti T.
'--- 145B49E225C94EA...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
NPDES yr/mo/day Inspection Type (Cont.)
NC0021709 I11 12I 23/02/23 117 18 ici cJ
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On February 23rd, 2023, Tricia Lowery met with Tim Church (ORC) to perform Compliance Evaluation
Inspection at Jefferson WWTP (NPDES PERMIT#NC0021709). This inspection consisted of two
parts: 1) in -office file review, and 2) on -site inspection of the treatment facility. Tim Church assisted
with the in -office review, and escorted inspector through the facility during the on -site inspection.
The attached EPA inspection form detail the areas that were evaluated with their respective
comments.
Area found to be of concern are:
1. The 2 traveling bridge teritary filters are out of service. Currently facility is bypassing this
treatment and sending effluent from secondary clarifiers to chlorine contact chamber. NPDES Permit
Part II, Section C(4)(c)(1)(B) states bypass from the treatment facility is prohibited and enforcement
action can be taken against a Permittee unless there were no feasible alternatives to the bypass.
2. DWR was not notified of bypass at the time it occured. NPDES Permit Part II, Section C(4)(b)(2)
states: The Permittee shall submit notice of an unanticipated bypass as required in Part II.E.6.
(24-hour notice).
Page#
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NCO021709 Owner -Facility: Jefferson WWTP
Inspection Date: 02/23/2023 Inspection Type: Compliance Evaluation
Permit
Yes
No
NA
NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
■
❑
❑
❑
application?
Is the facility as described in the permit?
■
❑
❑
❑
# Are there any special conditions for the permit?
❑
■
❑
❑
Is access to the plant site restricted to the general public?
■
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: Permit expired 3/31/2022. Permit renewal application was received 5/19/2022. Final
permit is not complete, therefore the facility operates under expired permit until new
one is finalized.
Record Keeping
Yes
No
NA
NE
Are records kept and maintained as required by the permit?
■
❑
❑
❑
Is all required information readily available, complete and current?
■
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
■
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
■
❑
❑
❑
Is the chain -of -custody complete?
■
❑
❑
❑
Dates, times and location of sampling
■
Name of individual performing the sampling
■
Results of analysis and calibration
■
Dates of analysis
■
Name of person performing analyses
■
Transported COCs
■
Are DMRs complete: do they include all permit parameters?
■
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
■
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
❑
❑
■
❑
operator on each shift?
Is the ORC visitation log available and current?
■
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
■
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility
❑
■
❑
❑
classification?
Is a copy of the current NPDES permit available on site?
■
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
■
❑
Page# 3
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NCO021709 Owner -Facility: Jefferson WWTP
Inspection Date: 02/23/2023 Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The is Grade III facility. Backup operator (Jacob Cruev) is in the process of obtaining
his Grade II certification. He works under the supervision of Tim Church until he
obtains Grade II status. (Tim Church WW-4 #9743: Jacob Cruev WW-1 #1011936)
Records are well maintained and kept for appropriate time. Inspector reviewed
December 2022 DMR. No issues found.
Facility has certification for field parameters: PH, TLC (low level), and DO. Water
Quality Labs (Cert Lab #544) analyzes all other parameters required for permit.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: Inspector found no issues.
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
Yes No NA NE
❑ ■ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Comment: Ultrasonic flow meter is used for influent flow measurement, but is not used for
reporting. The permit states flow to be measured at influent OR effluent.
Effluent flow
meter is used for reporting.
Flow Measurement - Effluent
Yes
No
NA NE
# Is flow meter used for reporting?
0
❑
❑
❑
Is flow meter calibrated annually?
M
❑
❑
❑
Is the flow meter operational?
❑
■
❑
❑
(If units are separated) Does the chart recorder match the flow meter?
❑
❑
0
❑
Comment: Flow meter was calibrated November 2022 and is calibrated annually. Note: Weir
plate is leaking around the edges and is currently being repaired. Carolina Tech Svcs
are making the new weir plate. Once complete, contractor will come to install. ORC
stated the flow is calculated on DMR until repair is complete. The flow meter is
operational and used for reporting, however until the weir plate is repaired, they are
calculatina flow.
Page# 4
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NCO021709 Owner -Facility: Jefferson WWTP
Inspection Date: 02/23/2023 Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Type of bar screen
a.Manual
❑
b.Mechanical
Are the bars adequately screening debris?
0
❑
❑
❑
Is the screen free of excessive debris?
0
❑
❑
❑
Is disposal of screening in compliance?
0
❑
❑
❑
Is the unit in good condition?
0
❑
❑
❑
Comment: Overall the bar screen is in qood condtion. They are currently doinq periodic
maintanence by repairing/replacing screens that are exhibiting normal wear.
Operations & Maintenance
Yes
No
NA NE
Is the plant generally clean with acceptable housekeeping?
0
❑
❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
❑
❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: MLSS is -2500 mg/l. SVI is -200. Good records are kept on process control tests. No
issues found.
Oxidation Ditches
Yes
No
NA NE
Are the aerators operational?
0
❑
❑
❑
Are the aerators free of excessive solids build up?
■
❑
❑
❑
# Is the foam the proper color for the treatment process?
■
❑
❑
❑
Does the foam cover less than 25% of the basin's surface?
0
❑
❑
❑
Is the DO level acceptable?
0
❑
❑
❑
Are settleometer results acceptable (> 30 minutes)?
■
❑
❑
❑
Is the DO level acceptable?(1.0 to 3.0 mg/1)
0
❑
❑
❑
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
0
❑
❑
❑
Comment: Settleability test -55% Co) 30mins. No excessive foam or solids build up.
Foam covers
<25% of surface. Good earthy smell to basin. DO levels are in acceptable range.
No
issues found.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NCO021709 Owner -Facility: Jefferson WWTP
Inspection Date: 02/23/2023 Inspection Type: Compliance Evaluation
Secondary Clarifier
Yes
No
NA
NE
Is the site free of evidence of short-circuiting?
■
❑
❑
❑
Is scum removal adequate?
■
❑
❑
❑
Is the site free of excessive floating sludge?
■
❑
❑
❑
Is the drive unit operational?
■
❑
❑
❑
Is the return rate acceptable (low turbulence)?
■
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
■
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
■
❑
❑
❑
Comment: No issues found during inspection. Sludge blankets average -2 ft.
Sand Filters (Low rate)
Yes
No
NA
NE
(If pumps are used) Is an audible and visible alarm Present and operational?
❑
❑
❑
■
Is the distribution box level and watertight?
❑
❑
❑
■
Is sand filter free of ponding?
❑
❑
❑
■
Is the sand filter effluent re -circulated at a valid ratio?
❑
❑
❑
■
# Is the sand filter surface free of algae or excessive vegetation?
❑
❑
❑
■
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
❑
❑
❑
■
Comment: The 2 traveling bridge teritary filters are out of service. Currently facility is bwassin
this treatment and sending effluent from secondary clarifiers to chlorine contact
chamber. Kemp Inc are coming to repair both filters. Inspector examined the estimate
and work order to complete repairs. However, DWR was not notified at the time the
filters became out of service and bypass was occuring at facility. NOD will be issued.
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Yes No NA NE
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
■ ❑ ❑ ❑
❑ ❑ ■ ❑
❑ ❑ ■ ❑
Page# 6
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NCO021709 Owner -Facility:
Inspection Date: 02/23/2023 Inspection Type:
Jefferson WWTP
Compliance Evaluation
Disinfection -Gas
Yes
No
NA
NE
Comment: No issues found during inspection. Contact chamber is free of growth with no sludge
buildup considering treatment is bypassing teritiary filters.
De -chlorination
Yes
No
NA
NE
Type of system ?
Other
Is the feed ratio proportional to chlorine amount (1 to 1)?
0
❑
❑
❑
Is storage appropriate for cylinders?
0
❑
❑
❑
# Is de -chlorination substance stored away from chlorine containers?
0
❑
❑
❑
Are the tablets the proper size and type?
❑
❑
MEI
Comment: Sodium thiosulfate is used for dechlorination. The Na2S203 is 'rice crystals' not
tablets (Sodium Thiosulfate Rice Pentahydrate).
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use?
Comment: No issues found durinq inspection.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
I
Yes No NA NE
❑ ■ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Currently using CT/CV sampling (not flow proportionate) until weir plate is repaired and
flow meter is put in operation again.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: No issues found during inspection.
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Page# 7
DocuSign Envelope ID: 0498E129-3DBA-4B60-A6F2-4D9FCBBEOA7E
Permit: NC0021709 Owner -Facility: Jefferson WWTP
Inspection Date: 02/23/2023 Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes
No
NA
NE
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
❑
❑
❑
■
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Comment: Nixon services generators 2x/vear. Generators are checked and logs kept of regular
maintenance and service. No issues found during inspection.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
Comment: Land application (-35 acres). Class B liquid. No excessive moisture or sludge build
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Yes No NA NE
■ ❑ ❑ ❑
Comment: Upstream: must below bridge na. Hwy 16 H00 ft above discharge). Downstream: right
past aerobic digester (-300 ft downstream). Records indicate samples are taken as
required. No issues found.
Page# 8