HomeMy WebLinkAboutNC0086053_Issuance of Permit_20110103 ..
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Coleen H. Sullins Dee Freeman
Governor Director Secretary
January 3, 2011
Mr.Alan J. Fass
Dynamis,Inc. • -
P.O. Box 50636
Knoxville,TN 37950
Subject: Issuance of NPDES Permit NC0086053
Pilot Travel Center#393 WWTP
Haywood County
Dear Mr. Fass:
Division personnel have reviewed and approved your application for renewal of the subject permit.
Accordingly,we are forwarding the attached NPDES discharge permit. This permit is issued pursuant to
the requirements of North Carolina General Statute 143-215.1 and the Memorandum of Agreement between
North Carolina and the U.S. Environmental Protection Agency dated October 15, 2007(or as subsequently
amended).
This final permit includes no majorchanges from the draft permit sent to you on
November 10, 2010.
If any parts, measurement frequencies or sampling requirements contained in this permit are
unacceptable to you,you have the right to an adjudicatory hearing upon written request within thirty(30)
days following receipt of this letter. This request must be in the form of a written petition,conforming to
Chapter 150B of the North Carolina General Statutes,and filed with the Office of Administrative Hearings
(6714 Mail Service Center,Raleigh, North Carolina 27699-6714). Unless such demand is made,this
decision shall be final and binding.
Please note that this permit is not transferable except after notice to the Division. The Division may
require modification or revocation and reissuance of the permit. This permit does not affect the legal
requirements to obtain other permits which may be required by the Division of Water Quality or permits
required by the Division of Land Resources,the Coastal Area Management Act or any other Federal or Local
governmental permit that may be required. If you have any questions concerning this permit,please
contact Charles Weaver at telephone number(919)807-6391.
Sincerely,
oleen H. Sullins
.0T
cc: Central Files
Asheville Regional Office/Surface Water Protection
NPDES Unit
1617 Mail Service Center,Raleigh,North Carolina 27699-1617 One
512 North Salisbury Street,Raleigh,North Carolina 27604 NorthCarolina
Phone: 919 807-63001 FAX 919 807-6495/httpJ/portal.ncdenr.org/web/wq 7' 'iztiiriiI/jj
An Equal Opportunity/Affirmative Action Employer-50%Recycled/10%Post Consumer Paper
Permit NC0086053 •
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provision of North Carolina General Statute 143-215.1,other lawful standards and regulations
promulgated and adopted by the North Carolina Environmental Management Commission,and the Federal Water Pollution
Control Act,as amended,
Pilot Travel Centers LLC
is hereby authorized to discharge wastewater from a facility located at the
Pilot Travel Center# 393
3712 Crabtree Rd
Waynesville
Haywood County
to receiving waters designated as Stingy Branch in subbasin 04-03-05 of the French Broad River Basin in
accordance with effluent limitations,monitoring requirements,and other conditions set forth in Parts I, II,
III and IV hereof.
This permit shall become effective February 1,2011.
This permit and authorization to discharge shall expire at midnight on January 31,2016.
Signed this day January 3,2011.
oleen H. Sullins, Director
Or Division of Water Quality
By Authority of the Environmental Management Commission
• . .
• Permit NC0086053
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES Permits issued to this facility, whether for operation or discharge are hereby
revoked. M of this permit issuance, any previously issued permit bearing this number is no longer
effective. Therefore, the exclusive authority to operate and discharge from this facility arises under the
permit conditions, requirements, terms, and provisions included herein.
Pilot Travel Centers LLC, is hereby authorized to:
1. Continue to operate an existing0.025 MGD extended aeration concrete
(concrete)
wastewater treatment facility that includes the following components:
• 5,000-gallon flow equalization basin with dual 0.5-hp alternating pumps and
manual bar screen
• Six 5,000-gallon aeration basins with dual 549-CFM blowers providing diffused
air
• Two rectangular 5200-gallon clarifiers with skimmers and sludge returns
• 5000-gallon aerobic digester
• Tablet chlorine disinfection
• 875-gallon chlorine contact chamber
• Tablet dechlorination
• 500-gallon dechlorination / post aeration chamber
The facility is located at Pilot Travel Center # 393, (3712 Crabtree Rd,
Waynesville), northwest of Clyde in Haywood County.
2. Discharge from said treatment works at the location specified on the attached map
into Stingy Branch, currently classified C waters in hydrologic unit 06010106 of
the French Broad River Basin.
.... ': ..1 i 1 1.„ .. 1..,\ . \\ ,./ i‘4,.! .. ,,P-
....'
, % 1, e I .. ... / 1 ..... , ,
.;.,...-- / i
. •
e( ( . .. i .- + . \
) -...
• -- .
/7
1 \\ . I ' .. r 0 e .
• ; I/ .." •
' . • 0 • . il0: / /' '''•• ) II Q e 4 / .-------. . ..-/
, ? ( \
N._ / ?I:1i k -rt..- sI( .....-
. . • .. . i''...,.........'.". ' .0 ."". -L..... . I \ . ,
y
' /...... p. .- -------Nz:N, , ... t
. ,
•.1 -. ..0'3 ' C. ... r' • 0', ''••oi 541 11\...
is ‘ • -•••• ...- -
- , . •
4143. I .• ;li •••••• . ..-„,„. r` - -- -• \ --\".., ..
litC ..." ---___ 1
--. 1
- :.. ... •. , ••-;/: - - ....,.1••%.„,".-ss„ ,, ^-_5-;„-- -. • \
1 • •
, :4,• ..,- .„---:•...,.... .... --a.t.-„,,; ,
•,, ., td• ,...1 ../-„,--- ;4.o,- • r• , , . %-, ..\
.
,..., k \ , "_,.. .1 ! • • ,
•
" I • '1.\.\ \ ( c• - ..•.. ---- \\ i''• k ';'-'..
ti i .,;.':,\, ‘ \ \ -, • -*, -,. \ --7,;-----
- \ -- ', , ,..:•-i_ir\.,,I . . .."-- -- Ns \'i%,‘\i Ai\ i , %s1 ., \ \e' ,. - • • -'-'173-1.61-0rts.:
•, \ . ', ki, ,, -'--- i '. •\,... ..../ • ‘1. 1. .../ " •-'1 -ss• ,_
..• •e.A.. .
r• "ir ' . N \ •-• /--'•
. '-'' / /4! '''.- --, ___;`,„ .,___} / i rs--/ , 11, , --, \ t. , .•,_. ...•,_ _ •- •• .•- •• • : •
'_.) ';\.•_ • -- . . 1 ,
.. . r :••,..7:."S.,N.:\‘..,k'S C).,..e.../.ii,.,) ...
• I
. 1 I
,., ''...."..t. . .....,
1 ,. ..1*1 . • ,
•
\ ' ' 4'...
\Y\:;.. . ' '
i • ' '..z 1 .s...,--.--"Th s-- ry . • . - 7 "/ 0/1111111_1.7- ',( 41 t \ •- '
?'. (Li _ _ -, ' 11 '.. ; •‘--- .,..-- r.,.....). .• ':•':1' 4- ''''SC• 241
e,../1. . •/44‘ , . - ...• ri .v.Aip "..... . \ .1.,,._....., . .,
4. l• ..•..
'... 1 . P8
1 i N'',. .
, , k : \ 1,,‘..•
: i '
I I (..%.4,1 • I ....
•
-!, , ,..-,-•i i 4110 , \
•
. , .,....—• I
,N,‘,.•, . o i _-"i •i1
.I\1(I'\I- • • I
,', Discharge Point 1 f
.
\ ? '.. , .. \\ ,t N00086053 .
. t%N... -•.c')-
,...
, . • 1
•. .\\.,
. ' i i • s.. s, , ,,. ,--'. 8)? , . , •, • --,.... ,-.., ,
1 \I _ d
i
0 ...„ 4 ... •. \ \ s' •. • .' •..,.. fl
•I kls
So . ' , I • \
•., p %111‘ . 0\;;;..... t1 n. ar.., •
' '... . .
. .,,! •• ...-•,- •
• .
ire /
\
. .. . .• . -.i..,:‘,. \--t, ../ .., ,.. rz- fr 1
41:0\,,, ..„.. . Lil •-• 1 *.***'.. '.'4'4r". ••'' ' , -.\..
_._• ••,. .....• •
•••••:••'• .,
-1,7 --•"-- .. 11 . '. I / ‘,..••„......,...
. ,. . -.. P f •'. . ..••• • .
. i - • -•• • -., „, • ,, •,,,,
---......_ •- - ; i I. . ,1, .•
.....• •...v.:-
• ......., , ,
,1
I ...:41....0
. .,•'. ' . %.
,* . •
•
..".. .. 1Mt; ••••,...
. .;%S. •• .. ..
. .
. S•,
. .... ''' • -
"'.iiii' lltilliiiii lio.p.,.2 1 1 , 1, • \N . . %'1 '
r\
'"1 \'''!!'.A..n i;o.\t h - „.-• ..1, , • . •
. —__.....
--.., i - = •- : ‘,4_ _ ....._24__
\**,...„„,...,---,--''''...."..
\ • ........„...--,..
--
Iv
0 _. _ _
••.,..,_ . _ _ _ ..”• ,,..:.4..4.7.--Z.:. ..,_
, I .‘ r.s. .,.7.?,.., ••• ........ *_
..,, , ,
1 I i 1. 1 ••
'N's..•••,:-... • • La
.... -- . .. 1
j ....._
„.. . ...• .,,
- -- .
_...v..
- \ ; ,; f .. .
. , ,.r--1-_ • - . - _-----. )11126 - ..,-... - _- - ,.1 1 1 . . .
•
.! -. .... -• !'__ -.
ti, ..... ' )- 7: ..--• --) 0 5 . ,. ...--- -.- .
-- - ii • . . • r
//r '' • - -
• '
. .
i ...1 I, i,.I _ , ..• • . .-'-
„,,,- .., ._,".• ( 't,,..-...._:::2 5 4._. 1 (7'r-----'""..".": \'''''',.., ! ; :. ' .- • ,
1 ),
4 /: , •
. • I
.v ... '
• • • - .. ' ... I
, • t - • • . '
'
i • '',.."...`i , i t- - '"--)
-.., - i I. , . . •••• ' .- )
. .
• I /...-- . ..- _._.• ,.
•
.k...,-) •..'( • . . '',. • ', '
.I.' . .• ..,'...... ..•" ...- ,.',. ' ..----;, . .• . • :, vittO • ' t !N.•.., k., .., .,_ _..
. IP
,--;.,• f.,...-.• , /,„.-.:... .. ... e _- -:, , ,, .
•'''''"----''." 1 1 : '''. ‘ ' -
. -.-.
- \ . I t: ••••,.., I --,,I.,,,„ .., \•••'4 \-...,:- 4.
-.•••... -' .",-/ „ . :- ,/ j 1 ,
•'(,.•..,• .;--..= t.' ' 1. ', ,--- ,.---;::-:‘"? 'I' \--.- • • ..:-) --—.N. .\ 1
• . ....,„„.. ... ,
\ •.,:, , , , . ... „...--' 1 , --'- -• ,..,- ," `'N\ . ..4,
Vi ,.:..--.,..,--1„',i)-•- • - . ..., \ .
,,,' , ,.• , 1 ... 1..--,,,.,. -•. f •--• ..r• • .• N ,, I i __ _
....4 , 1"---,,..••, ..
,i 'e .1,- . -, , . ' i .. - • .," , _ ,..\.. •
i' 1,, ,,,, ••• •.i.
__ ...
,•_ ..• .
_,..., - d " ,./ i • 1 i /-) I
• .
1 r.1;',; .f'• , ' • "- ' .^. ' ' I f '. ---L, t
L------
NC0086053 - Pilot Travel Center #393 Facility
Latitude: 35°34'22" Sub-Basin: 04-03-05 i Location
Longitude: 82°57'10" River Basin: French Broad
Quad Name: Clyde,N.C. Hydrologic Unit: 06010106 ,,
Stream Classt. C " •
Receiving Stream: Stingy Branch 7/49?/14 Haywood County
Map not to scale
•
Permit NC0086053
A. (1) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
During the period beginning on the effective date of this permit and lasting until expiration, the
Permittee is authorized to discharge from outfall.001. Such discharges shall be limited and monitored .
by the Permittee as specified below:
PARAMETER LIMITS MONITORING REQUIREMENTS
[PCS code] Monthly Average Daily Maximum Measurement Sample Sample
Frequency Type Location
Flow 0.025 MGD Continuous Recording Influent or
[50050] Effluent
BOD,5 day(2020) 30.0 mg/L 45.0 mg/L Weekly Composite Effluent
[C0310]
Total Suspended Solids 30.0 mg/L 45.0 mg/L Weekly Composite Effluent
[C0530]
NH3 as N(April 1-October 31) 11.9 mg/L 35.0 mg/L Weekly Composite Effluent
[C0610]
NH3 as N(November 1 -March 31) 2/Month Composite Effluent
[C0610]
Fecal Coliform(geometric mean) 200/100 ml 400/100 ml Weekly Grab Effluent
[31616]
Total Residual Chlorine(TRC)' 28 pg/L 2/Week Grab Effluent
[50060]
Oil&Grease 30.0 mg/L 60.0 mg/L Weekly Grab Effluent
[00556]
pH >6.0 and<9.0 standard units Weekly Grab Effluent
[00400]
Footnotes:
1. The facility shall report all effluent TRC values reported by a NC certified laboratory including field
certified. However, effluent values below 50 µg/L will be treated as zero for compliance purposes.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
•
Weaver, Charles
From: Frazier, Wanda
Sent: Monday, November 29, 2010 3:09 PM
To: Weaver, Charles
Cc: Edwards, Roger, Pugh, James L.
Subject: NC0086053 Pilot Travel Center DRAFT permit renewal
Attachments: NC0086053 Pilot Travel Center#393 Expedited Fact Sheet.doc; NC0086053 Pilot Travel
Center#393 DRAFT permit 2010.doc; NC0086053 Pilot Travel Center box 2010.doc;
NC0086053 Pilot Travel Center#393 map.ppt; 86053 a cover page 2010.doc; NC0086053
4-28-09.pdf; NC0086053 2-25-10.pdf
Hi Charles,
Here are my comments for the permit renewal for NC0086053 Pilot Travel Center.
Attached are the two most recent inspections and facility cover page.
Here's what I would suggest for the draft permit:
Supplement to permit cover page: (see attachment)
Continue to operate:
0.025 MGD extended aeration concrete plant consisting of: 5,000 gallon flow equalization
basin with dual alternating 0.5 HP pumps and manual bar screen; six 5,000 gallon aeration
basins with dual 549 cfm blowers providing diffused air; two rectangular 5200 gallon (78 sq
ft each) clarifiers with skimmers and sludge returns; 5000 gallon aerobic digestor; tablet
chlorinator; 875 gallon chlorine contact chamber; tablet dechlorinator; and 500 gallon
dechlorination / post aeration chamber.
Everything else looks good.
ARO recommends renewal of this permit.
Thanks,
Wanda
Wanda Frazier
Email: Wanda.FrazierPncdenr.gov
North Carolina Department of
Environment and Natural Resources
Asheville Regional Office
Division of Water Quality
Surface Water Protection Section
2090 US 70 Highway
Swannanoa, NC 28778
Switchboard: 828-296-4500 x 4662
Direct line: 828-296-4662
Fax: 828-299-7043
1
Current NC NPDES Workload
November 1, 2010
Individual Permits- 1264
MAJOR Permits- 239
• Municipals-
• Industrial- 66 7
MINOR Permits- 1025
• Municipal- 124
• Industrial- 159
• 100% Domestic- 487
• GW Remediation- 37
• WTPs- 218
General Wastewater Permits- 5 GPs covering 1715 COCs
• NCG50- Non-contact cooling water- 186 COCs, expires 7/31/2012
• NCG51- Groundwater remediation- 140 COCs- expires 9/30/2011
• NCG52- Sand Dredging- 47 COCs- expires 7/31/2012
• NCG53- Fish Pack/Rinse/Farm- 82 COCs- expires 7/31/2012
• NCG55- Single family residence- 1260 COCs- expires 7/31/2012
Upcoming Topics of Interest:
• Pickle chloride variances- January 2011
• Triennial Review/Proposed switch to Dissolved Metals
• Cape Fear Permitting- renewals begin early 2011- largest basin with 218
permits including 57 Majors (24% of total).
• Nutrients- Falls Lake, Proactive Regs
• Pesticide GP scheduled for April 2011
•
Facility information
NPDES permit#: NC0086053 Haywood County
Facility name: Pilot Travel Centers LLC -
Pilot Travel Center# 393 WWTP
WWTP class: Il
WWTP type: 0.025 MGD extended aeration concrete plant with:
5,000 gallon flow equalization basin with dual
alternating 0.5 HP pumps and manual bar screen;
six 5,000 gallon aeration basins with dual 549 cfm
blowers providing diffused air; two rectangular
5200 gallon (78 sq ft each) clarifiers with
skimmers and sludge returns; 5000 gallon
aerobic digestor; tablet chlorinator; 875 gallon
chlorine contact chamber; tablet dechlorinator;
and 500 gallon dechlorination / post aeration
chamber.
Annual Average Flow: 0.003 MGD (3 year ave. - 2007-2010)
Collection System: < 12 connections
Development: Commercial service station with 60 employees.
Sludge Management: Commercial hauler (Mike's Septic Service) to the
Town of Waynesville's WWTP.
Facility location: 3712 Crabtree Rd.; Waynesville, NC 28786
(1-40 Exit 24 to Hwy 209; northwest of Clyde)
Responsible official: Alan J. Fass, P.G. (authorized representative)
Project Manager— Dynamis Inc.
PO Box 50636; Knoxville, TN 37950
" - also: Joey Cupp, Environmental Manager
Pilot Travel Centers LLC
Physical address: 5508 Lonas Road; Knoxville, TN 37909-3221
(Email: joey.cupp@pilottravelcenters.com)
Environmental matters: Canna Jones; Dynamis, Inc.; 3707 Henson Road;
Knoxville, TN 37921
NPDES PERMIT APPLICATION - SHORT FORM C - WTP •
For discharges associated with water treatment plants
• 1001 provides a punishment by a fine of not more than$25,000 or imprisonment not more than 5 ypars,(it)3oth,..,
for a similar offense.)
. . N3tyk
) 4. • 4
...1* -!%7:1;.
.•
ff.t. •••• •: ;:"
•
•
tt. • Itrfif)4 .
f 4‘• '.;
!"1'."•t.).":.'1,..•
1 ,17
41 I.: • `••: •
- 1..f? 9/11711V telk : -
!74.
!"!
•:.'".2 • 1.‘".`:...1••[•': • •1. kik )
.
‘ •
7-•;) •• • •-• tge';, -T.
:
-^
, • . .1.21 ,14t4tik. -
.,-...!?••.‘-ir
•••4 ,•'/•. ).'"•)$.,..
:A-
•C.' • • : 11Vfl(I
y. .:• yrxo
•
Page 4 of 4 C-WTP 03/05
•
•
•
Phone numbers
865-588-5422 Alan Fass — Dynamis Inc.- in Knoxville
865-588-6857 " - fax
865-588-7488 Joey Cupp — PTC - in Knoxville
865-297-1752 " - fax
865-588-5422 Canna Jones — in Knoxville
865-588-6857 " - fax
828-627-8611 Scott Vreeland or Nathan Schook — mgrs on-site
800-213-4035 Environmental Inc. (toll-free) — ORC & Lab Contr.
828-293-9396 " - Kristi Leis — office
828-586-0800 " - fax (lab: Anthony Tyrona & Steve)
828-506-9450 Mark Teague - cell
828-226-7784 JoeDavid Hall - cell
828-342-0340 Dale Wike - cell
Operator information
ORCs: Mark Fredrick Teague — Grade II — Cert. # 10920
JoeDavid Matthew Hall — Grade II — Cert. # 993269
Dale Howard Wike — Grade II — Cert. # 27314
Mailing address: Env. Inc.; PO Box 954; Cullowhee, NC 28723
Location address: 50 West Sylva Shopping Area; Sylva, NC 28779
Email: environmentalinc a@aol.com
Permit information
Date issued: 12-1-2006
Expiration date: 1-31-2011
New permit expiration: 1-31-2016
Stream information
Stream & river basin: Stingy Branch; French Broad River Basin
Sub-basin: 04-03-05
Hydrologic Unit Code: 06010106
Quad: Clyde
Grid: E 7 SW
Stream classification:C
Drainage area sq mi: 2.3
Ave stream flow cfs: 3 cfs
Instream Waste Conc.: no data
Wake Forest Hwy 98 F
`ilk / A
J
UT to Rocky Branch
(flows west)
rl
IN
Outfall
(drains west
00
Ernest L Briggs Property
6206 Old Kemp Road, NC 27703
Receiving Stream: LfT to Rocky Branch [27-7-(2)] Sub -Basin: 03-04-01
Stream Class: WS-IV; NSW, CA Drainage Basin: Neuse River
Latitude: 35,961258' Longitude: 78.747611 °
State Grid/ USGS Quad: D23NE / SE Durham. NC
A
/
ME
Facility
Location
not to scale
North NPDES General COC NCG551102
Durham Count
•
Summer 7Q10 cfs: 0.54
Winter 7Q10 cfs: 0.86
30Q2 cfs: 1.19
Other information
Directions: 1-40 West to Hwy 209 (Exit 24); Go north on
Hwy 209. The site is located immediately on the
right. The WWTP is located behind the station.
NEUSE RIVER BASIN
Name of Stream Subbasin Stream Index Number Map Number Class
Yellow Marsh Branch (Yellow Swamp) NEU12 27-54-5-3-(2) F26SE8 WS-IV;NSW
Yellow Marsh Branch (Yellow Swamp) (Durham Lake) NEU12 27-54-5-3-(1) F26SE8 WS-IV,B;NSW
. .
Page 23 of 23 2010-11-20 07:23:54
ASHEVILLE
E
CITIZEN-TIMES
VOICE OF THE MOUNTAINS•CITIZEN-TIMES.com
AFFIDAVIT OF PUBLICATION
SS.
BUNCOMBE COUNTY
Public Notice a S.
North CareClinamE ronin D6 unMNag t
ia11rbiii ecc s r NORTH CAROLINA
Notice ofr intent to Issue a NPDES
rt . Wastewater Permit
Co is th proposes�to issue a'NPD Sgt' Before the undersigned, a Notary Public of said County and
Cwoammis on
watoer discharge permit to the person(s) listed
b ' State, duly commissioned,qualified and authorized by law
Written comments regarding the proposed pe
mit wHll be accepted until 30 days after the pub to administer oaths,personally appeared Elyse Giannetti,
sh date 0f this notice. The Director of the N
Division of Water Quality (DWQ) mayhold •
public [rearing s�roufd there be a significant de who,being first duly sworn, deposes and says: that she is
gree of public merest Please malt comments
a d/or information reque to DWQ at the
a above address. interesteel persons mar vis, the Legal Billing Clerk of The Asheville Citizen-Times,
yie at 512 N.Salisbu Street, Rale N•
toe review Information on rltle. ACditionsinfo
rDration On NPDES permits and this notice ma engaged in publication of a newspaper known as The
rbeorg/web/wn�sour ,wnpdes/cahlendar orn�by
calling(919)8b7r/ Asheville Citizen-Times,published, issued, and entered as
Buncomber2County Board of Education rc . first class mail in the City of Asheville, in said County and
M drdVe Schiil In�Bu c C uonty; this rpe
ed
discharge is treated dpmestic waste • State; that she is authorized to make this affidavit and
ter to Cane CreeK.French Broad River Basin.
The Town of Spruce Pine requested renewal q" sworn statement; that the notice or other legal
rrnit Nce:or y 3 for sprruce Pine wwrP I
ed municipal wasstewater"fo dorth ToesR , advertisement, a true copy of which is attached hereto, was
French Broad River Basin.
Pilot Travel Centers, Inc. requested renewal o• published in The Asheville Citizen-Times on the
NPDES permit NCOOR6OS3 for PII s Travel Cente 14th treateH.aywote County. Inas Trag��harg:. following date: November 14 , 2010. And that the said
treatded wastewater tnto StF c re
Brerona ffeec�Raiiver Basin. Currently ammon n
$alchlori'neca'ewate glualitylhnitednd total resid newspaper in which said notice,paper, document or legal
NC DOT requested renewal of N00024805 for th• advertisement was published was, at the time of each and
i-40 Welcome Center/ie�t Area WWTP In Ha
wood County. This facility discharges treat-•
wastewater to i the Pigeon River / Fm every publication, a newspaper meeting all of the
Broad River Basin. Currently, no parameters
are water quality limited
Ever rreen Foundation requirements and qualifications of Section 1-597 oft e
WV/ r2quested 5aitei�Centee
���pppppermit NC0032361 for The Bat
Into R i Viand C County. Facility discharge General Statues of North Carolina and was a qualified
Into R hiar Creek./French,Broad River Basin
sIdarpnc nitrogen, fecal cVIrf and total re
sidualchrlorinearewequestetityeinetedi. newspaper within the meaning of Section 1-597 of the
Sam' Mart Inc. requested renews of NPDES
ppeem,�t a 199 for the ac Illys :Marge
,tart ge5 General Statues of North Carolina.
treated waste County. Fac littsy discharge
treated wastewater into the PTgein River
French Broad River Basinn. Current y rro ..
r rr nester are water t�u m c invited.
e Nat oral Park ery ce requested renewal o
NPDES permit
permit wastewater
fore Mount Pisgah
,.-
treated
road Riv Basin. Dissrilv�P'ds Pisga
h
aalty dF fecal l Signed this 15th day of November,2010
collltooromodare water quality iiml edt d. n
Dive' permi nNC00 573 1 four ttee BetheleSSchto�eo
[WWrBtro FaCciillit dischargesn � ttreatedRiwwa tewaa to
Currently, total i;,�rti l chlorinGe and fecal co )--es,-�r,�� /�_
Iform are water uuality limited.
November 1 2010 - 7875 (signatur of person making affidavit)
Sworn to and subscribed before me the 15th day of
Nove r ber�110.
,tary Pu lic)
1°II ;III>k -----.
My Co mission expires the 5th day of October, 2013�Y�M�
(828)232-5830 (828)253-5092 FAX NOTAR
14 O.HENRY AVE. I P.O.BOX 2090 I ASHEVILLE,NC 28802 I (800)800-4204
caPUBLIC V•
rv�Err ,, +,
''''wa'''ge%
10 I I I Mb Mb 4111
ill •r■/NUJtuft
■ ■�■
�
P.O. Box 50636
Knoxville, TN 37950
Phone: (865) 588-5422
Fax: (865) 588-6857
August 3,2010
Mrs. Dana Sprinkle
NC DENR/DWQ/Point Source Branch
1617 Mail Service Center
Raleigh,NC 27699-1617
RE: NPDES Permit Renewal
NPDES Permit#NC0086053
Pilot Travel Center#393
3712 Crabtree Rd.
Waynesville, Haywood County,NC 28726
Sent via: USPS CERTIFIED MAIL# 7007 0710 0001 3785 8910
Dear Mrs. Sprinkle:
Please find enclosed the following documents per your agency's request:
• One original and two copies of NPDES Application for Permit Renewal—Form A.
• Written documentation showing delegated authority for Dynamis, Inc. (an authorized
representative of Pilot)to prepare the renewal package.
• One signed original and two copies of a narrative description of the sludge management
plan for the facility.
In addition,on July 22-23,2010,the following repair and routine maintenance items were
performed on the WWTP,in order to increase aeration treatment and improve the levels of
ammonia in the treated effluent:
1. Installed new belts on the blowers.
2. Changed out oil in the blowers.
3. Greased the motors and blowers.
4. Repaired the 2" line at the Equalization tank where the water is pumped up to the first flow
splitter box.
1
•
5. Improved aeration at each of the aeration tanks by increasing diffuser drops to two per tank.
Upon completion of the repairs,the WWTP was turned back on and was operating normally.
If you have any questions or require additional information,please contact me at 865-588-5422
Ext. 208.
Sincerely,
abrAto
Alan J. Foss,P.G.
Project Manager
Dynamis, Inc.
enclosures
cc: Joey Cupp,Environmental Manager, Pilot Travel Centers LLC, 5508 Lonas Rd.,
Knoxville, TN 37909
2
•
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters<1.0 MGD
Mail the complete application to:
N. C. DENR / Division of Water Quality / NPDES Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
'NPDES;Permit INCOO$(i053
- = - -
If.you are completing this. TA
form in computer use the. B,key,or the up,�down arrows.to,movefrom:one.:
field't+d'the next'Tcnihc3ck'thebozes;'cli k your mou`se on top of the box. Otheiuicse,please print or tape,.
1. Contact Information:
Owner Name lUOT TQAVE C6Nricts Lt-C
Facility Name 1,;lot Travel Ce tAtr3 Lc it 3/3
Mailing Address 550,3 Lo►i.u.s T2d.
City kerVi
State / Zip Code TN' 37c 1 o el
Telephone Number (g95) 588. 114 SS' -
Fax Number (81o5) cfri— ! 15.
e-mail Address l3Cl • Gu pp C toi-tiviweicailhers,cop4
2. Location of facility producing discharge: 0
Checlhee if sante address as.above ❑
Street Adss or State Road.t,
City ® . All: . �. ..
State / Zip Code S : DENR WAr.? 1 Y
�. CH
County KR Wood .
3. Operator Information:
Name of the firm, public organization or other entity that operates the facility. (Note that this is not
referring to the Operator in Responsible Charge or ORC)
Name 17i Lo-r TeAv E t-
Mailing Address 550$ LO n.aS 12,51-
City
2,51.City ec ri Ue�
State / Zip Code TAI .3- 9 0'9
Telephone Number (EID5) 5.Sg 17423
Fax Number (1410)
lot 3 Form-D05/08
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters <1.0 MGD
4. Description of wastewater:
Facility Generating Wastewater(check all that apply):
Industrial ❑ Number of Employees'
Commercial Number of Employees• -: ;; (.O over 9.'sW 1
Residential /
0 Number of Homes
School 0 Number of Students/Staff
Other 0 Explain:
Describe the source(s) of wastewater(example: subdivision, mobile home park, shopping centers,
restaurants, etc.):
Population served: 2 /YT N C , �lubJ
e t
5. Type of collection system
Separate(sanitary sewer only) 0 Combined (storm sewer and sanitary sewer)
6. Outfall Information:
Number of separate discharge points
Outfall Identification numbers) C) I '
Is the outfall equipped with a diffuser? IXYes 0 No
•
7. Name of receiving stream(s) (Provide a map showing the exact location of each outfallk
SH95 , Ir�;r1C,h $roa.ol.. .12 ver'
8. Frequency of Discharge: 1g Continuous 0 . Intermittent
If intermittent:
Days per week discharge occurs: Duration:
9. Describe the treatment system
List all.installed components, including capacities,provide design removal for BOD, TSS, nitrogen and
phosphorus. If the space provided is not sufficient,attach the description of the treatment system in a
separate sheet of paper.
see ca- ckeJ 5orp feitteKt.
•
2 of 3 FomrD 05/08
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters <1.0 MGD
10. Flow Information:
Treatment Plant Design flow 0•025 MGD•• �• -•
Annual Average daily flow 0.003 MGD (for the previous 3 years)
Maximum daily flow 0. --MGD (for the.previo4s-3years)_: •
11. Is this facility located on-Indian country? -
❑ Yes g•No •
12. Effluent Data
Provide data for the parameters listed.Fecal Coliform, Temperature and pH shall be grab samples,for all other
parameters 24-hour composite sampling shall be used If more than one analysis is reported,report daily maximum
and monthly average.If only one analysis is reported,report as daily maximum.
Parameter Daily Monthly• Units of
Maximum Average Measurement
Biochemical Oxygen Demand (BODS) ,/
2S l�, 0. ref( fs.5,g.)3.11 tl�-
Fecal Coliform 5502 5 rb dc90 l�,��6,V j 10.5 cF I oo m
Total Suspended Solids 'rj • 2 .I it-9
/
l� 3 . � �Fl� 3 2 �9 �� � } •fYl G
Temperature (Summer) at i7.55 ot'f Pis 0'1l 23.2 C g 1)99.
Temperature (Winter) 18.t%(D,�j awe q . A .3)3,0 7 . C e[9i(/g'
pH fpirr.. G.Srl.0 7,0 V :7,2 7.s 7.4 -
•
13. List all permits,construction approvals and/or applications:
Type .Permit Number Type .._ Permit Number
Hazardous Waste(RCRA) NESHAPS (CAA)
UIC (SDWA) • Ocean Dumping(MPRSA)
NPDES W c,o0g 6 053 Dredge or fill(Section 404 or CWA)
PSD (CAA) Other .
Non-attainment program(CAA)
•
14. APPLICANT CERTIFICATION • • _ .r:
•
I certify that I am familiar with the information contained in the application and that to the
best of my knowledge and belief such information is true, complete, and accurate. •
-bny-trbnlyunfed Manat3c(
Printed name or erson Signing - Title
�- 2 C�
Si••IfA•p ' Date
i.f ardina General S 143-215.6(bX2)states:Any person who knowingly makes any false statement representation, or certification in any
application,record,report plan,or other document files or required to be maintained under Article 21 or regulations of the Environmental Management
Commission implementing that Article, or who falsifies, tampers with, or knowingly renders inaccurate any recording or monitoring device or method
required to be operated or maintained under Article 21 or regulations of the Environmental Management Commission implementing that Article,shall be
guilty of a misdemeanor punishable by a fine not to exceed$25,000,or by imprisonment not to exceed six months,o by both. (18 U.S.C.Section 1001
provides a punishment by a fine of not more than$25,000 or imprisonment not more than 5 years,or both,for a similar offense.)
3 of 3 Form-D 05108
[ pi ' ci1
A VEL CENTERS
LLC
I, Joey Cupp, a Cognizant Official for Pilot Travel Centers LLC,do give Dynamis, Inc, an
Authorized Representative,permission to construct and submit the renewal application for Pilot
Travel Center#393, Haywood County,NPDES Permit NC0086053.
/
,i /��
_7- Z // b
Ale—App, 'n ' o"- taj,,,i'ager Date
The Customer Driven Company
Pilot Travel Centers LLC•P.O.Box 10146•Knoxville,TN 37939-0146•(865)588-7488
Dynamls, Inc.
P.O. Box 50636
Knoxville, TN 37950
Phone: (865) 588-5422
Fax: (865) 588-6857
Narrative Description of the Sludge Management Plan for:
Pilot Travel Center# 393-WWTP
3712 Crabtree Rd.
Waynesville,NC 28726
It is my understanding that the sludge from this waste water treatment plant(WTPP)is wasted
from the clarifier as process control dictates necessity. Sludge is collected in a dedicated tank for
thickening. Mike Smith, a North Carolina licensed waste hauler, hauls the thickened sludge to
the local WWTP for disposal.
See attached system specification sheet for information on the wastewater treatment plant
(WWTP).
Respectfully Submitted,
& &
Alan J. Fass
Dynamis, Inc.
• .
, • 1
SYSTEM SPECIFICATIONS
PLANT PHASE PROPOSED
ACTUAL AND DESIGN CONDITIONS
AVERAGE FLOW, GPD 25.000
AVERAGE FLOW, GPM 17.36
PEAK INSTANTANEOUS INPUT FLOW, GPM (EQUALIZATION PUMPS) 20
MAXIMUM EQUALIZED PLANT INPUT, GPM (EQUALIZATION PUMPS) 34.72
5 DAY BOD, MG/L FOR INITIAL FLOWS OF 15,000 GPD 310
5 DAY BOO, MG/L FOR FUTURE FLOWS OF 10,000 GPD 200
FLOW EQUALIZATION
CAPACITY, GALLONS 5,000
NO. OF PUMPS, I00% ALTERNATING 2
CIRCULATION RATE, GPM 50
TDH REQUIRED, FT 15
MOTOR HORSEPOWER, EACH PUMP .50
VOLTAGE/PHASE 115/1
SPLITTER BOX WEIR ADJUSTMENT 0-65 GPM
AERATION
CAPACITY, GALLONS 30,000
DOD LOADING RATE, LE/KCF(INITIAL PLUS FUTURE) 13.86
DETENTION TIME BASED ON ADF, HRS • • 28.8
BOD REMOVAL REQUIRED, LB/DAY! 49.91
AIR REQUIRED, CF/LB BOD(GLUMRB) 2100
FINAL SETTLING 5,200
TOTAL CAPACITY, GALLONS (EACH BASIN) 78
SURFACE AREA, SF (EACH BASIN) 320
MAXIMUM SURFACE SETTLING RATE, GPD/SF(ONE BASIN)
WEIR LENGTH, FT(EACH BASIN) 9.33
MAXIMUM WEIR OVERFLOW RATE, GPD/LF(ONE BASIN) 2,680
SLUDGE RETURN RATE, MINIMUM, GPM 13
SLUDGE RETURN RATE, MAXIMUM, GPM 26
EXISTING
AEROBIC SLUDGE DIGESTER
CAPACITY, GALLONS 5,000
PERSONS SERVED EQUIVALENT 222
LOADING, CF PER CAPITA 3.00
CHLORINE FEED & CONTACT CHAMBER
CAPACITY OF EACH CHAMBER, GALLONS 875
'PEAK FLOW RATE, GPM(EQUALIZATION PUMPS) 20
DETENTION TIME AT PEAK FLOW RATE, MINUTES 43.75
DESIGN CHLORINE DOSAGE, LB/DAY 1.67
DECHLOR FEED & CONTACT CHAMBER
CAPACITY OF CHAMBER, GALLONS • 500
PEAK FLOW RATE, GPMCEQUALIZATION PUMPS) 20
DETENTION TIME AT PEAK FLOW RATE, MINUTES 28.8
DESIGN Nc1 SO3 DOSAGE, LB/DAY ; 0.24
AIR SUPPLY •
No. OF OPERATING BLOWERS 1
No. OF STANDBY BLOWERS 1
PRESSURE, PSI I 4
FLOW RATE EACH,BLOWER, CFM ; 549
MOTOR HORSEPOWER, EACH BLOWER 15
VOLTAGE/PHASE 230/3
. ►
FACT SHEET FOR EXPEDITED PERMIT RENEWALS
This form must be completed by Permit Writers for all expedited permits which do not require
full Fact Sheets. Expedited permits are generally simple 100%domestics(e.g.,schools,mobile
home parks,etc)that can be administratively renewed with minor changes,but can include
facilities with more complex issues(Special Conditions,303(d)listed water,toxicity testing,
instream monitoring,compliance concerns).
Basic Information for Expedited Permit Renewals
Permit Writer/Date Charles H. Weaver— 11/3/2010
Permit Number NC0086053
Facility Name Pilot Travel Center#393 WWTP
Basin Name/Sub-basin number French Broad/04-03-05
Receiving Stream Stingy Branch
Stream Classification in Permit C
Does permit need Daily Max NH3 limits? No—already present
Does permit need TRC limits/language? No—already present
Does permit have toxicity testing? No
Does permit have Special Conditions? No
Does permit have instream monitoring? No
Is the stream impaired(on 303(d)list)? No
Any obvious compliance concerns? No
Any permit mods since last permit? No
New expiration date 1/31/2016
Comments received on Draft Permit?
Most Commonly Used Expedited Language:
• 303(d)language for Draft/Final Cover Letters:"Please note that the receiving stream
is listed as an impaired waterbody on the North Carolina 303(d)Impaired Waters List.
Addressing impaired waters is a high priority with the Division,and instream data will
continue to be evaluated. If there is noncompliance with permitted effluent limits and
stream impairment can be attributed to your facility,then mitigative measures may be
required".
• TRC language for Compliance Level for Cover Letters/Effluent Sheet Footnote:
"The facility shall report all effluent TRC values reported by a NC certified laboratory
including field certified. However,effluent values below 50µg/1 will be treated as zero
for compliance purposes."
2u0dwnd ai;das 3o 3diaaag