SUBJECT: Compliance Inspection Report
Warsaw Sanitation Trailer Wash
Non -discharge Permit No. WQ0023310
Duplin County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Warsaw Sanitation
Trailer Wash on 1/31/2023. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0023310. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the
inspection and therefore, a response to this inspection report is not required.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
Sincerely,
EDocuSigned by:
Toµ "T�n�cl. �cOA, For
7F141E73B6F3456...
Morelia Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Michael Norris — electronic copy
Derek Brown — electronic copy
Upload to Laserfiche
D_E QZ� North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
910.796.7215
DocuSign Envelope ID: F1 7B67DC-BC7B-4FA1 -9676-1 CE4828B2A1 D
Dr QZ North Carolina Department of Environmental Quality I Division of Water Resources
_
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
oeo.ammemi�m.m o,i� /`� 910.796.7215
DocuSign Envelope ID: F17B67DC-BC7B-4FA1-9676-10E482862A1D
Compliance Inspection Report
Permit: WQ0023310 Effective: 09/17/19 Expiration: 11/30/24 Owner: Murphy -Brown LLC
SOC: Effective: Expiration: Facility: Warsaw Sanitation Trailer Wash
County: Duplin 2822 Hwy 24 W
Region: Wilmington
Warsaw NC 28398
Contact Person: Amy J Elmore Title: Env. Compliance Phone: 910-293-3434
Directions to Facility:
From Warsaw, travel west on Hwy 24, turn right onto Old Courthouse Road. Facility is located on the left
System Classifications: S1,
Primary ORC: Bradley Devone Herring Certification: 988691 Phone: 910-385-8878
Secondary ORC(s):
On -Site Representative(s):
On -site representative Michael Leon Norris 910-284-0435
Related Permits:
Inspection Date: 01/31/2023 Entry Time 09:OOAM Exit Time: 10:OOAM
DocuSigned by:
Primary Inspector: Helen I PerezElD645B4A39694BE...
D S' d Phone: 910-796-7387
Secondary Inspector(s): � DouSi�9 nTed by:
E-T7011'41E73B6F3456...
Ati lY�affl oti 2/2/2023
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions
Treatment Flow Measurement -Water Treatment Record Keeping
Use Records
Treatment Lagoons End Use -Irrigation Treatment Influent Pump Station
Treatment Flow Measurement Wells
(See attachment summary)
Page 1 of 5
DocuSign Envelope ID: F1 7B67DC-BC7B-4FA1 -9676-1 CE4828B2A1 D
Permit: WQ0023310 Owner - Facility: Murphy -Brown LLC
Inspection Date: 01/31/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Warsaw Sanitation Trailer Wash WWTF was conducted on January 31, 2023. The
purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified
in Permit WQ0023310. Michael Norris and Derek Brown were present during the inspection.
This facility is a 2-bay, "clean" trailer wash facility with a SWECO solid -liquid mechanical separator and an oil -water
separation unit. From the headworks, influent flows to a 2,573,134 gallon clay -lined lagoon and then irrigated on
approximately 32 acres of spray fields consisting of Fescue and row crops. The facility estimates flow by water usage and is
limited to 7,300,000 gallon per any consecutive 12 months. As of November 2022, the facility reported a flow of 2,796,200
gallons. Since the current NDMR form does not calculate flow as gallons per year, please be conscientious when calculating
and reporting the 12-month rolling total gallons on the NDMR.
There are plans to remove and reseed the Fescue on Zones 1-5 this spring. The Waste Utilization Plan has not had any
recent changes. Operation/maintainence records were available for review and organized and complete. A review of records
showed 1 NOD was issued for a freeboard limit violation.
MW-1 R and MW-3R, located around the row crop Fields A throuh H, have had Nitrate limit exceedances for the majority of
this permit cycle. Very little application on the fields nearest to those MWs, Field A and H, has occured. The Wilmington
Regional Office continues to monitor the trends.
The facility is compliant with Non -Discharge Permit WQ0023310. Please review the comment sections of the inspection
report for more details.
Page 2 of 5
DocuSign Envelope ID: F1 7B67DC-BC7B-4FA1 -9676-1 CE4828B2A1 D
Permit: WQ0023310 Owner - Facility: Murphy -Brown LLC
Inspection Date: 01/31/2023 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Reuse (Quality)
❑
Infiltration System
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Activated Sludge Spray, HR
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
❑
Single Family Drip
❑
Lagoon Spray, LR
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑
Comment: No comment.
Treatment Influent Pump Station Yes No NA NE
Is the pump station free of bypass lines or structures? 0 ❑ ❑ ❑
Is the general housekeeping acceptable? ❑ ❑ ❑
Are all pumps present? ❑ ❑ ❑
Are all pumps operable? ❑ ❑ ❑
Are floats/controls operable? ❑ ❑ ❑
Are audio and visual alarms available? 0 ❑ ❑ ❑
Are audio and visual alarms operational? ❑ ❑ ❑
# Are SCADA/Telemetry alarms required? ❑ ❑ ❑
Are SCADA/Telemetry available? ❑ ❑ ❑
Are SCADA/Telemetry operational? ❑ ❑ 0 ❑
Comment: Wastewater from the wash drains flows to a mechanical separator system that removes grit,
trash, and shavings. The solids removed are emptied into a dumpster and hauled to the
landfill. An oil -water separation unit is also used. The audible and visual alarms were
operational when the high level float was pulled during the inspection.
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Yes No NA NE
❑❑■❑
Page 3 of 5
DocuSign Envelope ID: F1 7B67DC-BC7B-4FA1 -9676-1 CE4828B2A1 D
Permit: WQ0023310 Owner - Facility: Murphy -Brown LLC
Inspection Date: 01/31/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Comment:
Treatment Flow Measurement -Water Use Records Yes No NA NE
Is water use metered? 0 ❑ ❑ ❑
Are the daily average values properly calculated? 0 ❑ ❑ ❑
Comment: The facility has a 7,300,000 gallons per year limit over any consecutive 12 months, and is
estimated per the permit monitoring requirements.
Treatment Flow Measurement -Effluent
Yes No NA NE
Is flowmeter calibrated annually?
❑
❑ 0 ❑
Is flowmeter operating properly?
❑
❑ 0 ❑
Does flowmeter monitor continuously?
❑
❑ 0 ❑
Does flowmeter record flow?
❑
❑ 0 ❑
Does flowmeter appear to monitor accurately?
❑
❑ 0 ❑
Comment:
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are flow rates less than of permitted flow?
❑ ❑ ❑
Are application rates adhered to?
❑ ❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑ ❑ ❑
Are all samples analyzed for all required parameters?
❑ ❑ ❑
Are there any 2L GW quality violations?
❑ ❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑ ❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑ ❑ ❑
# Are PAN records required?
❑ ❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑ ❑ ❑
Do lab sheets support data reported on NDMR?
❑
❑ ❑
Do lab sheets support data reported on GW-59s?
❑
❑ ❑
Are Operational and Maintenance records present?
❑ ❑ ❑
Were Operational and Maintenance records complete?
❑ ❑ ❑
Page 4 of 5
DocuSign Envelope ID: F1 7B67DC-BC7B-4FA1 -9676-1 CE4828B2A1 D
Permit: WQ0023310 Owner - Facility: Murphy -Brown LLC
Inspection Date: 01/31/2023 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Has permittee been free of public complaints in last 12 months? 0 ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? 0 ❑ ❑ ❑
Comment: Operation/maintenance logs included field irrigation, freeboard and crop yield records as well
as work orders for maintenance of the trailer wash facility. The soil analysis is completed
annually by the Permittee, although it is only required every 3 years. The required monitoring
parameters are reported from the NC Department of Agriculture Division's Waste Analysis
Report. The monitoring wells are sampled and analyzed by Envirochem Lab. MW-1 R and
MW-3R, located around the row crop Fields A throuh H, have had Nitrate limit exceedances for
the majority of this permit cycle. Very little application on the fields nearest to those MWs, Field
A and H, has occured. The Wilmington Regional Office continues to monitor the trends.
End Use -Irrigation
Yes No NA NE
Are buffers adequate?
0
❑ ❑ ❑
Is the cover crop type specified in permit?
❑
❑ ❑
Is the crop cover acceptable?
❑ ❑ ❑
Is the site condition adequate?
❑ ❑ ❑
Is the site free of runoff / ponding?
❑ ❑ ❑
Is the acreage specified in the permit being utilized?
❑ ❑ ❑
Is the application equipment present?
❑ ❑ ❑
Is the application equipment operational?
❑
❑ ❑
Is the disposal field free of limiting slopes?
❑ ❑ ❑
Is access restricted and/or signs posted during active site use?
❑ ❑ ❑
Are any supply wells within the CB?
❑
❑ ❑
Are any supply wells within 250' of the CB?
❑
❑ ❑
How close is the closest water supply well?
❑
❑ ❑
Is municipal water available in the area?
❑
❑ ❑
# Info only: Does the permit call for monitoring wells?
❑ ❑ ❑
Are GW monitoring wells located properly w/ respect to RB and CB?
❑ ❑ ❑
Are GW monitoring wells properly constructed, including screened interval?
❑
❑ ❑
Are monitoring wells damaged?
❑
0 ❑ ❑
Comment: Fields appeared to be well maintained. The irrigation equipment
was last calibrated on
5/2/2022. The 3 MWs are all capped and appear to be in good
condition. The lagoon's
freeboard was 61 inches.
Page 5 of 5