HomeMy WebLinkAboutNCG500669_Compliance Evaluation Inspection_20151001*)
� 4JL
NCDENR
North Carolina Department of Environmental Quality
Pat McCrory
Governor
October 1, 2015
Winston Salem/Forsyth County Utilities Division
Attn: Ron Hargrove, Utilities Director.
P.O. Box 2511
Winston Salem, NC 27101
Donald R. van der Vaart
Secretary
Subject: Compliance Evaluation Inspection
NPDES Permits: NCG500669, Swann (Northwest) Water Treatment Plant
Forsyth County
Dear Mr. Hargrove:
1. Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the
Division) conducted compliance evaluation inspections (CEI) at the subject facility on September 30,
2015. The assistance and cooperation of Bill Brewer and Harry Hull was greatly appreciated. Inspection
reports are attached for your records and the inspection findings are summarized below.
General
2. The facility is located at 2800 River Ridge Road, in Winston Salem, Forsyth County, North Carolina. The
facility is authorized to discharge wastewater from the treatment works through outfall 001 to an unnamed
tributary (UT) of Bashavia Creek, which is currently classified as Class C waters in the Yadkin Pee -Dee
River basin. The wastewater treatment system consists of one equalization basin and two settling
lagoons with a sodium bisulfite dechlorination system. The waste stream consists of backwash water
from the water treatment system's filters and sludge from the water treatment system's sedimentation
basins.
Documentation & Monitoring Review
3. All required records were readily available, complete, and current. Discharge monitoring records for 2015
were reviewed and no discrepancies were noted.
Site Review
4. Filter backwash wastewater goes to the equalization basin, then to the lagoon(s), and is then discharged.
The sedimentation basin blowdowns (sludge) go directly to the lagoons for settling and are then
discharged. Wastewater is dechlorinated using sodium bisulfate before discharge. Decanted and dried
North Carolina Division of Water Resources, Winston-Salem Regional Office
Location: 450 West Hanes Mill Road, Suite #300, Winston-Salem, North Carolina 27105
Phone: 336-776-98001 FAX: 336-776-97971 Customer Service;1-877-623.6748
Internet:v .nowaterquality.org -
An Equal Opportunity 1 Affirmative Action Employer
sludge from the lagoons is land applied on site as authorized by Permit WQ0031314. The effluent flow
meter was last calibrated on 9/16/2015. The site was very clean and no discrepancies or violations were
noted:
5. Please encourage your operators to continue their outstanding efforts in complying with all permit
conditions. Should you have any questions, please feel free to contact Mr. Boone or me at (336) 776-
9800.
Sincerely,
W. Corey Basinger
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Reports
cc: SWP — WSRO
Central Files
NPDES Unit
City of Winston Salem
Swann Water Treatment Plant
Attn: Bill Brewer and Harry Hull
2800 River Ridge Road
Pfafftown, NC 27040-8600
United States Environmental Protection Agency
Form Approved.
EPA Washington, D C. 20460
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fad Type
1 IN I 2 15 t 3 I NCG590003 I11 12 15/09/30 17 18 1 C I 19 Li I 201 I
211111 I I I I I I II I I I I I I I I I I I I I I I I I I I I I I I II I I III 166
Inspection Work Days Facility Self -Monitoring Evaluation Rating 31 QA -----------Reserved------------
I I I I I I I80
72 LN I 731 75L1
671 I 70L—I 71 LyDJ_L L L L LI
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include.
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number)
09:OOAM 15/09/30
15/02/01
P.W. Swann WTP
Exit Time/Date
Permit Expiration Date
River Ridge Rd
10:OOAM 15/09/30
19/07/31
Winston Salem NC 27103
Names) of Dinette Representalive(s)/Titles(s)/Phone and Fax Numbers)
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
James F Crump,2801 Griffith Rd Winston Salem NC 271036417//336-765-0165/
No
Section-C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit 0 Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program 0 Facility Site Review Effluent/Receiving Waters Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Names) and Signature(s) of Inspectors) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//336-776-9690/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
p� 7�P -p W2 1J5lRd i Ou Zs�.t
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#
NPDES yr/mo/day Inspection Type
31 NCG590003 I11 12 15/09/30 17 18 ICI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
1
Page# 2
Permit: NCG590003 Owner - Facility: P.W. Swann WTP
Inspection Date: 09/30/2015 Inspection Type: compliance Evaluation
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
M
❑
application?
Is the facility as described in the permit?
❑
❑
0
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
M
❑
❑
❑
Comment: None
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
M
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)?
0
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
M
❑
❑
❑
Is the chain -of -custody complete?
0
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
M
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
M
❑
on each shift?
Is the ORC visitation log available and current?
M
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
0
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Facility has copy of previous year's Annual Report on file for review?
❑
❑
0
❑
Comment: None
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? 0 ❑ ❑ ❑
Is flow meter calibrated annually? 0 ❑ ❑ ❑
Page# 3
Permit: NCG590003
Inspection Date: 09/30/2015
Flow Measurement - Effluent
Owner -Facility: P.W Swann WrP
Inspection Type: Compliance Evaluation
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ M ❑
Yes No NA NE
■ ❑ ❑ ❑
❑ ❑ ■ ❑
Page# 4