HomeMy WebLinkAboutNC0079821_Compliance Evaluation Inspection_20151116 (2)North Carolina Department of Environmental Quality
Pat McCrory Donald R. van der Vaart
Governor Secretary
November 16, 2015
Winston Salem/Forsyth County Utilities Division
Attn: Ron Hargrove, Utilities Director
P.O. Box 2511
Winston Salem, NC 27102-2511
Subject: Compliance Evaluation Inspections
NPDES Permits: NC0086011, Neilson Water Treatment Plant
NC0079821, RA Thomas Water Treatment Plant
Forsyth County
Dear Mr. Hargrove:
1. Ron Boone of the Winston-Salem Regional Office of the NC Division of Water Resources (DWR or the Division) conducted
compliance evaluation inspections (CEI) at the Neilson and RA Thomas water treatment plants on November 13, 2015. The
assistance and cooperation of Bill Brewer, Rodney Darr, and Kenneth Atkins was greatly appreciated. Inspection reports are
attached for your records and the inspection findings are summarized below.
NC0086011, NEILSON WATER TREATMENT PLANT
General
2. The facility is located at 5725 Frye Bridge Road, in Winston Salem, Forsyth County, North Carolina. The facility is authorized
to discharge wastewater from the treatment works through outfall 001 to an unnamed tributary (UT) of Muddy Creek, this
section of which is currently classified as Class C waters in the Yadkin Pee -Dee River basin. However, the wastewater
treatment system does NOT discharge. All wastewater is recycled through two wastewater treatment lagoons and one of the
raw water reservoirs. The wastewater is then treated through the potable water treatment system. The waste stream consists
of backwash water from the water treatment system's filters and sludge from the water treatment system's sedimentation
basins.
Documentation & Monitoring Review
3. All required records were readily available, complete, and current. There are no DMRs for review. The plant currently has a
waiver from submitting monthly DMRs because the plant recycles all wastewater and there is no discharge. The waiver is in
effect until the plant begins discharging again.
Site Review
4. Filter backwash wastewater is pumped to the easternmost raw water reservoir. Sedimentation basin blowdowns (sludge) go
to one of three waste lagoons and decant from that sludge is then also pumped to the easternmost raw water reservoir. All
wastewater is recycled through this process and then back through the potable water treatment system. As stated above,
there is currently no discharge from the waste treatment system. Decanted and dried sludge from the waste lagoons is land
disposed on the "Cooper Road Disposal Site", which is located a few miles from the water treatment plant.
The site was very clean and no discrepancies or violations were noted.
North Carolina Division of Water Resources, Winston-Salem Regional Office
Location: 450 West Hanes Mill Road, Winston-Salem, North Carolina 27105
Phone: 336-776-98001 FAX: 336-776-9797 \Customer Service; 1-877-623-6748
Internet: www.ncwaterquality.org
An Equal Opportunity 1 ARrmative Acton Employer
NC0079821, RA THOMAS WATER TREATMENT PLANT
General
5. All required records were readily available, complete, and current. Discharge monitoring reports for 2015 were reviewed and
no discrepancies were noted.
Site Review
6. Filter backwash wastewater goes directly to the equalization basin, then to the clarifier. The treated effluent from the clarifier
goes to a flume where it is measured and discharged. The sludge from the clarifier goes to the waste lagoons. Sedimentation
basin blowdowns (sludge) go directly to the waste lagoons. Decant from the waste lagoons goes to the equalization basin,
then to the clarifier. The effluent flow meter was last calibrated on September 16, 2015.
7. Please encourage your operators to continue their outstanding efforts in complying with all permit conditions. Should you have
any questions, please feel free to contact Mr. Boone or me at (336) 776-9800.
Sincerely,
Sherri V. Knight
Asst. Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Reports
cc: SWP — WSRO
Central Files
NPDES Unit
City of Winston Salem
Neilson Water Treatment Plant
Attn: Rodney Darr
5725 Frye Bridge Road
Clemmons, NC 27012
City of Winston Salem
RA Thomas Water Treatment Plant
Attn: Kenny Atkins
1201 South MLK Junior Drive
Winston Salem, NC 27107
United States Environmental Protection Agency
EPA Washington, D C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 6-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day - Inspection
1 IN 2 IS I 3 I_ NC0079821 111 12I 15/11/13 117
Type
18Isi
I I I I I
Inspector Fac Type
19H 201 I
21I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
I I I
�6
L I I I- I ` 6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA---------- -----Reserved------------
67I 1 70I 1 71 I I 72 I N I 73I I 174 79
I I I I
I I I I I I I80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
RA Thomas WTP
1201 Martin Luther King J
Winston Salem NC 27107
Entry Time/Date
10:30AM 15/11/13
Permit Effective Date
09/09/01
Exit Time/Date
11:30AM 15/11/13
Permit Expiration Date
14/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Kenneth Craig Atkins/ORC/336-784-7597/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Edward Nathaniel Davis,PO Box 2511 Winston Salem NC 271079998//336-784-7597/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program • Sludge Handling Disposal • Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Ron Boone WSRO WQ//336-776-9690/•
Date
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
,/6-- 4.4 - vim. / 4"-Ik,Q 4 ) i// (0 I IS
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type
31 NC007e821 11 121 15/11/13 117 18
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
Page# 2
Permit: NC0079621
Owner -Facility: RA Thomas WTP
Inspection Date: 11/13/2015 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ • ❑
application?
Is the facility as described in the permit? •❑ ❑ ❑
# Are there any special conditions for the permit? OM ❑ ❑
Is access to the plant site restricted to the general public? •❑ ❑ ❑
Is the inspector granted access to all areas for inspection? •❑ ❑ ❑
Comment: None
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: None
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other p'arameters(excluding field parameters) performed by a certified lab?
Yes No NA NE
• ❑ On
• ❑ OE
• ❑ ❑ ❑
• ❑ On
• ❑ On
•
•
•
•
•
• ❑ On
• ❑• ❑
❑•❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑•❑
Yes No NA NE
• ❑ DO
• ❑ DO
Page# 3
Permit: NCO019821
Owner - Facility: RA Thomas WTP
Inspection Date: 11/13/2015 Inspection Type: Compliance Evaluation
Laboratory
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: None
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
•
▪ •
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ •❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑• ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4