HomeMy WebLinkAboutNC0064726_Compliance Evaluation Inspection_20160321 (2)PAT MCCRORY
3;.
Governor
_DONALD R. VAN DER VAART
Secretary
Water Resources
ENVIRONMENTAL QUALITY S. JAY ZIMMERMAN
March 21, 2016 Director
Town of East Bend
Attn: Larry W. Adams, Mayor
108 West Main Street
East Bend, NC 27018
SUBJECT: Compliance Evaluation Inspection
East Bend Industrial Park Wastewater Treatment Plant
NPDES Permit: NCO064726
Yadkin County
Dear Mr. Adams:
Ron Boone of the Winston Salem Regional Office (WSRO) of the North Carolina Division of Water
Resources (DWR or the Division) conducted a compliance evaluation inspection of the East Bend Industrial Park
Wastewater Treatment Plant on March 17, 2016. The assistance and cooperation of Mark Matthews, Operator in
Responsible Charge (ORC), was greatly appreciated. An inspection report is attached for your records and the
inspection findings are summarized below.
The East Bend Industrial Park Wastewater Treatment Plant is located at the south end of Salem Trail, in
East Bend, Yadkin County, North Carolina, at approximate coordinates 36.211336e,-80.494283e. The Town of East
Bend is authorized to operate this 0.01 million -gallon -per -day (MGD) wastewater treatment plant, which consists of
extended aeration, settling, sludge holding, UV disinfection, and backup chlorination and dechlorination, and discharge
treated effluent from outfall 001 of said treatment works into an unnamed tributary to the Yadkin River, this section of
which is currently classified as Class WS-IV waters and is located in the Yadkin Pee -Dee River Basin.
SITE REVIEW
Mr. Boone reviewed the entire plant with Mr. Matthews. Everything was in good condition and well
maintained. Mr. Boone noted no discrepancies.
DOCUMENTATION REVIEW
Mr. Matthews had all required paperwork on hand. This includes discharge monitoring reports, laboratory
reports, chains of custody, operation and maintenance logs, operator visitation logs, etc. The only discrepancy Mr.
Boone noted was that the Town does not currently have a valid certification for the field lab parameters of pH,
temperature, and dissolved oxygen. This must be addressed immediately and the appropriate field lab certification
acquired by the Town. You may initiatethis process by contacting the Division's Laboratory Certification Branch. Please
call Gary Francies at 828-296A677 or Jason Smith at 828-296-4679. You may also go to their website at:
https://deg.nc.gov/about(divisions/water-resources/water•resources-datalwater-sciences-home-
page/laboratory-certification-branchlfield-lab-certification
The website tells you step by step how to acquire the required field laboratory certification. Please complete this as
soon as possible. Technically, all lab data acquired without the required field lab certification is non -reportable.
Therefore, in effect, you're not even taking those samples.
State of North Carolina I Environmental Quality I Water Resources
450 West Hanes Mill Road, Suite 300 [ Winston-Salem, North Carolina 27105
336 776 9800
There were no other discrepancies noted. Mr. Matthews is doing a good job operating and maintaining the
plant. Please keep up the good work in ensuring the plant is properly operated and maintained and meeting all the
terms and conditions of the permit. Please remember that violations of the permit are subject to enforcement actions
not to exceed $25,000 per day, per violation.
If you have any questions regarding the inspection or this letter, please do not hesitate to contact Mr. Boone
or me at 336-776-9800, Thank you for your cooperation in this matter.
Sincerely,
Sherri V. Knight, P.E.
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Report
CC: Central Files
NPDES Unit
WSRO/SWP Files
Town of East Bend
Attn: Mark Matthews, Operator in Responsible Charge
108 West Main Street
East Bend, NC 27018
United States Environmental Protection Agency
Form Approved.
EPA - Washington, D.C. 20460 -
OMB No. 2040-0057
Water Compliance Inspection Report
Approval expires8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 IN t 2 15 1 3 I N00064726 I11 12 16/03/17 17 18ICI 19I c I 201 I
2111111111111111111111111111111111111111111 Lj6
Inspection
Work Days Facility Self -Monitoring Evaluation Rating 31 CA ---------------Reserved----------
671
�_1 701LJ 71 72 LNJ 73I 174 75L J_LJ
80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
Entry Time/Date
Permit Effective Date
POTW name and NPDES permit Number) -
10:30AM 16/03/17
14/06/01
East Bend Industrial Park WVJiP
NO Hwy 67 E
Exit Time/Date
Permit Expiration Date
East Bend NO 27018
11:30AM 18/03/17
18/12l31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
Other Facility Data
Mark C Matthews/ORC/336-403-2171/
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Mark Matthews,108 W Main St East Bend NO 27018/1336-699-4481/
No
Section C: Areas Evaluated. During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenance Records/Reports
Self -Monitoring Program Sludge Handling Disposal Facility Site Review Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signatures) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone WSRO WQ//336-776-9690/
b
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are. obsolete.
Page#
NPDES yr/mo/day Inspection Type
3I. NCO064726 12 16/03/17 17 18 J.0 I.._ ...
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
1
Page# 2
Permit: NCO064726 Owner - Facility: East Bend Industrial Park VVVVTP
Inspection Dater 03/17/2016 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable 0 ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Permit
Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
❑
❑
i
- ❑
application?
Is the facility as described in the permit?
0
❑
❑
❑
# Are there any special conditions for the permit?
❑
0
❑
❑
Is access to the plant site restricted to the general public?
0
❑
❑
❑
Is the inspector granted access to all areas for inspection?
■
❑
❑
❑
Comment: None
Record Keeping
Yes No NA NE
Are records kept and maintained as required by the permit?
0
❑
❑
❑
Is all required information readily available, complete and current?
0
❑
❑
❑
Are all records maintained for 3 years (lab. reg. required 5 years)? _
❑
❑
❑
Are analytical results consistent with data reported on DMRs?
0
❑
❑
❑
Is the chain -of -custody complete? -
❑
❑
❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
0
❑
❑
❑
Has the facility submitted its annual compliance report to users and DWQ?
❑
❑
0
❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator
❑
❑
❑
on each shift?
Is the ORC visitation log available and current?
M
❑
❑
❑
Is the ORC certified at grade equal to or higher than the facility classification?
0
❑
❑
❑
Is the backup operator certified at one grade less or greater than the facility classification?
M
❑
❑
❑
Is a copy of the current NPDES permit available on site?
0
❑
❑
❑
Page# 3
Permit: NCO064726 owner -Facility: East Bend Industrial Park WWTP
._ Inspection Date: 03/17/2016 Inspection Type: compliance Evaluation
Record Keepina Yes No NA NE
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ 0 ❑
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: None
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: None
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ■ ❑
I[��f•7:F�:1
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
■ ❑ ❑ ❑
M ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4
Permit: NCO064726 Owner -Facility: East Bend Industrial Park VVWTP
Inspection Dater 03/17/2016 Inspection Type: Compliance Evaluation _
Equalization Basins
Yes No NA NE
Is the basin aerated?
N
❑
❑
❑
Is the basin free of bypass lines or structures to the natural environment?
0
❑
❑
❑
Is the basin free of excessive grease?
0
❑
❑
❑
Are all pumps present?
0
❑
❑
❑
Are all pumps operable?
0
❑
❑
❑
Are float controls operable?
E
❑
❑
❑
Are audible and visual alarms operable?
E
❑
❑
❑
# Is basin size/volume adequate?
0
❑
❑
❑
Comment: None
Secondary Clarifier
Yes No NA NE
Is the clarifier free of black and odorous wastewater?
E
❑
❑
❑
Is the site free of excessive buildup of solids in center well of circular clarifier?
❑
❑
0
❑
Are weirs level?
■
❑
❑
❑
Is the site free of weir blockage?
N
❑
❑
❑
Is the site free of evidence of short-circuiting?
N
❑
❑
❑
Is scum removal adequate?
0
❑
❑
❑
Is the site free of excessive floating sludge?
0
❑
❑
❑
Is the drive unit operational?
❑
❑
N
❑
Is the return rate acceptable (low turbulence)?
N
❑
❑
❑
Is the overflow clear of excessive solids/pin floc?
0
❑
❑
❑
Is the sludge blanket level acceptable? (Approximately''%, of the sidewall depth)
❑
❑
❑
Comment: None
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Yes No NA NE
Ext. Air
Diffused
■o❑❑
❑
❑
■
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
•
❑
❑
❑
Page# 5
Permit: NCO064726 Owner -Facility: East Bend Industrial Park VVWrP
Inspection Date: 03/17/2016 Inspection Type: compliance Evaluation
Aeration Basins Yes No NA NE
Is the DO level acceptable?(1.0 to 3.0 mg/1) 0 ❑ ❑ ❑
Comment: None
Disinfection - UV
Yes No NA NE
Are extra UV bulbs available on site?
M
❑
❑
❑
Are UV bulbs clean?
- 0
❑
❑
❑
Is UV intensity adequate?
0
❑
❑
❑
Is transmittance at or above designed level?
0
❑
❑
❑
Is there a backup system on site?
IN
❑
❑
❑
Is effluent clear and free of solids?
0
❑
❑
❑
Comment: None
Pumps-RAS-WAS
Yes No NA NE
Are pumps in place?
0
❑
❑
❑
Are pumps operational?
0
❑
❑
❑
Are there adequate spare parts and supplies on site?
0
❑
❑
❑
Comment: None
Laboratory
Yes No NA NE
Are field parameters performed by certified personnel or laboratory?
❑0
❑
❑
Are all other parameters(excluding field parameters) performed by a certified lab?
0
❑
❑
❑
# Is the facility using a contract lab?
0
❑
❑
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/_ 0.2 degrees?
❑
❑
❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
❑
❑
❑
Comment: Town does not have field laborartory certification
Influent Sampling
Yes No NA NE
# Is composite sampling flow proportional?
❑
❑
0
❑
Is sample collected above side streams?
0
❑
❑
❑
Is proper volume collected?
-0
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
Page# 6
Permit: NCO064726 Owner - Facility: East send Industrial Park WWrP
Inspection Date: 03117/2G16.. Inspection Type: Compliance Evaluation.
_.
.
Influent Sampling
Yes No NA NE
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is sampling performed according to the permit?
0
❑
❑
❑
Comment: None
Effluent Sampling
Yes No NA NE
Is composite sampling flow proportional?
❑
❑
N
❑
Is sample collected below all treatment units?
0
❑
❑
❑
Is proper volume collected?
❑
❑
❑
Is the tubing clean?
❑
❑
0
❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees
❑
❑
❑
Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
❑
❑
❑
representative)?
Comment: None
Upstream IDownstream Saulolina Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, and IN ❑ ❑ ❑
sampling location)?
Comment: None
Page# 7