Loading...
HomeMy WebLinkAboutNC0038709_Compliance Evaluation Inspection_20151012North Carolina Department of Environmental Quality Pat McCrory Governor October 12, 2015 Mr. Tommy Spicer Wilkes County Schools 613 Cherry Street North Wilkesboro, NC 28659 SUBJECT: Compliance Evaluation Inspection Roaring River Elementary WWTP NPDES Permit # NCO038709 Wilkes County Dear Mr. Spicer: Donald R. van der Vaart Secretary A Compliance Evaluation Inspection was performed by George Smith on October 7, 2015. Mr. Tommy Spicer, ORC was present at this inspection. The inspection is comprised of an overall evaluation of the facilities equipment, and capability to produce an effluent discharge that meets NPDES permit limits. Permit Your NPDES permit became effective on October 1, 2013 and expires on September 30, 2018. The eDMR requirement is included in the permit under Section A.(3). Wilkes County Schools did register for eDMR, and is working on eDMR submission. Please remember that both paper and eDMR submission are required at this time. Records & Reports Mr. Spicer maintains an operator log, which documents sampling, analysis, Operations & Maintenance, and his visitations. The records are well organized and maintained in a file cabinet. All are in excellent order. Facility Site Review The surface sandfilter was covered with pea gravel. The distribution lines were in good condition. The bed appeared to be level and working properly. The effluent pump station showed that both pumps were operational, and float controls were working. The vegetation around the pump station was high. 450 W Hanes Mill Rd., Suite 300, Winston-Salem, NC 27105 Phone: 336-776-98001Internet: www.ncdenr.gov An Equal Opportunity i. AffirmaGva Action Employer— Made in part by recycled paper Flow Measurement The flow is measured using a digital counter installed on the dosing tank. The tank discharges 1236 gal/flush. Laboratory Wilkes County Schools is an approved field certified lab (# 5406). The pH calibration is performed with a SensIon 156, using a three-point calibration method (buffers 4, 7, 10), and a midrange check at 7.0. The calibration is recorded. Temperature is measured with the pH meter and is calibrated, documented, and is traceable to NIST. Effluent/Receiving Waters The effluent in the pump station was clear, which discharges into the Yadkin River, Class WS-IV waters. Operations & Maintenance The facility is satisfactorily operated and maintained. Mr. Tommy Spicer, Grade I is the ORC; Mr. Stacy Higgins, Grade I, Back-up ORC; Mr. Dalon Durham, Grade II. Self -Monitoring Program A review of the monthly self -monitoring reports from January 2015 through July 2015 showed no limit violations. The compliance evaluation inspection is satisfactory. If you have any questions please contact George Smith or me at (336) 776-9800. Sincerely, W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ r 11%1yczj United States Environmental Protection Agency Form Approved. EPA Washington, D C 20460 OMB No. 2040-0057 Water Compliance Inspection Report Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type 1 1,,, ( 2 Is I 3 I NCO038709 I11 121 15/10/07 I17 18 L,j 19 1 c I 201 I 211111 I I I I I � �1 11 I I I I I I I I I I I I I I I I I I I I I II I I III 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------Reserved------------ 67I 72 LnJ 73174 75I I I I �I 7071 itJ 80 Section 6: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include Entry Time/Date Permit Effective Date POTW name and NPDES permit Number) 12:32PM 15/10/07 13/12/01 Roaring River Elementary School 283 White Plains Rd Exit Time/Date Permit Expiration Date Roaring River NC 28669 12:45PM 15/10/07 18/09/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data /// Thomas J Spicer/ORC/336-651-4010/ Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Bangle Speaks,613 Cherry St North Wilkesboro NC 286591/336-667-2021/3366679688 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Operations & Maintenance E Records/Reports Self -Monitoring Program Facility Site Review Effluent/Receiving Waters Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date George S Smith WSRO WQ//336-776-9700/ o�©(,f' Epp ��,,/p t Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date 4e'4 --� It-'6EZp . Pu/2 - 60/?o 12.d 67� es ' EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# Permit: NCO038709 Owner - Facility: Roaring River Elementary School Inspection Date: 10/07/2015 Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? 0 ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ 0 ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: operates visually Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ 0 ❑ application? - Is the facility as described in the permit? 0 ❑ ❑ ❑ # Are there any special conditions for the permit? 0 ❑ ❑ ❑ Is access to the plant site restricted to the general public? 0 ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? 0 ❑ ❑ ❑ Comment: eDMR requirement Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? 0 ❑ ❑ ❑ Is all required information readily available, complete and current? 0 ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? 0 ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? M ❑ ❑ ❑ Is the chain -of -custody complete? 0 ❑ ❑ ❑ Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCS Are DMRS complete: do they include all permit parameters? ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ 0 ❑ (If the facility is = or> 5 MGD permitted flow) Do they operate 24/7 with a certified operator ❑ ❑ 0 ❑ on each shift? Is the ORC visitation log available and current? 0 ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classificagon!? 0 ❑ ❑ ❑ „ Is the backup operator certified at one grade less or greater than the facility classification? 0 ❑ ❑ ❑ Is a copy of the current NPDES permit available on site? ❑ ❑ 0 ❑ Page# 3 Permit: NCO038709 Owner -Facility: Roaring River Elementary School Inspection Date: 10/07/2015 Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Facility has copy of previous year's Annual Report on file for review? 0 ❑ ❑ ❑ Comment: permits are ini the maintenance office Septic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational? ❑ ❑ M11 Is septic tank pumped on a schedule? 0 ❑ ❑ ❑ Are pumps or syphons operating properly? M ❑ ❑ ❑ Are high and low water alarms operating properly? 0 ❑ ❑ ❑ Comment: Sand Filters (Low rate) Yes No NA NE (If pumps are used) Is an audible and visible alarm Present and operational? ❑ ❑ 0 ❑ Is the distribution box level and watertight? 0 ❑ ❑ ❑ Is sand filter free of ponding? 0 ❑ ❑ ❑ Is the sand filter effluent re -circulated at a valid ratio? ❑ ❑ 0 ❑ # Is the sand filter surface free of algae or excessive vegetation? 0 ❑ ❑ ❑ # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) ❑ ❑ 0 ❑ Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ 0 ❑ Is sample collected below all treatment units? 0 ❑ ❑ ❑ Is proper volume collected? 0 ❑ ❑ ❑ Is the tubing clean? ❑ ❑ 0 ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees ❑ ❑ 0 ❑ Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type 0 ❑ ❑ ❑ representative)? Comment: grab Samples On ice Page# 4