HomeMy WebLinkAboutNC0078115_Compliance Evaluation Inspection_20150223 NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Resources
Water Quality Regional Operations
Pat McCrory Donald R. van der Vaart
Governor Secretary
February 23, 2015
RECEIVEDIDENRIDWR
Aqua North Carolina, Inc.
Attn: Thomas J. Roberts, President MAR f'r A115
202 Mackenan Court woe Quality
Cary, NC 27511 pennettiv Seo`
SUBJECT: Compliance Evaluation Inspection
Greystone Subdivision Wastewater Treatment Plant
NPDES Permit: NC0078115
Forsyth County
Dear Mr. Roberts:
Ron Boone of the Winston Salem Regional Office (WSRO) of the North Carolina Division of Water
Resources (DWR or the Division) conducted a compliance evaluation inspection of the Greystone Subdivision
Wastewater Treatment Plant on February 10, 2015. The assistance and cooperation of Sam Pegram, Operator in
Responsible Charge (ORC), was greatly appreciated. An inspection report is attached for your records and the
inspection findings are summarized below.
The Greystone Subdivision Wastewater Treatment Plant is located off the north end of Pine Creek Road
in Kernersville, Forsyth County, North Carolina, at approximate coordinates 36.167662°, 80.086436°. Aqua North
Carolina, Inc is authorized to operate this 0.032 million-gallon-per-day (MGD) wastewater treatment plant, which
consists of a bar screen, an influent pump station, an equalization basin,dual extended aeration basins and clarifiers,
a sludge digester, tablet chlorination and dechlorination, and a flow meter, and discharge treated effluent from outfall
001 of said treatment works, which is located approximately 25 feet east of the treatment works at approximate
coordinates 36.167670°, 80.086130°,to Belews Creek, which is currently classified as Class C waters and is located
in the Roanoke River Basin.
SITE REVIEW
Mr. Boone reviewed the entire plant with Mr. Pegram. No discrepancies or violations were noted. The
plant appears to be operated and maintained very well.
DOCUMENTATION REVIEW
Mr. Pegram had all required documentation for the inspection and everything was complete and current.
Mr. Boone found no discrepancies or violations. Mr. Pegram has done an excellent job of documenting his operation
and maintenance of the plant.
North Carolina Division of Water Resources,Winston-Salem Regional Office
Location:450 West Hanes Mill Road,Suite#300,Winston-Salem,North Carolina 27105
Phone:336-776-98001 FAX:336-776-97971 Customer Service;1-877-623-6748
Internet:www.ncwaterquality.org
An Equal Opportunity.Affirmative Action Employer
Please keep up the excellent work in ensuring the Greystone Subdivision Wastewater Treatment Plant is
properly operated and maintained and meeting all the terms and conditions of the permit. Please remember that
violations of the permit are subject to enforcement actions not to exceed$25,000 per day,per violation.
If you have any questions regarding the inspection or this letter, please do not hesitate to contact Mr.
Boone or me at 336-776-9800.Thank you for your cooperation in this matter.
Sincerely,
.,,i4tS1(64-4°"4-4r--1
W.Corey Basinger
Regional Supervisor
Water Quality Regional Operations
Division of Water Resources
Attachments:
1. BIMS Inspection Report
CC:
Central Files
NPDES Unit
WSRO/SWP Files
Aqua North Carolina, Inc.
Attn:Sam Pegram,Operator in Responsible Charge
152-B Furlong Industrial Drive
Kemersville, NC 27284
• 3
United States Environmental Protection Agency Form Approved.
EPA Washington,D.C.20480 OMB No.2040-0057
Water Compliance Inspection Report Approval expires 8-31-98
Section A:National Data System Coding(i.e.,PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 l�, 2 [ I 3 NC0078115 111 12 I 15/02/10 117 18 i I 19 1 . I 201 I
lid
Li
J LJ 1=1 LJ
21111111 IIIII111 [ 1111111111 I IIIII IIIII111111 r
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA Reserved
671 1 70 U 71 U 72 1 731 1 174 75I 11 1 1 1 1 (80
•
Section B:Facility Data LJ
Name and Location of Facility Inspected(For Industrial Users discharging to POTW,also include Entry Time/Date Permit Effective Date
• POTW name and NPDES permit Number) 10:00AM 15/02/10 12/05/01
Greystone Subdivision WWfP
Lot 74 Creek Bed Rd Exit Time/Date • Permit Expiration Date
11:00AM 15/02/10 • 17/02/28
Kemersville NC 27284
Name(s)of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) Other Facility Data
111
Samuel E.Pegram/ORC/704-489-9404/
Name,Address of Responsible Official/Title/Phone and Fax Number
Contacted
Dustin K Metreveon,NCSR 1802 Salisbury NC 28144//704-788-9497/7047888006
No
Section C:Areas Evaluated During Inspection(Check only those areas evaluated)
• Permit II Flow Measurement • Operations&Maintenance • Records/Reports
II Self-Monitoring Program • Sludge Handling Disposal II Facility Site Review II Effluent/Receiving Waters
• Laboratory
Section D:Summary of Finding/Comments(Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s)and Signature(s)of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron BooneZ 23 1 WSRO M/336-771-4967/
45.
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3(Rev 9-94)Previous editions are obsolete.
Page# 1
NPDES yr/mo/day Inspection Type 1
31 NC0078115 111 121 15/0.2110
1
17 18 ,_
Section D:Summary of Anding/Comments(Mach additional sheets of narrative and checklists as necessary)
Please refer to the attached inspection summary letter.
•
•
•
•
Paget. 2
Permit NC0078115 Owner-Facility: Greystone Subdivision WW1P
Inspection Dab: 02/10/2015 Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new 0 0 • 0
application?
Is the facility as described in the permit? U 0 0 0
#Are there any special conditions for the permit? 0 I 0 0
Is access to the plant site restricted to the general public? • 0 0 0
Is the inspector granted access to all areas for inspection? • 0 0 0
Comment: None
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • 0 0 0
Is all required information readily available,complete and current? • 0 0 0
Are all records maintained for 3 years(lab. reg.required 5 years)? • 0 0 0
Are analytical results consistent with data reported on DMRs? • 0 0 0
Is the chain-of-custody complete? • 0 0 0
Dates,times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs •
Are DMRs complete:do they include all permit parameters? • 0 0 0
Has the facility submitted its annual compliance report to users and DWQ? 0 0 • 0
(If the facility is=or>5 MGD permitted flow)Do they operate 24/7 with a certified operator 0 • 0 0
on each shift?
Is the ORC visitation log available and current? • 0 0 0
Is the ORC certified at grade equal to or higher than the facility classification? • 0 0 0
Is the backup operator certified at one grade less or greater than the facility classification? U 0 0 0
Is a copy of the current NPDES permit available on site? I 0 0 0
Facility has copy of previous years Annual Report on file for review? 0 0 • 0
Comment: None
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? • 0 0 0
Are all other parameters(excluding field parameters)performed by a certified lab? U 0 0 0
Pages 3
Permit NC0078115 Owner-Facility: Greystone Subdivision VWVTP
Inspection Date: 02/10/2015 Inspection Type: Compliance Evaluation
Laboratory, Yes No NA NE
#Is the facility using a contract lab? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0
Celsius)?
Incubator(Fecal Coliform)set to 44.5 degrees Celsius+/-0.2 degrees? 0 0 0 •
Incubator(BOD)set to 20.0 degrees Celsius+/-1.0 degrees? 0 0 0 •
Comment: None
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • 0 0 0
Is sample collected below all treatment units? • 0 0 0
Is proper volume collected? • 0 0 0
Is the tubing clean? • 0 0 0
#Is proper temperature set for sample storage(kept at less than or equal to 6.0 degrees • 0 0 0 •
Celsius)?
Is the facility sampling performed as required by the permit(frequency,sampling type • 0 0 0
representative)?
Comment: None
Upstream/Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit(frequency,sampling type,and • 0 0 0
sampling location)?
Comment: None
Pump Station -Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • 0 0 0
Is the wet well free of excessive grease? • 0 0 0
Are all pumps present? • 0 0 0
Are all pumps operable? • 0 0 0
Are float controls operable? • 0 0 0
Is SCADA telemetry available and operational? • 0 0 0
Is audible and visual alarm available and operational? • 0 0 0
Comment: None
Equalization Basins Yes No NA NE
•
Page# 4
• Permit NC0078115 Owner-Facility: Greystone Subdivision WWTP
Inspection Date: 02/10/2015 inspection Type: Compliance Evaluation
Equalization Basins • Yes No NA NE
Is the basin aerated? • 0 0 0
Is the basin free of bypass lines or structures to the natural environment? • 0 0 0
• Is the basin free of excessive grease? • 0 0 0
Are all pumps present? • 0 0 0
Are all pumps operable? • 0 0 0
Are float controls operable? • 0 0 0
Are audible and visual alarms operable? • 0 0 0
#Is basin size/volume adequate? • 0 0 0
Comment: None
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical 0
Are the bars adequately screening debris? • ❑ 0 0
Is the screen free of excessive debris? • 0 0 0
Is disposal of screening in compliance? • 0 0 0
Is the unit in good condition? • 0 0 0
Comment: None
Aeration Basins Yes No NA NE
Mode of operation Ext.Air
Type of aeration system Diffused
Is the basin free of dead spots? • 0 0 0
Are surface aerators and mixers operational? 0 0 • 0
Are the diffusers operational? • 0 0 0
Is the foam the proper color for the treatment process? • 0 0 0
Does the foam cover less than 25%of the basin's surface? U 0 0 0
Is the DO level acceptable? U 0 0 0
Is the DO level acceptable?(1.0 to 3.0 mg/I) • 0 0 0
Comment: None
Secondary Clarifier Yes No NA NE
Page# 5
Permit NC0078115 Owner-Facility: Greystone Subdivision VW 1p
Inspection Date: 02/10/2015 Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • 0 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? 0 0 • 0
Are weirs level? • 0 0 0
Is the site free of weir blockage? • 0 0 0
Is the site free of evidence of short-circuiting? • 0 0 0
Is scum removal adequate? • 0 0 0
Is the site free of excessive floating sludge? • 0 0 0
Is the drive unit operational? 0 0 • 0
Is the return rate acceptable(low turbulence)? • 0 0 0
Is the overflow clear of excessive solids/pin floc? • 0 0 0
Is the sludge blanket level acceptable?(Approximately 1/4 of the sidewall depth) 0 0 0 •
Comment: None
•
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational? • 0 0 0
Are the tablets the proper size and type? • 0 0 0
Number of tubes in use? 4
Is the level of chlorine residual acceptable? 0 0 0 •
Is the contact chamber free of growth,or sludge buildup? • 0 0 0
Is there chlorine residual prior to de-chlorination? 0 0 0 •
Comment: None
De-chlorination Yes No NA NE
Type of system? Tablet
Is the feed ratio proportional to chlorine amount(I to I)? • 0 0 0
Is storage appropriate for cylinders? 0 0 • 0
#Is de-chlorination substance stored away from chlorine containers? • 0 0 0
Are the tablets the proper size and type? • 0 0 0
Comment: None
Are tablet de-chlorinators operational? • 0 0 0
Number of tubes in use? 4
Comment: None
Page# 6
•
Permit NC0078115 Owner-Facility: Greystone Subdivision VWVIP
inspection Date: 02/10/2015 inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? • 0 0 0
Are pumps operational? • 0 0 0
Are there adequate spare parts and supplies on site? • 0 0 0
Comment: None
Flow Measurement-Effluent Yes No NA NE
#Is flow meter used for reporting? • 0 0 0
Is flow meter calibrated annually? • 0 0 0
Is the flow meter operational? • 0 0 0
(If units are separated)Does the chart recorder match the flow meter? • 0 0 0
Comment: None
•
Effluent Pine Yes No NA NE
Is right of way to the outfall properly maintained? • 0 0 0
Are the receiving water free of foam other than trace amounts and other debris? • 0 0 0
If effluent (diffuser pipes are required) are they operating properly? 0 0 • 0
Comment: None
Aerobic Digester Yes No NA NE
Is the capacity adequate? • 0 0 0
Is the mixing adequate? • 0 0 0
Is the site free of excessive foaming in the tank? • 0 0 0
#Is the odor acceptable? U 0 0 0
#Is tankage available for properly waste sludge? • 0 0 0
Comment: None
Operations&Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 0
Does the facility analyze process control parameters,for ex: MLSS,MCRT,Settleable • 0 0 0
Solids,pH,DO,Sludge Judge,and other that are applicable?
Comment: None