HomeMy WebLinkAboutNC0029297_Wasteload Allocation_19890106NPDES WASTE LOAD ALLOCATION
PERMIT NO.: NCO() �`i'V7%
FACILITY NAME: �"' ed F°"rd `9k 5e-h°0/
Facility Status: (EEXWTV PROPOSED
(circle one)
Permit Status: REREIVEWlie MODIFICATION UNPERMITTED NEW
(circle one)
Major WIROI
Pipe No: 001
Design Capacity (MGD):
Domestic (X of Flow): (op
Industrial (X of Flow):
Comments:
a o2
RECEIVING STREAM: Pe/4/ Creej(
Class:
Sub -Basin- 63-OI-35
Reference USGS Quad: E ✓3 SF
County.
(please attach)
Regional Office: As Fa Ra Wa WI WS
(circle one)
Requested By:
g/Aviaa,.
/
Prepared By: COiLt
Reviewed By:
j
Date: /%0Y
6t Date: �1 �r
Date: / - 6
sy
Modeler
Date Rec.
Ioj s
p,8
4-911 I
Drainage Area (mil)-/� Avg. Streamflow (cfs)- ,'16)
7Q10 (cfs) (, Winter 7Q10 (cfs) 30Q2 (cfs)
Toxicity Limits: IWC % (circle one) Acute / Chronic
lnstream Monitoring:
Parameters £ (1, l empe`(/tre, (pndUc/t rr ) ed Arno
Upstream `,L. Location ��.bave cl/SC 1(1 ye pi
Downstream Location '-ic,2°°1 be%O1SCL C pf
`►-eevenC�' u.�eK/yv r,)su�rtrx¢V( Apr)
r� / on4-n9-uY,Y/((/V V mow)
Effluent
Effluent Summer Winter
Characteristics
BOD5 (mg/I) �'•
NHs N (mg/1)
D.O. (mg/I) (p
TSS (mg/I)v
F. Col. (/ 100m1) / Od 0
pH (SU) (j - q
RCb'- n-r to fra fr m.00O (yi rliacho cit ()j& t, a r ,
A__,Qtyk_itzeiv4 A,Lt_ce-nktio 7-j„,,a,(161)LorrED
Comments:-` -1 —e `Yt")Y�vt ''Y'�J rx2vt� k1 Q
1,0-lk �,�,wi
9h np,4-7 9
Comments:-` -1 —e `Yt")Y�vt ''Y'�J rx2vt� k1 Q
1,0-lk �,�,wi
9h np,4-7 9
~
~% `
t No. :4897
Permit Number
Facility Name
Type of Waste
Status
Receiving Stream
Stream Class
Subbasin
County
Regional Office
Requestor
Date of Request
Quad
.
WASTELOAD ALLOCATION APPROVAL FORM
NC0029297
FRED T. FOARD HIGH SCHOOL
DOMESTIC
EXISTING
UT POTT CREEK
C
030835
CAT()
LULA HARRIS
10/5/88
E13SE
Drainage Area
Average Flow
Summer 7010
Winter 7010
3002
RECOMMENDED EFFLUENT LIMITS
Wasteflow (mgd): 0.02
5-Day DOD (mg/l>: 30
Ammonia Nitrogen (mg/l):
Dissolved Oxygen (mg/1): 6
TSS (mg/l): 30
Fecal Coliform (#/100ml): 1000
PH (SU): 6-9
:
:
:
� -
R����y������
_~~"_' ' '.,�
^^
�8N �
on."
P£[ /: `� ^
�
MONITORING
(sq mi)
(cfs)
(cfs)
(cfs)
(cfs)
»r
.
Upstream (Y/N): Y Location: ABOVE DISCHARGE POINT
Downstream (Y/N): Y Location: ~ 200' BELOW DISCHARGE POINT
.045
.06
0.0
0.0
0.0
---------------------------------- COMMENTS ----------------------------
RECOMMEND INSTREAM MONITORING FOR DO, TEMPERATURE, FECAL COLIFORM,
AND CONDUCTIVITY
FREQUENCY: WEEKLY FOR SUMMER (APR-OCT) AND MONTHLY FOR WINTER (NOV-MAR)
RECOMMNED REMOVAL OF DISCHARGE WHEN AN ALTERNATIVE BECOMES AVAILABLE.
INSTREAM MONITORING REQUIREMENT MAY BE DROPPED WHEN THE FACILITY AGREES,
IN WRITING, TO A SCHEDULE FOR REMOVAL OF THEIR POINT -SOURCE DISCHARGE.
SEE ATTACHED MEMO CONCERNING INSTREAM MONITORING REQUIREMENTS.
Recommended by
Reviewed by:
ech. Support Supervisor
Regional Supervisor _
Permits & Engineering __
RETURN TO
TECHNICAL
Date _
�
*m
�
!�Ny� 1�A�
w"'"�° '�"^
SERVICES BY .
Date
Date
MEMORANDUM
To:
From:
Through:
Subject:
DIVISION OF ENVIRONMENTAL MANAGEMENT
December 7, 1988
Rex Gleason
Carla Sanderson (4
David Vogt 0 lc/
Trevor Clements
Fred T. Foard High School
NPDES NO. NC0029297 Catawba
Instream Monitoring Data
County
On October 5, 1988, Technical Support received a WLA request
for the renewal of the Fred T. Foard High School NPDES permit.
The permit requirements for this facility include in -stream moni-
toring for temperature and D.O. Central Files does not have any
instream monitoring data. This data is necessary to evaluate the
existing limits and ensure they are protecting our water quality
standards. Therefore, it is important that the Region inform
this facility of the need to adhere to the monitoring require-
ments of their permit.
If you have any questions please contact me at (919) 733-5083,
ext. 514.
CC:
Steve Reid
WLA File
Central Files
F-1,40LI .. Foai-d f4-91( xticnI
c,c)-= OZG ajd
ia/%88
030835
UT Po-14 Creek
-oarc 14--I.i3h 56(100I
& (,0 = 0.0D vm d 3a q r.) ' 8 &_)
(�q = O.b(D c-Es
'(ow c
soaa= o
State of North Carolina
Department of Natural Resources and Community Development
Mooresville Regional Office
James G. Martin, Governor
S. Thomas Rhodes, Secretary
Albert F. Hilton, Regional Manager
DIVISION OF ENVIRONMENTAL MANAGEMENT
December 20, 1988
Mr. Mark Bumgardner, Director
Maintenance Department
Catawba County Schools
Post Office Box 1000
Newton, North Carolina 28658
Subject:
In -Stream Self -Monitoring
Data
Fred T. Foard High School
NPDES Permit No. NC 0029297
Catawba County, NC
Dear Mr: Bumgardner:
The permit requirements for the subject facility include
in -stream monitoring for BOD5, Fecal Coliform, Dissolved Oxygen
and pH. Our files do not contain any in -stream monitoring data,
and this information is necessary to evaluate the impact of the
discharge on the receiving stream. Therefore, it is important
that you initiate a sampling program that will provide for
compliance with your NPDES Permit requirements.
If you have anv questions regarding this matter, please
feel free to contact Mr. Phelps or me.
Sincerely,
D. Rex Gleason, P. E.
Water Quality Regional Supervisor
Ms. Carla Sanderson, Tech. Support Unit
RGP:se
RECE IV:
DEC 2 _t 1988
TECHNICAL SERVICES BRANCH
919 North Main Street, P.O. Box 950, Mooresville, N.C. 28115-0950 • Telephone 704-663-1699