HomeMy WebLinkAboutNC0023281_Permit Modification_20080211ATA
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Michael F. Easley, Governor William G. Ross, Jr., Secretary
Coleen H. Sullins, Director
February 11, 2008
Mr. Dirk Cody
Tapoco Lodge, Inc.
14981 Tapoco Road
Robbinsville, NC 28771
Subject: Modification of NPDES Permit NC0023281
Tapoco Lodge & Village WWTP
Graham County
Dear Mr. Cody:
Division staff in the NC DENR Asheville Regional Office have requested a minor modification to the
subject permit. They correctly noted that the sample type for BOD and Total Suspended Solids should be
Grab, not Composite. This permit modification corrects the sample types in section A. 1. of the permit. No
other changes to the permit have been made.
Please find enclosed the revised effluent page, which should be inserted into your permit. The old page
may then be discarded. All other terms and conditions contained in the original permit remain unchanged
and in full effect. This permit modification is issued under the requirements of North Carolina General
Statutes 143-215.1 and the Memorandum of Agreement between North Carolina and the U.S.
Environmental Protection Agency.
If any parts, measurement frequencies or sampling requirements contained in this permit modification
are unacceptable to you, you have the right to an adjudicatory hearing upon written request within thirty
(30) days following receipt of this letter. This request must be a written petition conforming to Chapter 150B
of the North Carolina General Statutes, filed with the Office of Administrative Hearings (6714 Mail Service
Center, Raleigh, North Carolina 27699-6714). Unless such demand is made, this decision shall be final and
binding.
If you have any questions concerning this permit modification, please contact Charles Weaver of the
NPDES Unit at (919) 733-5083, extension 511.
Sincerely,
<I �� 1
Coleen H. Sullins
cc: Central Files
Asheville Regional Office / Janet Cantwell
NPDES Unit
1617 Mail Service Center, Raleigh, North Carolina 27699-1617
512 N. Salisbury St., Raleigh, North Carolina 27604
Phone: 919-733-5083 / FAX 919-733-0719 / www.ncwaterquality.org
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
NorthCarolina
Naturally
4
a.
Permit NC00023281
A. (1.) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
During the period beginning on the effective date of this permit and lasting until expiration, the Permittee is
authorized to discharge from outfall 001. Such discharges shall be limited and monitored by the Permittee as
specified below:
PARAMETER
LIMITS
MONITORING REQUIREMENTS
Monthly
Average
Daily
Maximum
Measurement
Frequency
Sample Type
Sample Location
Flow
0.02 MGD
Continuous
Recorder
Influent or Effluent
BOD, 5-day (20°C)
30.0 mg/L
45.0 mg/L
Weekly
Grab
Effluent
Total Suspended Solids
30.0 mg/L
45.0 mg/L
Weekly
Grab
Effluent
Temperature (°C)
Weekly
Grab
Effluent
Footnotes:
1. The temperature of the effluent shall not cause the temperature of the receiving stream to increase more than
0.5°C. In no case shall the effluent temperature cause the ambient temperature of the receiving stream to exceed
20°C.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
NC:0023281: Tapoca Lodge, Graham County: Composite Sampling
Subject: NC0023281: Tapoca Lodge, Graham County: Composite Sampling
From: Janet Cantwell <Janet.Cantwell@ncmail.net>
Date: Thu, 07 Feb 2008 14:54:39 -0500
To: Charles Weaver <charles.weaver@ncmail.net>
Hi Charles ---This facility has had composite sampling on their last two permits. A permit in 1998 had
grab sampling. We don't have any draft permits in the file for comparison.
This facility has a design flow of 0.02 MGD but has an average flow of about 0.002 MGD. Since
composite sampling is required with design flows over 30,000 GPD, why does Tapoca Lodge have
composite sampling? Can we have it removed? Thanks in advance for your help ---Janet
Janet Cantwell - Janet.Cantwell@ncmail.net
North Carolina Dept. of Environment and Natural Resources
Asheville Regional Office
Division of Water Quality - Water Quality Section
2090 US Highway 70
Swannanoa, NC 28778-8211
Tel: 828-296-4500
Fax: 828-299-7043
Link to the NC Division of Water Quality:
http://www.ncwaterquality.org/
Link to NPDES Programs & Compliance Info: (DMRs, Annual Report, Etc.):
http://h2o.enr.state.nc.us/NPDES/
Link to Technical Assistance & Compliance Unit, WW Operator Regs, Etc.:
http://h2o.enr.state.nc.us/tacu/index.html
Link to Collection Systems (PERCS Unit)
http://www.ncwaterquality.org/peres/Collection%20Systems/CollectionSystemsHome.html
Link to NC Surface Waters & Wetlands Standards ("Redbook"):
http://h2o.enr.state.nc.us/admin/rules/codes statutes.htm
Link to NC Stream Classifications:
http://h2o.enr.state.nc.us./bims/reports/reportsWB.html
Link to Water Supply Watershed Info:
http://h2o.enr.state.nc.us/wswp/index.html
Link to Stormwater, General Permits, & Runoff Pollution:
http://h2o.enr.state.nc.us/Stormwater.html
http://h2o.enr.state.nc.us/su/Forms Documents.htm#stormwaterGP
Janet Cantwell <Janet.Cantwell@ncmail.net>
NC DENR - Asheville Regional Office
Division of Water Quality -Surface Water Protection
1 of 1 2/8/2008 11:52 AN1