Loading...
HomeMy WebLinkAboutNC0023884_Notice of Fecal Exceedance_20221222Strickland, Bev From: Charles Wood <charles.wood@salisburync.gov> Sent: Thursday, December 22, 2022 9:11 AM To: Scheller, Roberto Cc: Bell, Wes Subject: [External] Fecal Exceedance CAUTION: External email. Do not click links or open attachments unless you verify. Send all suspicious email as an attachment to Report Spam. Good Morning All, The week of November 13 we had a fecal exceedance was due to seasonally early temperature changes causing treatment problems specifically solid settling issues. The seasonal early and quick water temperature change caused the Chlorine contact chamber to flip sooner than usual and solids that have accumulated and settled with time within the contact chamber showed themselves. The contact chamber cleanout is scheduled as a preventative maintenance task within our automatic generated worker order system. The contact chamber traditionally receives a yearly wash -out however the ORC vacancy and staffing transition was occurring during the typical wash -out period and the cleanout was not performed. Charles Wood WWTP Supervisor / ORC / Bio-Solids Salisbury -Rowan Utilities City of Salisbury I 11915 Grubb Ferry Rd. Salisbury, North Carolina 28144 Office: (704) 216-2728 I I Cell: (704) 798-7602 charles.wood@salisburync.gov I I www.salisburync.gov/SRU 1