I. General
The treatment system is an existing 0.020 MGD wastewater
Treatment facility with the following components:
• Bar screen
• Aeration basin
• Secondary clarifier with sludge return
• Chlorine contact chamber with tablet disinfections
• Sludge holding tank
This facility is located southwest of Hickory at the Catholic
Conference Center WWTP at 1551 Trinity Lane off NCSR 1120 in
Catawba County. Discharge from the Catholic Conference Center
Wastewater facility is received into an unnamed tributary to Camp
Creek, classified WS-III Waters in the Catawba River Basin.
1
Annual WW Report 2014
II. Compliance Performance:
The North Carolina Department of Environment and Natural
Resources (NCDENR) regulate the Catholic Conference Center
effluent discharge under the National Pollutant Discharge Elimination
System (NPDES). The NCDENR issued to Catholic Conference
Center a NPDES Permit that includes water quality limits and
sampling and monitoring requirements. The NPDES permit requires
Catholic Conference Center to test for routine wastewater parameters
of the treated water leaving the wastewater facility. The monitoring
frequency for these tests is set at various intervals as set forth in the
permit. The following table is a summary of the testing for the
parameters that are assigned Water Quality Standards by the NPDES
Permit.
There were no bypasses or spills during 2014.
Number Number Average Monthly Permit
Parameter Tests Tests Results Limit
Required* Conducted
0.0001
Flow 52 53 MGD 0.020 MGD
Biochemical Oxygen 52 50 2.34 mg/L 30.0 mg/L
Demand (BOD)
Total Suspended Solids 52 50 3.78 mg/L 30.0 mg/L
(TSS)
Ammonia as Nitrogen 30 30 2.1 mg/L 4.7 mg/L
(NH3asN)
April-October
Ammonia as Nitrogen 22 20 2.4 mg/L 17.0 mg/L
(NH3asN)
Nov.-March
Fecal Coliform 52 50 1 200 CFU/100
CFU/100mL mL
Total Residual Chlorine 104 115 28 ug/L 28 ug/L
Temperature 52 70 21 °C No limit
pH 52 68 Range 6.7 to >=6, <9
7.1
The last two weeks in December there was "no flow", as the facility was
closed.
2
•
• Annual WW Report 2014
III. Notification:
This report is made available on the bulletin board in the main hall.
IV. Certification:
I have personally examined and am familiar with the information
submitted in this document. Based upon my inquiry of those
individuals immediately responsible for obtaining the information
reported herein, I believe that the submitted information is true,
accurate, and complete. I am aware that there are significant penalties
for submitting false information.
Signed this �'.)-r►6 day of j(i3..)c.r Arty , 2015
i
fL
Paul onin
3
Annual Performance Report
Notification Certification Form
Name of System: C&Ittb(c. (oN Q j'-L Cc - 4►� W�j'�
NPDES# NC-0o'7 141
I confirm that the Annual Performance Report has been made available to
customers and that the information is correct and consistent with the
compliance monitoring data previously submitted to the DWQ.
The information was made available:
Posted on the Internet
Mailed the report to customers
Posted on the bulletin board in the office
—Documen made available for review at /S ( i'tN iT 1- Ni-r
kfick NL, 3-86o)_1
Certified By:
Name G. (.4:z )
Title V_cT 2_