HomeMy WebLinkAboutNC0078000_Report of Compliance Evaluation Inspection_20221209ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Mr. Charles Herron
Brenntag Mid -South, Inc.
2 HCI Boulevard
Greensboro, North Carolina 27409
NORTH CAROLINA
Environmental Quality
December 8, 2022
SUBJECT: Compliance Evaluation Inspection
Brenntag Groundwater Remediation System
NPDES Permit Number NC0078000
Guilford County
Dear Mr. Herron:
Mr. Jim Gonsiewski of the North Carolina Division of Water Resources (DWR), Winston-Salem
Regional Office (WSRO), visited your facility on November 10, 2022 and met with you to perform
a compliance evaluation inspection of your facility's groundwater remediation system. The
inspection found Brenntag to be compliant with the NPDES permit. Details of that inspection are
included on the attached EPA Water Compliance Inspection Report.
The following items were noted during the inspection:
The remediation system is designed to treat chlorinated and non -chlorinated solvents. Groundwater
is pumped from two extraction wells (EW-1 and EW-2) to the treatment building (RAS Building)
near the southeast corner of the site. The groundwater flows into a holding tank, into two (2) in -
line strainers, and then into a two -stage air stripper for final treatment. Treated water is then
discharged through a PVC pipe into a tributary of South Buffalo Creek. Currently fifty-two (52)
groundwater monitoring wells are located on and off site. The saprolite wells are sampled in April
while the bedrock wells are sampled in October. The effluent is sampled monthly for pH and
quarterly for volatiles and whole effluent toxicity. The system is very well run. The system and the
building in which it is located appear to be in good condition.
The outfall for the 4-inch PVC effluent pipe that transports treated water from the remediation
system is located near the southeast corner of the site. This outfall empties into an unnamed
tributary to South Buffalo Creek.
�D_E
oeportnent al Environmental a•rlr�
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
If you have any questions or concerns, please contact Jim Gonsiewski by phone at 336-776-9704,
or by email at jim.gonsiewski@ncdenr.gov. You may also contact me by phone at 336-776-9700,
or by email at lon.snider@ncdenr.gov.
Sincerely,
DoeuSlpned by:
C�A -r. JMi�f
145B49E225C94EA...
Lon T. Snider
Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ - WSRO
Attachment:
1. EPA Water Compliance Inspection Report
cc: Jim Shilliday — ARCADIS U.S., Inc. (Electronic Copy)
Cr,),
DepMwnl of En ionmatlM Dvmi�
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 ( Raleigh, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
[ 1I 2[ I
211III I I I
NPDES yr/mo/day Inspection
3 I NC0078000 111 121 22/11/10 117
Type
181 � I
I I I I I
Inspector Fac Type
19 I S I 201
I I III I I I I I I I I I I I I I I I I I
III I I I I I l66
I
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
71 1 I I 1 1 1 I80
871 I 7° I5 I 711 I 72 I N I 731 1 174
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Brenntag / Greensboro remediation
2 Segal Blvd
Greensboro NC 27409
Entry Time/Date
10:OOAM 22/11/10
Permit Effective Date
16/12/01
Exit Time/Date
11:40AM 22/11/10
Permit Expiration Date
21/05/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Charley Fredrick Herron/ORC/336-851-6824/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Grenoble,2000 E Petigrew St Durham NC 277034049/District SRQ
Manager/270-869-5806/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Records/Reports Self -Monitoring Progran
Facility Site Review • Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Jim J Gonsiewski
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DWR/Division of Water Quality/336-776-9704/
.-DocuSigned by: 12/8/2022
�y,(l Aft. l�ovu.i ZU�s(-i
wF197R6eF1791745F
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Docusigned by: 12/8/2022
It .. "T. SH4dcr
EPA Form 3± r§ e-94) Previous editions are obsolete.
Page# 1
3I
NPDES
NC0078000
111 121
yr/mo/day
22/11/10
Inspection Type
I17 18LI,
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mr. Jim Gonsiewski of the North Carolina Division of Water Resources (DWR), Winston-Salem
Regional Office (WSRO), visited the facility on November 10, 2022 to perform a compliance
evaluation inspection of the facility's groundwater remediation system. The inspection found
Brenntag to be compliant with the NPDES permit. Details of that inspection are included on the
attached EPA Water Compliance Inspection Report.
The following items were noted during the inspection:
The remediation system is designed to treat chlorinated and non -chlorinated solvents. Groundwater
is pumped from two extraction wells (EW-1 and EW-2) to the treatment building (RAS Building) near
the southeast corner of the site. The groundwater flows into a holding tank, into two (2) in -line
strainers, and then into a two -stage air stripper for final treatment. Treated water is then discharged
through a PVC pipe into a tributary of South Buffalo Creek. Currently fifty-two (52) groundwater
monitoring wells are located on and off site. The saprolite wells are sampled in April while the bedrock
wells are sampled in October. The effluent is sampled monthly for pH and quarterly for volatiles and
whole effluent toxicity. The system is very well run. The system and the building in which it is located
appear to be in good condition.
The outfall for the 4-inch PVC effluent pipe that transports treated water from the remediation system
is located near the southeast corner of the site. This outfall empties into an unnamed tributary to
South Buffalo Creek.
Page# 2
Permit: NC0078000
Inspection Date: 11/10/2022
Owner - Facility: Brenntag / Greensboro remediation
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new • ❑ ❑ ❑
application?
Is the facility as described in the permit? MI000
# Are there any special conditions for the permit? ❑• ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: There is a fence around the property.
Page# 3