Loading...
HomeMy WebLinkAboutWQ0043985_Application (FTSE)_20221208State of North Carolina DWR Department of Environmental Quality Division of Water Resources FAST TRACK SEWER SYSTEM EXTENSION APPLICATION Division of Water Resources FTA 06-21 & SUPPORTING DOCUMENTATION Application Number: '400 4J I D (to be completed by DWR) All items must be completed or the application will be returned I. APPLICANT INFORMATION: 1. Applicant's name: City of High Point (company, municipality, HOA, utility, etc.) 2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility ❑ Federal ❑ State/County ® Municipal ❑ Other 3. Signature authority's name: Derrick Boone per 15A NCAC 02T .0106(b) Title: Assistant Public Services Director 4. Applicant's mailing address: PO Box 230 City: High Point State: NC Zip: 27261 - 230 5. Applicant's contact information: Phone number:( 336 ) 883-3279 Email Address: derrick.boone@highpointnc.gov II. PROJECT INFORMATION: 1. Project name: Sewer Line Relocation -Panther Pavilion 2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project If a modification, provide the existing permit number: W000 and issued date: , For modifications, also attach a detailed narrative description as described in Item G of the checklist. If new construction, but part of a master plan, provide the existing permit number: W000 3. County where project is located: Guilford County 4. Approximate Coordinates (Decimal Degrees): Latitude: 35.97 ° Longitude: - 79.99 ° 5. Parcel ID (if applicable): 182447 (or Parcel ID to closest downstream sewer) III. CONSULTANT INFORMATION: 1. Professional Engineer: Daniel W. Pritchett, PE License Number: 11659 Firm: Jamestown Engineering Group, Inc. Mailing address: 117 E. Main Street, PO Box 365 City: Jamestown State: NC Zip: 27282 - Phone number: 336 886-5523 Email Address: dan@iamestownengineering.com IV. WASTEWATER TREATMENT FACILITY (W WTF) INFORMATION: 1. Facility Name: High Point Eastside Treatment Plant Pennit Number: NC 0024210 Owner Name: City of Hieh Point V. RECEIVING DOWNSTREAM SEWER INFORMATION: 1. Permit Number(s): WQ 2. Downstream (Receiving) Sewer Information: inch ❑ Gravity ❑ Force Main 3. System Wide Collection System Permit Number(s) (if applicable): WQCS Owner Name(s): FORM: ETA 06-21 Page I of 5 VI. GENERAL REQUIREMENTS 1. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ❑ Yes ❑ No ® N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached? ❑ Yes ❑ No ® N/A 3. If the Applicant is a Home/Property Owners' Association, has an HOA/POA Operational Agreement (FORM: HOA) and supplementary documentation as required by 15A NCAC 02T.0115(c) been attached? ❑ Yes ❑ No ® N/A 4. Origin of wastewater: (check all that apply): ❑ Residential (Individually Owned) ❑ Retail (stores, centers, malls) ❑ Car Wash ❑ Residential (Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels ® School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool/Clubhouse ❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash ❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment) 5. Nature of wastewater : 100 % Domestic % Commercial % Industrial (See 15A NCAC 02T .0103(20)) If Industrial, is there a Pretreatment Program in effect? ❑ Yes ❑ No 6. Hasa flow reduction been approved under 15A NCAC 02T .0114(fl? ❑ Yes ® No ➢ If yes, provide a copy of flow reduction approval letter with this application 7. Summarize wastewater generated by project: Establishment Type (see 02T.0114(f)) Daily Design Flow',^ No. of Units Flow Tailgate Pavilion or food Kiosk 50 gal/I00 SF floor space 6000 SF 3000 GPD gal/ GPD gall GPD gal/ GPD gal/ GPD gal/ GPD Total GPD a See 15A NCAC 02T .0114(b), (d), (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01141 shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 3,000 GPD (per 15A NCAC 02T .0114) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero, please indicate why: ❑ Pump Station/Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line. Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow. ❑ Flow has already been allocated in Permit Number: Issuance Date: ❑ Rehabilitation or replacement of existing sewers with no new flow expected ❑ Other (Explain): FORM: ETA 06-21 Page 2 of 5 VII. GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T .0305 & MDC (Gravity Sewers): 1. Summarize gravity sewer to be permitted: Size (inches) Length (feet) Material 12" 190 PVC(SDR 26) ➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria ➢ Section III contains information related to minimum slopes for gravity sewer(s) ➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains): PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT 1. Pump station number or name: N/A 2. Approximate Coordinates (Decimal Degrees): Latitude: Longitude: -. 3. Total number of pumps at the pump station: 3. Design flow of the pump station: millions gallons per day (firm capacity) ➢ This should reflect the total GPM for the pump station with the largest pump out of service. 4. Operational point(s) per pump(s): gallons per minute (GPM) at feet total dynamic head (TDH) 5. Summarize the force main to be permitted (for this Pump Station): Size (inches) Length (feet) Material If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per MDCPSFM Section 2.01 C. Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify) 6. Power reliability in accordance with 15A NCAC 02T .0305(h)(1): ❑ Standby power source or ❑ Standby pump ➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(h)(1)(13): ➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day ➢ Must be permanent to facility and may not be portable Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C): ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - or ❑ Portable pumping unit with plugged emergency pump connection and telemetry: ➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided as part of this permit application in the case of a multiple station power outage. FORM: FTA 06-21 Page 3 of 5 IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T .0305(Q): 1. Does the project comply with all separations/alternatives found in 15A NCAC 02T .0305(f) & (g)? ® Yes ❑ No 15A NCAC 02T.0305(fl contains minimum separations that shall be provided for sewer systems: Setback Parameter* Separation Required Storm sewers and other utilities not listed below (vertical) 18 inches 2Water mains (vertical - water over sewer preferred, including in benched trenches) 18 inches 2Water mains (horizontal) 10 feet Reclaimed water lines (vertical - reclaimed over sewer) 18 inches Reclaimed water lines (horizontal - reclaimed over sewer) 2 feet **Any private or public water supply source, including any wells, WS-I waters of Class I or Class Il impounded reservoirs used as a source of drinking water, and associated wetlands. 100 feet "Waters classified WS (except WS-1 or WS-V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands associated with these waters (see item IX.2) 50 feet **Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches, as well as wetlands associated with these waters or classified as WL. 10 feet Any building foundation (horizontal) 5 feet Any basement (horizontal) 10 feet Top slope of embankment or cuts of 2 feet or more vertical height 10 feet Drainage systems and interceptor drains 5 feet Any swimming pools 10 feet Final earth grade (vertical) 36 inches ➢ If noncompliance with 02T.0305(fl or (g), see Section X.1 of this application *15A NCAC 02T.0305(a) contains alternatives where separations in 02T.0305(fl cannot be achieved. Please check "yes" above if these alternatives are used and provide narrative information to explain. **Stream classifications can be identified using the Division's NC Surface Water Classifications webpage 2. Does this project comply with the minimum separation requirements for water mains? ®Yes []No ❑ N/A ➢ If no, please refer to 15A NCAC 18C.0906(f) for documentation requirements and submit a separate document, signed/sealed by an NC licensed PE, verifying the criteria outlined in that Rule. 3. Does the project comply with separation requirements for wetlands? ® Yes ❑ No ❑ N/A ➢ Please provide supplementary information identifying the areas of non-conformance. ➢ See the Division's draft separation requirements for situations where separation cannot be met. ➢ No variance is required if the alternative design criteria specified is utilized in design and construction. 4. Is the project located in a river basin subject to any State buffer rules? ® Yes Basin name: Randleman ❑ No If yes, does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ® Yes ❑ No ➢ This includes Trout Buffered Streams per 15A NCAC 213.0202 5. Does the project require coverage/authorization under a 404 Nationwide/individual permits ❑ Yes ® No or 401 Water Quality Certifications? ➢ Please provide the permit number/permitting status in the cover letter if coverage/authorization is required. 6. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? ® Yes ❑ No Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications must be being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stonnwater management plans, etc.). 7. Does this project include any sewer collection lines that are deemed "high -priority?" ❑ Yes ® No Per 15A NCAC 02T.0402, "high -priority sewer" means any aerial sewer, sewer contacting surface waters, siphon, or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer. Siphons and sewers suspended through interference/conflict boxes require a variance approval. ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permittee's individual System -Wide Collection permit. FORM: FTA 06-21 Page 4 of 5 X. CERTIFICATIONS: 1. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version) as applicable? ® Yes ❑ No If no, for projects requiring a single variance, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review to the Central Office. Approval of the request will be issued concurrently with the approval of the permit, and projects requiring a variance approval may be subject to longer review times. For projects requiring two or more variances or where the variance is determined by the Division to be a significant portion of the project, the full technical review is required. 2. Professional Engineer's Certification: I, Daniel W. Pritchett , attest that this application for Sewer Line Relocation — Panther Pavilion (Professional Engineer's name from Application Item 11I.I.) (Project Name from Application Item ILI) has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Pennitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. Misrepresentation of the application information, including failure to disclose any design non-compliance with the applicable Rules and design criteria, may subject the North Carolina -licensed Professional Engineer to referral to the licensing board. (21 NCAC 56.0701) North Carolina Professional Engineer's seal, signature, and date: 3. Applicant's Certification per 15A NCAC 02T .0106(b): 1, Derrick Boone attest that this application for Sewer Line Relocation — Panther Pavilion (Signature Authority Name from Application Item 1.3.) (Project Name from Application Item II.1) attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. I understand that any discharge of wastewater from this non -discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: I Date: FORM: FTA 06-21 Page 5 of 5 Public Services Department Derrick Q. Boone ASSISTANT DIRECTOR NORTH CAROLINA s INTERNATIONAL CITYTM December 5, 2022 NCDENR Winston-Salem Regional Office 450 W. Hanes Mill Rd, Suite 300 Winston-Salem, NC 27105 Project: Panther Drive Pavilion Private sewer service Dear Sir or Madam: This is to acknowledge that the City of High Point will accept for treatment in the Eastside Wastewater Treatment Plant (Permit #NC0024210), wastewater flow from the High Point University Pavilion private sewer service, in the amount of 3,000 GPD, which will be discharged to facilities operated and maintained by the City of High Point. If further information is needed, please let me know. Very truly yours, errick Q. Boone Assistant Director of Public Services DQB/tab City of High Point, P.O. Box 230, 211 South Hamilton Street, High Point, NC 27261 USA Fax:336.883.1675 Phone:336.883.3215 TDD:336.883.8517 34 ' State of North Carolina Department of Environmental Quality Division of Water Resources Flow Tracking for Sewer Extension Applications Dlvlslon of kvater Resolnfes (FTSE 10-18) Application Number: 2020-183 Entity Requesting Allocation: City of High Point Project Name for which flow is being requested: Sewer line relocation - Panther Dr. Pavilion More than one FTSE uray be required for a single project Jfthe owner of the IVIVTP is not responsible for all ptuap stations along the route of the proposed rvasteivaterflorv. 1. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility name: EastsideWWTP b. W WTP Facility Permit M NC-0024210 Al/flows are In MGD c. W WTP facility permitted flow: 26.0000 d. Estimated obligated flow not yet tributary to the W WTP: 3.0649 e. W WTP facility's actual average flow: 13.7292 f. Total flow for this specific request: 0.0030 g. Total actual and obligated flows to the facility: 16.7971 h. Percent of permitted flow used: 64.60% II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the W WTP. (A) (B) (C) (D)=(B+C) (E)=(A-D) Pump Pump Firm Design Approx. Obligated, Total Current Available Station Station Capacity' Average Current Not Yet Flow Plus Capacity, (Name or Permit Daily Flow' Avg, Daily Tributary Obligated Number) Number (Finn/pf), Flow, Daily Flow, Flow MCD MGD h1GD MGD MGD MGD Rivmdele W00008872 30.0887 11.4842 $3996 1.0149 10.1144 U698 -- MIA MN/A MNIA MA MWA MWA *NIA MA MNIA MNIA MNIA MNIA MWA MWA bat/A MIA MN/A MNIA MNIA MNIA MWA MNIA MNIA MNIA MNIA NN/A MWA MNIA MWA MWA MNIA " The Firm Capacity (design Bmv) of any pump stfl tam is defined as the maximum pumped flow -that can be achieved with the largest pump taken out of service. . Design Average Flow is the firm capacity of the pump station divided by the peaking factor (po not less limn 2.5, per Section 2.02(A)(4)(c) of the Minimum Design Criteria. ""' A Planning Assessment Addendum shall he attached for each pump station located between the project connection point and the W WTP where the Available Capacity Is 5 0. Downstream Facility Name (Sewer): Downstream Permit Number: Page 1 of 6 FTSE 10-18 III. Certification Statement I, Derrick Q. Boone certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and 11 plus all attached planning assessment addendums for which I am the responsible party. Signature of this form certifies that the receiving collection system or treatment works has adequate capacity to transport and treat the proposed new wastewater. Signing Official Asstsad-r R&)&-i ' 5&?04V5 &Z&r7et' Title of Signing Official Date 12/2/2022 Page 2 of 6 FTSE 10-18 /y , �' bi'o A�� �toneyArrh,k S� urt 'v f 4 � At 14 Q IA CM. ry u � ' � (npUCl4t9i AVe � KLt4. c,�4nrtaorror z x �� � � •. 8n.it,lq t• � u O" Cnathiltn Oc 73 v 4 4 a lr101tt`(aM1 1 wain>` nraagAve o v w D::nrrs,',°? z • i-r E Lcxtngtmn Age a Nr7lUoms (vve siF E Dayton.0vpo'}F ti Stare Ave e rvt> rY in � � 0 J. J etA*- Ktnt t V TelMe lit 4a C5 V 06v ` Fafasrvv - o Cedruiv:)i `2 Yi 'Y t5 omtrnoulh Ave J' Nye,amaen,%V, C , a Farm; E 4 S� ,rdadl d=;=r SRr r40bSrpng pMk y � ':° yid 11wnt1diq kae Y tlipb Ft Un�xer L�rf Ave u'., Graf js a•2 2 BoroeeMe D.7n$Ave -Dall,s 1•re �iD 3ro W n'i0AVPi ... @t ,4 iAWOecI `' O i rym-r1�-p s c� Moil eve D�ypi �o �llo,tr ngto % Offit i65pnel I Leonard Ave :.eoelArd Al, Granby Ave Si5'V'�A '3a�r n N u Furioush Ave '+ High Point x Vernon pi u N !� appm rP Franidin Ave Fllberr f?I Green Dr q ' E Circen or N i I C LWOO Y' bjupbw t O,nsi,,.thinf lmn.5c ,.. O Ragan, Ave t% ,_ JAMESTOWN ENGINEERING GROUP, INC. L CIVIL ENGINEERS &SURVEYORS LAND PLANNING• MUNICIPAL CONSULTING inc. 117 East Main Street • P.O. Box 365 • Jamestown, N.C. 27282 Telephone (336) 886.5523 Fax (336) 886.5478 www.jamestownengineerin com December 5. 20�22 Re: Sewer Line Relocation City of High Point, NC JEG File No. 22007 NC Department of Environmental Quality Division of Water Resources Winston Salem Regional Office 450 W. Hanes Mill Road, Suite 300 Winston-Salem, NC 27105 Dear Sir or Madam: Environmental QU of t- Received DEC 0 8 2022 Winston-Salem Regional office Panther Pavilion With regards to the referenced project, and on behalf of the City of High Point, we are requesting your review/approval of public sewer applications required for the installation of a new Pavilion by High Point University on Panther Drive. Relocation of 190 L.F. of 12" public sewer will be required prior to construction of the new facility. Anticipated flows from the new Tailgate Pavilion are included, which will be tied into the relocated 12" sewer line by a standard sewer service connection. On this basis, we have enclosed the following public application package in support of the sewer line relocation: One original and one copy of the Fast Track Sewer Application (FTA 04-16) Two copies of Form FTSE 04-16 completed by the City of High Point $480 Application Fee Letter of Flow Acceptance from the City of High Point 8.5" X 11" USGS topographic map If there are any questions or additional information required, please call. Yours very truly, JAMESTOWN ENGINEERING GROUP, INC. Aaniel ntch E & PLS DWP/cp Enclosures Cc: Mr. Derrick Boone, City of High Point Mr. Tom Beckett, City of High Point Mr. Jason Sweet, High Point University