HomeMy WebLinkAboutWQ0002001_BIMS Report_20221205Compliance Inspection Report
Permit: WQ0002001 Effective: 01/04/22 Expiration: 06/30/28 Owner : Waters Edge Property Owners Association on
High Rock Lake
SOC: Effective: Expiration: Facility: Waters Edge WWTP
County: Rowan 470 Deer Lk Run
Region: Mooresville
Contact Person: Cameron Spencer
Salisbury NC 28146
Title: Phone:
Directions to Facility:
From the intersection of Stokes Ferry Rd (SRand Providence Church Rd, travel east approx. 2.5 miles and turn right on to Waters
Edge Rd. Turn right on to Deer Lake Run. The plant is through the gate to the right of the tennis court.
System Classifications: SI,
Primary ORC: A Lynn Aldridge
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 12/02/2022
Certification: 993778 Phone: 704-431-5266
Entry Time 09:OOAM Exit Time: 10:OOAM
Primary Inspector: Edward Watson Phone:
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant Not Compliant
Question Areas:
1. Miscellaneous Questions
▪ Treatment Lagoons
▪ Storage
(See attachment summary)
▪ Treatment
In End Use -Irrigation
▪ Wells
▪ Record Keeping
▪ Treatment Disinfection
Page 1 of 5
Permit: WQ0002001 Owner - Facility: Waters Edge Property Owners Association on High Rock Lake
Inspection Date: 12/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
On December 2, 2022, MRO staff performed a Compliance Evaluation Inspection at the Watel's Edge WWTP under permit
WQ0002001. During the site visit, it was observed that there is excessive vegetation growing in the berm around the storage
lagoon. Some of this vegation is woody. Woody vegetation indicates the potential for the berm to become compromised.
Please remove the woody growth from the berm wall. No animal burrows were observed to be present in the lagoon berm
walls.
Although there were geese present, no nests were present in the high grass in the lagoon berm.
The system meter appears to be in good condition. The ORC reports no observed indications of irregularities with the flow
meter readings. To check the meter is adequately reading flow, a bucket test can be performed. However, Section III
Operation and Mainteneace Requirements, Line 16: Metering equipment shall be tested and calibrated annually. [154 NCAC
02T .0507(d)].
Page 2 of 5
Permit: WQ0002001 Owner - Facility: Waters Edge Property Owners Association on High Rock Lake
Inspection Date: 12/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Reuse (Quality)
Infiltration System
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Recycle/Reuse
Single Family Drip
Lagoon Spray, LR
Yes No NA NE
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? • ❑ ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) • ❑ ❑ ❑
Comment: The chlorine feed tablet treatment appeared to be in good condition during the site visit.
Treatment Disinfection Yes No NA NE
Is the system working? • ❑ ❑ ❑
Do the fecal coliform results indicate proper disinfection? • ❑ ❑ ❑
Is there adequate detention time (>=30 minutes)? • ❑ ❑ ❑
Is the system properly maintained? • ❑ ❑ ❑
If gas, does the cylinder storage appear safe? ❑ ❑ • ❑
Is the fan in the chlorine feed room and storage area operable? ❑ ❑ • ❑
Is the chlorinator accessible? • ❑ ❑ ❑
If tablets, are tablets present? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Is contact chamber free of sludge, solids, and growth? • ❑ ❑ ❑
If UV, are extra UV bulbs available? ❑ ❑ • ❑
If UV, is the UV intensity adequate? ❑ ❑ • ❑
# Is it a dual feed system? ❑ • ❑ ❑
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ • ❑
If yes, then is there a Risk Management Plan on site? ❑ ❑ • ❑
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment: During the site visit, it was observed that the proper tablets are being used for disinfection.
This is not a dual -feed system. There are no chlorine tanks associated with the facility.
Record Keeping
Yes No NA NE
Page 3 of 5
Permit: WQ0002001 Owner - Facility: Waters Edge Property Owners Association on High Rock Lake
Inspection Date: 12/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: O&M records were reviewed for the period of January 2022 through November 2022. The
records appear to be in order.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 5
Permit: WQ0002001 Owner - Facility: Waters Edge Property Owners Association on High Rock Lake
Inspection Date: 12/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
Comment: Monitor well 1 is scheduled to be replaced. The schedule date for the replacement well is
March 2023. MRO staff will be notified when a date is fixed. The well needs to be drilled
deeper to be able to be at the groundwater interface. MRO staff intends to be present during
the well replacement event.