Loading...
HomeMy WebLinkAboutWQ0000193_Compliance Evaluation Inspection_20221122DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director Joseph Patrick McCann Village of Bald Head Island PO Box 3009 Bald Head Island, NC 28461-3009 NORTH CAROLINA Environmental Quality November 30, 2022 SUBJECT: Compliance Inspection Report Village of Bald Head Island WWTP Non -discharge Permit No. WQ0000193 Brunswick County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Village of Bald Head Island WWTP on 11/22/2022. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0000193. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". There were no significant issues or findings noted during the inspection and therefore, a response to this inspection report is not required. If you should have any questions, please do not hesitate to contact Helen Perez with the Water Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at helen.perez@ncdenr.gov. Sincerely, DocuSigned by: I ONE �Aarct Oti for 7F141 E73B6F3456... Morella Sanchez -King, Regional Supervisor Water Quality Regional Operations Section Wilmington Regional Office Division of Water Resources, NCDEQ ATTACHMENTS Cc: Nate Lindsay — Electronic copy Upload to Laserfiche D_E QZ� North Carolina Department of Environmental Quality I Division of Water Resources Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405 910.796.7215 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Compliance Inspection Report Permit: WQ0000193 Effective: 02/15/21 Expiration: 05/31/27 Owner : Village of Bald Head Island SOC: Effective: Expiration: Facility: Village of Bald Head Island WWTP County: Brunswick 256 Edward Teach Wynd Region: Wilmington Bald Head Island NC 284613069 Contact Person: Joseph Patrick McCann Title: Utilities Director Phone: 910-457-7351 Directions to Facility: System Classifications: SI, WW3, Primary ORC: Nathan James Lindsay Certification: 1006813 Phone: 910-457-7350 Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 11/22/2022 Entry Time 09:30AM Exit Time: 11:30AM Primary Inspector: Helen I Perez DDo uSig ed by: Phone: 910-796-7387 lI^JVa, DocuSigned by: Secondary Inspector(s): (JE-,7F141E73B6F3456... TE1 D645B4A39694BE...o4,, lY�affl Oti Reason for Inspection: Routine Inspection Type: Compliance Evaluation Permit Inspection Type: High Rate Infiltration Facility Status: Compliant ❑ Not Compliant Question Areas: Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent Miscellaneous Questions Treatment Flow Measurement -Water Treatment Treatment Barscreen Use Records Treatment Filters Record Keeping Treatment Activated Sludge Treatment Sludge Storage/Treatment Treatment Disinfection End Use -Infiltration Treatment Flow Measurement End Use -Reuse Standby Power (See attachment summary) Page 1 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine Inspection Summary: A routine compliance inspection of the Bald Head Island WWTF was conducted on November22, 2022. The purpose of the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit WQ0000193. Nate Lindsay, ORC, was present during the inspection. The Village of Bald Head Island WWTF consists of a Sequencing Batch Reactor (SBR), reclaimed water generation system and is permitted for 300,000 gpd. Non -discharge disposal consists of a 52.2-acre conjunctive utilization system (Site C-1), a 3.43-acre conjunctive utilization area (Site C-2), a 46.3-acre dedicated site (NC-1) and two high -rate infiltration basins (Basin #4, Basin #5). There are four reclaimed water storage structures: Conservation Pond, Irrigation Pond, Pond 6 and Pond 7. There has been a recent change in the ORC and BORC for the facility. The new ORC has had manufacturer's consultants on site to help fine tune the operation of the plant towards more efficient treatment In addition, the facility has a new SCADA system to better monitor and operate the plant and collection system. The average yearly flow for 2021 was approximately half of the permitted flow, but the summer months can reached levels at approximately 80% of the permitted flow. The Village is already in the planning stage for a future upgrade to the plant It was noted during the inspection that the composite sample is collected before the UV system. The tubing had some scum build-up and was long in length from the compositor. It might be benenficial to locate the compositor to collect the composite sample after the UV disinfection and shorten the length of the tubing for easy cleaning or replacement. The facility is compliant with Non -Discharge Permit WQ0000193. Please review the comment sections of the inspection report for more details. Page 2 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine Type Yes No NA NE Lagoon Spray, LR ❑ Single Family Spray, LR ❑ Activated Sludge Spray, LR ❑ Activated Sludge Spray, HR ❑ Activated Sludge Drip, LR ❑ Single Family Drip ❑ Reuse (Quality) Infiltration System Recycle/Reuse Treatment Yes No NA NE Are Treatment facilities consistent with those outlined in the current permit? 0 ❑ ❑ ❑ Do all treatment units appear to be operational? (if no, note below.) 0 ❑ ❑ ❑ Comment: No comment. Treatment Flow Measurement -Influent Yes No NA NE Is flowmeter calibrated annually? 0 ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? 0 ❑ ❑ ❑ Comment: The influent flowmeter used for reporting was calibrated on 09/21/2022 by JS Dismuke Co., Inc. Treatment Flow Measurement -Water Use Records Yes No NA NE Is water use metered? ❑ ❑ ❑ Are the daily average values properly calculated? ❑ ❑ 0 ❑ Comment: Treatment Flow Measurement -Effluent Yes No NA NE Is flowmeter calibrated annually? ❑ ❑ ❑ Is flowmeter operating properly? ❑ ❑ ❑ Does flowmeter monitor continuously? ❑ ❑ ❑ Does flowmeter record flow? ❑ ❑ ❑ Does flowmeter appear to monitor accurately? ❑ ❑ ❑ Comment: Standby Power Yes No NA NE Is automatically activated standby power available? 0 ❑ ❑ ❑ Page 3 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine Is generator tested weekly by interrupting primary power source? Is generator operable? Does generator have adequate fuel? Comment: The wastewater and water treatment facilities are at the same location and three qenerators are available on site. They are serviced biannually and tested weekly under load. Treatment Barscreen Yes No NA NE Is it free of excessive debris? 0 ❑ ❑ ❑ Is disposal of screenings in compliance? 0 ❑ ❑ ❑ Are the bars spaced properly? ❑ ❑ ❑ Is the unit in good condition? 0 ❑ ❑ ❑ Comment: The facility has a screw type mechanical bar screen with bag compactor. Screenings are collected in a dumpster and disposed of at the Brunswick County landfill. Treatment Activated Sludge Yes No NA NE Is the aeration mechanism operable? ❑ ❑ ❑ Is the aeration basin thoroughly mixed? ❑ ❑ ❑ Is the aeration equipment easily accessed? ❑ ❑ ❑ Is Dissolved Oxygen adequate? ❑ ❑ ❑ Are Settleometer results acceptable? ❑ ❑ ❑ Is activated sludge an acceptable color? 0 ❑ ❑ ❑ Comment: From the 223,000 gallon aerated equalization basin, influent flows to the three SBRs. Two of the three 155,000 gallon SBRs were in service during the inspection due to lower flows. The facility has a carbon source, liquid alum and alkalinity chemical feed systems. Currently, the alkalinity feed system is not needed. The pH sensors in the reactors are in the process of being ordered and replaced. Process control testing includes settleometer tests, colormetric nitrate tests, pH and DO. Treatment Filters Yes No NA NE Is the filter media present? ❑ ❑ ❑ Is the filter media the correct size and type? ❑ ❑ ❑ Is the air scour operational? ❑ ❑ ❑ Is the scouring acceptable? ❑ ❑ ❑ Is the clear well free of excessive solids? ❑ ❑ ❑ Is the mud well free of excessive solids and filter media? ❑ ❑ ❑ Does backwashing frequency appear adequate? 0 ❑ ❑ ❑ Comment: From the 28,000 qallon post equalization basin with floatinq aerator, the wastewater flows to two cloth Aqua Disk tertiary filters. They are backwashed every 8 hours or more if needed. Treatment Sludge Storage/Treatment Yes No NA NE Is the aeration operational? ❑ ❑ ❑ Is the aeration pattern even? ❑ ❑ ❑ Page 4 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine If required, are Sanitary "Ts" present in tankage? ❑ ❑ 0 ❑ Comment: The 336,000 gallon aerobic digester has three compartments, each with a floating aerator. Utilitech is contracted for sludge removal and documentation of hauling activities were available for review. Treatment Disinfection Yes No NA NE Is the system working? ❑ ❑ ❑ Do the fecal coliform results indicate proper disinfection? ❑ ❑ ❑ Is there adequate detention time (>=30 minutes)? ❑ ❑ ❑ Is the system properly maintained? ❑ ❑ ❑ If gas, does the cylinder storage appear safe? ❑ ❑ ❑ Is the fan in the chlorine feed room and storage area operable? ❑ ❑ ❑ Is the chlorinator accessible? ❑ ❑ ❑ If tablets, are tablets present? ❑ ❑ ❑ Are the tablets the proper size and type? ❑ ❑ ❑ Is contact chamber free of sludge, solids, and growth? ❑ ❑ ❑ If UV, are extra UV bulbs available? ❑ ❑ ❑ If UV, is the UV intensity adequate? ❑ ❑ ❑ # Is it a dual feed system? ❑ ❑ ❑ Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? ❑ ❑ ❑ If yes, then is there a Risk Management Plan on site? ❑ ❑ ❑ If yes, then what is the EPA twelve digit ID Number? (1 000-- ) If yes, then when was the RMP last updated? Comment: The facility has two UV banks in series and a secondary tablet chlorine disinfection unit for back-up. Extra UV bulbs, sleeves and chlorine tablets were stored on site. Record Keeping Yes No NA NE Is a copy of current permit available? ❑ ❑ ❑ Are monitoring reports present: NDMR? ❑ ❑ ❑ NDAR? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are flow rates less than of permitted flow? ❑ ❑ ❑ Are application rates adhered to? ❑ ❑ ❑ Is GW monitoring being conducted, if required (GW-59s submitted)? ❑ ❑ ❑ Are all samples analyzed for all required parameters? ❑ ❑ ❑ Are there any 2L GW quality violations? ❑ ❑ ❑ Is GW-59A certification form completed for facility? ❑ ❑ ❑ Is effluent sampled for same parameters as GW? ❑ ❑ ❑ Do effluent concentrations exceed GW standards? ❑N ❑ ❑ Page 5 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine Are annual soil reports available? ❑ ❑ 0 ❑ # Are PAN records required? ❑ ❑ 0 ❑ # Did last soil report indicate a need for lime? ❑ ❑ 0 ❑ If so, has it been applied? ❑ ❑ 0 ❑ Are operational logs present? 0 ❑ ❑ ❑ Are lab sheets available for review? 0 ❑ ❑ ❑ Do lab sheets support data reported on NDMR? ❑ ❑ ❑ Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ Are Operational and Maintenance records present? 0 ❑ ❑ ❑ Were Operational and Maintenance records complete? 0 ❑ ❑ ❑ Has permittee been free of public complaints in last 12 months? 0 ❑ ❑ ❑ Is a copy of the SOC readily available? ❑ ❑ 0 ❑ No treatment units bypassed since last inspection? ❑ 0 ❑ ❑ Comment: Operational and maintenance records were available for review. A new SCADA system allows the operators to monitor the plant operations, alarms and track trends. Staff has limited operational control through SCADA on their phones on off -hours to allow enough time to get back on the island if needed. Samples are relinquished on the chain of custody to Envirochem Lab before cooler is placed on the ferry to the main land as required. A review of records since the last inspection in 2021, show an enforcement issued in February 2022 for TSS and TP, a NOV in July 2022 for Fecal and ammonia and a NOV in August 2022 for ammonia and TP. MW-1, MW-5, MW-7 and MW-8 have had sporadic exceedances in TDS which is typical of an island environment and the Wilminaton Reaional Office continues to monitor the trends. End Use -Infiltration Yes No NA NE # Is the application High Rate or Low Rate? High Rate Are buffers maintained? 0 ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? 0 ❑ ❑ ❑ Are GW monitoring wells required? 0 ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? 0 ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ Is a usable green area maintained? 0 ❑ ❑ ❑ Is the disposal site acceptable? 0 ❑ ❑ ❑ Is the distribution equipment acceptable? 0 ❑ ❑ ❑ Is the disposal site free of ponding? ❑ ❑ 0 ❑ Is the disposal site free of breakout? ❑ ❑ ❑ Are the disposal sites free of solids, algae, etc.? ❑ ❑ ❑ Do the records show that the fields are properly maintained? 0 ❑ ❑ ❑ Are the disposal sites free of vegetation? ❑ ❑ ❑ Page 6 of 7 DocuSign Envelope ID: 82ECD813-DED6-47D1-8AFC-52655BBE5BFF Permit: WQ0000193 Owner - Facility: Village of Bald Head Island Inspection Date: 11/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine Do any surface water features appear to be adversely impacted by GW discharge? ❑ ❑ 0 ❑ No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.? 0 ❑ ❑ ❑ Comment: Infiltration Ponds #4 and #5 are located on the golf course and signs are posted to notify the public of reclaimed water use. The facility does not have a 5-day upset pond. Instead, effluent is automatically diverted to the high -rate ponds when the turbidity or fecal limits are above reclaimed quality. End Use -Reuse Yes No NA NE Is the acreage in the permit being utilized? ❑ ❑ ❑ Does the acreage specified in the permit correspond to the measured acreage at the site? ❑ ❑ ❑ Are all essential units provided in duplicate? ❑ ❑ ❑ Is an automatically activated standby power source available? ❑ ❑ ❑ Is the equalization capacity adequate? ❑ ❑ ❑ Is aerated flow equalization present? ❑ ❑ ❑ Has the turbidity meter been calibrated in the last 12 months? ❑ ❑ ❑ Does the turbidity meter have recording capabilities? ❑ ❑ ❑ Is all flow diverted at the appropriate times? ❑ ❑ ❑ Is all upset wastewater diverted from reuse storage unit? ❑ ❑ ❑ Is all upset wastewater treated, retreated, or disposed of acceptably? ❑ ❑ ❑ Is upset wastewater treated prior to discharge to irrigation storage? ❑ ❑ ❑ Is public access restricted from irrigation area during active site use? ❑ ❑ ❑ If golf course, is a sign posted in plain sight on the club house? ❑ ❑ ❑ Is the cover crop acceptable? ❑ ❑ ❑ Are buffers adequate? ❑ ❑ ❑ Is the site free of ponding/runoff? ❑ ❑ ❑ Is the acreage in the permit being utilized? ❑ ❑ ❑ Is the application equipment acceptable? ❑ ❑ ❑ Is the application area free of limiting slopes? ❑ ❑ ❑ How close is the closest water supply well? ❑ ❑ ❑ Are any supply wells within the CB? ❑ ❑ ❑ Are any supply wells within 250' of the CB? ❑ ❑ ❑ Is municipal water available in the area? ❑ ❑ ❑ Are GW monitoring wells required? ❑ ❑ ❑ Are GW monitoring wells located properly w/ respect to RB and CB? ❑ ❑ ❑ Are GW monitoring wells properly constructed, including screened interval? ❑ ❑ ❑ Comment: The conjunctive reclaimed water irrigation is managed by the Bald Head Island Club staff and the remaining disposal is managed by the wastewater facility staff. The turbidity meter was calibrated by HACH on 7/6/2022. Page 7 of 7