HomeMy WebLinkAboutNCG550152_NOD2022PC0190 & CEI Report_20221121 (2)
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
November 21, 2022
Jorge Diaz & Pedro Boj
Email: bojped15@aol.com
SUBJECT: NOTICE OF DEFICIENCY
Tracking Number: NOD-2022-PC-0190
Permit No. NCG550152
43 Driftwood Court
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the 43 Driftwood Court on November
8, 2022. This inspection was conducted to verify that the facility is operating in compliance with the conditions
and limitations specified in NPDES WW Permit No. NCG550152. A summary of the findings and comments
noted during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following deficiencies were noted during the inspection:
Inspection Area Description of Deficiency _________________________________________________________________________________________________________________________________________________________________________ Effluent Pipe At the time of the inspection, the effluent pipe could not be located.
_________________________________________________________________________________________________________________________________________________________________________ Disinfection-Tablet The system does not currently have chlorination.
_________________________________________________________________________________________________________________________________________________________________________ De-chlorination The system does not currently have dechlorination.
_________________________________________________________________________________________________________________________________________________________________________
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law. To prevent further action, carefully review these deficiencies and address the causes of
non-compliance to prevent the recurrence of similar situations.
If you should have any questions, please do not hesitate to contact Lauren Armeni with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4667.
Sincerely,
G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection Report
Ec: Laserfiche
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NCG550152 22/11/08 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
43 Driftwood Court
43 Driftwood Ct
Asheville NC 28805
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
10:00AM 22/11/08 20/11/24
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
11:00AM 22/11/08 25/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
Jorge Diaz,508 Savona Ave Coral Gables FL 33146//305-665-3888/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Self-Monitoring Program Facility Site Review
Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Lauren E Armeni DWR/ARO WQ/828-296-4500/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
11/21/2022
11/21/2022
NPDES yr/mo/day
22/11/08
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Lauren Armeni, with the Asheville Regional Office, conducted a Compliance Evaluation Inspection of
the single-family wastewater disposal system that services 43 Driftwood Court on November 8, 2022.
This inspection was conducted to determine whether the system is being operated and maintained in
compliance with General NPDES Permit No. NCG550000. Mr. Pedro Boj (owner) was present during
the inspection. Mr. Jorge Diaz is also the owner of the property, but was not present during the
inspection.
Permit: During previous inspections, the layout for the septic systems located at 41 (NCG550151) and
43 Driftwood Court was unknown. At the time of the inspection, Mr. Boj was able to clarify the layout,
and he indicated that flow from both septic tanks enters a junction box, which then drains to one sand
filter connected to one effluent pipe, both located on the 43 Driftwood Court property. Because both
systems are connected one effluent pipe, Mr. Boj will request that the permit associated with 41
Driftwood Court (NCG550151) be rescinded after the effluent pipe on the 43 Driftwood Court property
is located (per instructions from Mr. Charles Weaver (NCDEQ Permitting Staff)).
Mr. Boj also indicated that 44 Driftwood Court currently has a septic system permit from the Local
Health Department, as there was previous confusion regarding the system on this property.
Effluent pipe/effluent sampling: The effluent pipe could not be located at the time of the inspection.
Mr. Boj indicated that he would have the effluent pipe located when the septic tanks are pumped in
March 2023. Once the effluent pipe is located, the pipe should be checked at least twice a year to
determine if the system is discharging and to ensure that no obvious evidence of system
malfunctioning is observed. If at any point throughout the year the effluent pipe is discharging, annual
sampling is required per General Permit NCG550000, Part I, Section C. Monitoring requirements are
based on the surface water classification of the receiving water.
Disinfection (chlorination)/dechlorination: Chlorination/dechlorination is required per General Permit
NCG550000, Part I, B.(1.). This system currently does not have chlorination/dechlorination. Mr.
Boj indicated that he would have both added to the system when the septic tanks are pumped in
March 2023.
The following deficiencies were noted during the inspection:
Effluent pipe: At the time of the inspection, the effluent pipe could not be located.
Chlorination/dechlorination: The system does not currently have chlorination/dechlorination.
NCG550152 17 (Cont.)
Page#2
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
Permit:NCG550152
Inspection Date:11/08/2022
Owner - Facility:
Inspection Type:
43 Driftwood Court
Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
At the time of the inspection, Mr. Boj indicated that the septic tanks at 41 and 43
Driftwood Court both enter one sand filter from a junction box, and that sand filter is
connected to one effluent pipe located on the 43 Driftwood Court property. See
summary for details.
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Mr. Boj indicated that the septic tanks (41 and 43 Driftwood Court) are pumped every
March. Both septic tanks were pumped on March 29, 2022 by Able Septic Tank
Service.
Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
Comment:
Page#3
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
Permit:NCG550152
Inspection Date:11/08/2022
Owner - Facility:
Inspection Type:
43 Driftwood Court
Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
The system does not currently have disinfection.Comment:
De-chlorination Yes No NA NE
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de-chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de-chlorinators operational?
Number of tubes in use?
The system does not currently have dechlorination.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
At the time of the inspection, the effluent pipe could not be located. See summary for
details.
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Page#4
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34
Permit:NCG550152
Inspection Date:11/08/2022
Owner - Facility:
Inspection Type:
43 Driftwood Court
Compliance Evaluation
Effluent Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
The effluent pipe has not been located, therefore the pipe has not been checked to
determine whether or not it is discharging. Once the pipe has been located, annual
sampling is required if the pipe is discharging. See summary for details.
Comment:
Page#5
DocuSign Envelope ID: FD4CB028-E657-40D0-8A00-787D912A0E34