HomeMy WebLinkAboutNC0032212_Denial_20160330s.
PAT MCCRORY
Water Resources
ENVIRONMENTAL DUALITY
Jadd Brewer, Operations Manager/Signatory
Water Quality Lab & Operations, Inc.
PO Box 1167 / Tynecastle Hwy
Banner Elk, North Carolina 28604
Dear Mr. Brewer:
DONALD R. VAN DER VAART
Sccrrlaly
S. JAY ZIMMERMAN
March 30, 2016
Subject: Concerning Your Request
to Modify Three NPDES Permits
Watauga County .
Director
The Division of Water Resources (the Division) hereby acknowledges your February 29, 2016 request to
modify the following NPDES permits:
1. NC0030473 - Mill Ridge Development WWTP
2. NC0061425 - Willow Valley WWTP
3. NC0032212 - Yonahlossee WWTP
We understand that you would prefer a "Grab" sampling instead of "Composite" sampling protocol. You
base your request on "...flow data that reflects that the plant has not exceeded 30,000 gpd inflow over the
past three (3) years." However, upon review of the BIMS/DMR database, we find flow rates exceeding
0.030 MGD reported for each of the above facilities. The most contrary example, Mill Ridge WWTP,
reported maximum rates of 0.072 MGD (2014), 0.095 (2015) and 0.064 MGD (2016). Considering a flow
limit of 0.052 MGD, these are permit violations, likely unassessed.
Please understand that North Carolina Rule bases Composite sampling on design flow; these are
mandatory for all systems designed at 0.030 MGD or greater. The Rule lists grab only samples as
parameter -specific exceptions to those requiring composites [see T15A. 02B.0500 (3) (B) and (3) (C)]. Our
review of the above NPDES permits shows that parameters are correctly identified in each as "Grab," i.e.,
we find no errors as issued.
In light of the above -identified conditions and records, the Division must deny your request. If you have
questions concerning this ruling, please email Joe R. Corporon, L.G. [joe.corporon@ncdenr.gov] or call
his direct line [919-807-6394].
fully,
S. Jay Zimmerman, L.G.
hc: NPDES Program Files
DWR/WSRO/SWPS, Sherri Knight, Supervisor
Central Files
ec: WSRO/SWPS, Sherri Knight, Supervisor
WSRO/SWPS George Smith
State of North Carolina I Environmental Quality I Water Resources
1611 Mail service Center I Raleigh, North Carolina 27699-1611
919 707 9000
Water Quality Lab & Operations, Inc.
P.O. Box 1167/ 1522 Tynecastle Highway
Banner Elk, NC 28604
Ph. 828-898-6277 Fax 828-898-6255
February 17, 2016
Mr. Joe Corporon
Division of Water Resources
WQ Permitting Section - NPDES
1617 Mail Service Center
Raleigh, NC 27699-1617
Re: Yonahlossee WWTP
Mr. Corporon:
RECEIVED/NCDEQ/DWR
PER 2 9 2016
Water Quality
Permitting Section
3 2 2c 2
I am writing to request that Yonahlossee, NPDES Number NC00332212, have their
permit amended to reflect that their samples are changed from flow proportional
sampling to grab sampling. Our request is based on flow data that reflects that the plant
has not exceeded 30,000 gallons in flow over the past three (3) years. We intend to
request the same when their permit renews in 2017.
I appreciate your time and attention to this matter. Please feel free to contact me with any
questions or concerns.
Sincerely,
fadd Brewer
Signatory for Yonahlossee
Operations Manager of Water Quality Labs
Cc: Charles Weaver, Winston-Salem Regional Office
George Smith, Winston-Salem Regional Office
Ovc)td E.YA)
d 0 4-0
b • �`�