SUBJECT: Compliance Evaluation Inspection
Irwin Creek WWTP
NPDES Permit No. NC0024945
Mecklenburg County
Dear Mr. Lockler:
NORTH CAROLINA
Environmental Quality
November 16, 2022
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on November 9, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge
(ORC) of our findings by forwarding the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
D_E
o,.mworkt G.ed o �
Sincerely,
DocuSigned by:
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
L
NPDES yr/mo/day Inspection Type Inspector Fac
3 I NC0024945 111 121 22/11/09 117 1810I 191 S I 2011
Type
21
1
1 1
1 1
1
1
1
1
11
1 1 1 I I
I 1 1
1
1
1
1
I
I I
I I
I I 1
1
1
1 11
1 1 1 I 1
P6
Inspection
67I2.0
Work Days
Facility Self -Monitoring
I 70I4
Evaluation Rating
I 71IN
B1
I 72
QA
I N I
731
1
I I
Reserved
74 751
1
I
I I
I
I
I
180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Irwin Creek WWTP
4000 Westmont Dr
Charlotte NC 28217
Entry Time/Date
09:20AM 22/11/09
Permit Effective Date
17/10/01
Exit Time/Date
01:05PM 22/11/09
Permit Expiration Date
22/05/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Jacob Wayne Bolick/ORC/704-336-2573/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Angela D Charles,5100 Brookshire Blvd Charlotte NC 282163371//704-336-5911/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DocuSigned by:
DWR/MRO WQ/704-663-1699 Ext.2192/ 11/16/2022
Lle&,, 3dit
A61696D90CC3437...
Signature of Managpmtcl
Andrew Pitner
g,aRjewer Agency/Office/Phone and Fax Numbers Date
i 4.Ie.ao ElP41A/R/MRO WQ/704-663-1699 Ext.2180/ 11/16/2022
EPA Form 3560-3 Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0024945 111 121 22/11/09
117
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On -site Representatives:
The following Charlotte Water staff were in attendance during the inspection: Mr. Jacob Bolick, Mr.
Tony Sponelli, Mr. Shannon Sypolt, Mr. Doug Wise, Mr. Michael Christiansen and Ms. Muriel Steele.
Page# 2
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The Division received Charlotte Water's permit renewal documentation on 12/1/2021.
Charlotte Water implements a Division approved Industrial Pretreatment Program.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 10/27/2020.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis ■
Name of person performing analyses ■
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? • ❑ ❑ ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ■ ❑ ❑ ❑
operator on each shift?
Is the ORC visitation log available and current? • El ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • El El El
Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? • El El El
Facility has copy of previous year's Annual Report on file for review? El El El •
Page# 3
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge Monitoring Reports (eDMRs) were reviewed from October 2021 through
September 2022. No limit and/or monitoring violations were noted during the review
period.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Influent and effluent analyses are performed by Charlotte Water Environmental
Services Laboratory (Certification #192). ETT Environmental and ETS have been
contracted to perform effluent chronic toxicity tests.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The subject permit requires influent BOD and TSS composite samples. The composite
samplers are calibrated weekly and checked (for proper operation) every shift.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ El
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Page# 4
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: The subject permit requires composite and grab effluent samples. The composite
samplers are calibrated weekly and checked (for proper operation) every shift.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well
maintained. Facility staff incorporate a comprehensive process control program with all
measurements being properly documented and maintained on -site. In-depth
operation and maintenance records are also maintained on -site. Approximately nine
(9) SCADA stations are located throughout the treatment plant site.
The facility's SCADA system was operational and in service.
Equalization Basins Yes No NA NE
Is the basin aerated? ❑ El • El
Is the basin free of bypass lines or structures to the natural environment? • El El El
Is the basin free of excessive grease? • El El El
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? ■ El El El
Are float controls operable? • El El El
Are audible and visual alarms operable? El El • El
# Is basin size/volume adequate? • ❑ ❑ ❑
Comment: The facility is equipped with a 30 MG equalization basin (10 MG cell and a 20 MG cell).
The equalization basin is connected to the on -site SCADA system. The facility also has
the capability of diverting influent flows to the Charlotte Water/McAlpine Creek WWTP
for final treatment/disposal.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Yes No NA NE
•
Page# 5
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? • ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • El El El
Are float controls operable? • El El El
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? • El El El
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: The flow meter is calibrated twice per year and was calibrated on 7/28/2022 by CITI,
LLC.
Grit Removal Yes No NA NE
Type of grit removal
a.Manual El
b.Mechanical •
Is the grit free of excessive organic matter? • El El El
Is the grit free of excessive odor? • El El El
# Is disposal of grit in compliance? • ❑ ❑ ❑
Comment: Screenings and grit are disposed at the Republic Services/CMS Landfill located in
Cabarrus County.
Primary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Yes No NA NE
• ❑ ❑ ❑
Page# 6
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Primary Clarifier Yes No NA NE
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the sludge blanket level acceptable?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: All three primaries were operational; however, only one was in service.
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? ■ ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: All seven aeration basins were operational and in service. Each aeration basin is
equipped with an anoxic zone with mixing. Magnesium hydroxide is added prior to the
aeration basins to maintain appropriate alkalinity/pH levels.
Chemical Feed
Is containment adequate?
Is storage adequate?
Are backup pumps available?
Is the site free of excessive leaking?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The facility is equipped with a chemical feed and storage facility for alum and
magnesium hydroxide.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Yes No NA NE
Page# 7
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: All four secondaries were operational; however, only three were in service.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Down flow
Is the filter media present? • ❑ ❑ ❑
Is the filter surface free of clogging? • ❑ ❑ ❑
Is the filter free of growth? • ❑ ❑ ❑
Is the air scour operational? • ❑ ❑ ❑
Is the scouring acceptable? • ❑ ❑ ❑
Is the clear well free of excessive solids and filter media? • ❑ ❑ ❑
Comment: All ten tertiary filters were operational and in service.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment: Both UV channels were operational.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ • ❑
Comment: The flow meter is calibrated twice per year and was calibrated on 7/28/2022 by CITI,
LLC.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did
not appear to be negatively impacted. Fish were observed at the confluence of the
effluent discharge and receiving stream.
Anaerobic Digester
Type of operation:
Is the capacity adequate?
# Is gas stored on site?
Is the digester(s) free of tilting covers?
Is the gas burner operational?
Is the digester heated?
Is the temperature maintained constantly?
Is tankage available for properly waste sludge?
Yes No NA NE
Fixed cover
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The facility is equipped with four primary anaerobic digesters and two storage tanks
(floating cover). Three primary digesters and one storage tank were in service. The
fourth primary digester was in the process of being cleaned out by a contracted
company (Bio-Nomic Services).
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 9
Permit: NC0024945
Inspection Date: 11/09/2022
Owner - Facility: Irwin Creek WWTP
Inspection Type: Compliance Evaluation
Solids Handling Equipment Yes No NA NE
The facility has an approved sludge management plan? • ❑ ❑ ❑
Comment: The facility is equipped with 2-gravity belt thickeners, 2-belt filter presses, WAS storage
tank (aerated), filtrate storage tank (aerated), bio-solids storage tank and a covered
bio-solids storage pad. All treatment units were operational.
Dewatered bio-solids are land applied by a contract company (Syangro) under the
authority of Permit No. WQ00O0057.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
Comment: Both backup generators are tested under load monthly and serviced quarterly by
Carolina CAT.