SUBJECT: Notice of Deficiency
Compliance Evaluation Inspection
Origin Food Group, LLC. WWTP
NPDES Permit No. NC0077615
Iredell County
Tracking #: NOD-2022-PC-0191
Dear Mr. Ulukaya:
NORTH CAROLINA
Environmental Quality
November 21, 2022
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on November 8, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge
(ORC) of our findings by forwarding the enclosed report.
This report is being issued as a Notice of Deficiency (NOD) due to the failure to have a designated operator perform the
required visitations (for approximately one month) which is a violation of the subject NPDES Permit and North Carolina
General Statute (G.S.) 143-215.1. Please note that G.S. 143-215.6A provides for a civil penalty of not more than twenty-five
thousand dollars ($25,000.00), or twenty-five thousand dollars ($25,000.00) per day when the violation is of a continuing
nature, against any person who violates or fails to act in accordance with the terms, conditions, or requirements of any permit
issued pursuant to G.S. 143-215.1. Penalties may also be assessed for any damage to surface waters of the State that may result
from the violation.
D_E
11,arliworkt el G. ritmloalal Oat'
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
It is requested that a written response be submitted to this Office by December 12, 2022, detailing the actions taken to
address the violation as discussed in more detail in the attached report. In responding, please address your comments to the
attention of Mr. Wes Bell.
Should you have any questions concerning this Notice, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
DNORTH CAPOLI.
_E
111.•rhworkt G. rOrmloalal Oat,'
Sincerely,
�DocuSigned by:
fi4 44 4/ H p;zW'
F161FB69A2D84A3...
Andrew H. Pitner, P.G.
Assistant Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 I5
21 1 1 1 1
NPDES yr/mo/day Inspection
I 3 I NC0077615 111 121 22/11/08 117
Type
18 i i
I I 1 1 1
Inspector Fac Type
191 S I 201
1 1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I2.0 I 70I4 I 71IN I 72 I N I 731 I 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Origin Food Group, LLC
306 Stamey Farm Rd
Statesville NC 28677
Entry Time/Date
11:35AM 22/11/08
Permit Effective Date
19/04/01
Exit Time/Date
01:OOPM 22/11/08
Permit Expiration Date
24/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Dennis W Murdock//828-238-4659 /
Todd Robinson/Area Manager/252-235-8809 /
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Halil Ulukaya,306 Stamey Farm Rd Statesville NC 28687//518-221-0830/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
�Docusiyned by: DWR/MRO WQ/704-663-1699 Ext.2192/
111/21/2022
Oe
"-A61696D9OCC3437...
Signature of Man ildigigukeRaviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitn r �4' ' H P4451NR/MRO WQ/704-663-1699 Ext.2180/ 11/21/2022
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
sI
NPDES yr/mo/day
NC0077615 111 121 22/11/08
I17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
RECORD KEEPING SECTION cont'd:
The facility was not being operated/visited by one of the designated backup ORCs following the
resignation of the previous ORC in September 2022. The non -designated operator has been visiting
the wastewater facility for approximately one month. Please be advised that the subject permit
requires that either the designated ORC or backup ORC(s) must visit the facility five days per week
excluding holidays [Permit Condition Reference: Part II, Section C(1) Certified Operator]. The
Permittee must ensure one of the designated backup ORCs operate/visit the facility until a new ORC
is designated (within 120 days).
Page# 2
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El • ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El El • El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff
on 7/16/2020.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 3
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge Monitoring Reports (eDMRs) were reviewed from October 2021 through
September 2022. Effluent BOD limit violations were reported in May 2022 (daily
maximum) and August 2022 (daily maximum and monthly average). Effluent TSS limit
violations were reported in May 2022 (daily maximum and monthly average), July 2022
(daily maximum) and August 2022 (daily maximum and monthly average). The Division
has previously addressed these limit violations through the issuances of civil penalty
assessments. See "Summary" Section for additional comments.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: On -site field analyses (pH, temperature and total residual chlorine) are performed
under Environlink's field laboratory certification #5212. Statesville Analytical has also
been contracted to perform analyses of all permit -required parameters except field.
The facility staff must ensure that post calibration checks are performed (on all
applicable meters) at the end of the day if these meters are used to perform effluent
analyses at multiple facilities (Reference: NC Wastewater/Groundwater Laboratory
Certification - Approved Procedure for the analyses of dissolved oxygen, pH and total
residual chlorine).
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ❑ ❑ • ❑
Is the tubing clean? ❑ ❑ ■ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: The subject permit requires effluent grab samples.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Yes No NA NE
Page# 4
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility continues to receive low influent flows and the wastewater is treated on a
batch basis. The wastewater treatment facility appeared to be adequately treating the
wastewater at the time of the inspection. Process control measurements are being
performed and documented.
The permittee must ensure to replace all grating and railing that exhibits signs of
deterioration and rust. In addition, the permittee must ensure all areas on the clarifier
and chlorination areas are equipped with proper grating and railing.
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? El El • El
Page# 5
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? ■ ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: Both blower/motor units were operational and both check valves operated properly
during the on -site test.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? • El El El
Is the contact chamber free of growth, or sludge buildup? • El El El
Is there chlorine residual prior to de -chlorination? • ❑ ❑ ❑
Comment: Calcium hypochlorite tablets are used for disinfection.
De -chlorination
Type of system ?
Yes No NA NE
Tablet
Page# 6
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
De -chlorination
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment: Sodium Sulfite tablets are used for dechlorination.
Yes No NA NE
• ❑ ❑ ❑
2
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? El El • El
Is flow meter calibrated annually? El El • El
Is the flow meter operational? ❑ El • ❑
(If units are separated) Does the chart recorder match the flow meter? El ❑ • ❑
Comment: Instantaneous flow measurements are based on pump run time and pump flow rate
(2.3 gpm).
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? El El El •
Are the receiving water free of foam other than trace amounts and other debris? ❑ ❑ ❑ •
If effluent (diffuser pipes are required) are they operating properly? ❑ ❑ • ❑
Comment: The effluent appeared clear with no floatable solids or foam.
Aerobic Digester Yes No NA NE
Is the capacity adequate? • ❑ ❑ ❑
Is the mixing adequate? • ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • El ❑ ❑
# Is the odor acceptable? • ❑ ❑ ❑
# Is tankage available for properly waste sludge? • ❑ ❑ ❑
Page# 7
Permit: NC0077615
Inspection Date: 11/08/2022
Owner - Facility: Origin Food Group, LLC
Inspection Type: Compliance Evaluation
Aerobic Digester Yes No NA NE
Comment: The facility is equipped with an aerated sludge holding tank. Wastewater solids are
removed on an as -needed basis by Lentz Septic Tank Service.
The permittee should initiate a structural evaluation on the wall between the aerated
sludge holding tank and aeration basin. All identified areas should be repaired as
soon as possible to prevent worsening conditions that could lead to structural failure.
Please be advised that the subject permit requires the permittee to properly operate
and maintain the facility at all times.
Page# 8