HomeMy WebLinkAboutNCG550009_Permit Issuance_19931208State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Environmental Management
James B. Hunt, Jr., Governor
Jonathan B. Howes, Secretary
A. Preston Howard, Jr., P.E., Director
December 8, 1993
Frank Evans
Rt. 6, Box 114
Burnsville, NC 28714
EDEHN1
Subject: General Permit NCG550000
Cert. of Coverage NCG550009
Frank Evans residence
Yancey County
Dear Mr. Evans:
In accordance with your application for an NPDES discharge permit received November 15, 1993
by the Division, we are herewith forwarding the subject Certificate of Coverage under the state-NPDES
general permit for the Frank Evans residence and one set of final approved plans and specifications.
Authorization is hereby granted for the construction and operation of a 1000 GPD wastewater treatment
system consisting of a septic tank, 420 square foot primary sandfilter, 210 square foot secondary
sandfilter, chlorine contact tank, dechlorinator, cascade aeration with discharge of treated wastewater into
Little Crabtree Creek. This Certificate of Coverage is issued pursuant to the requirements of North
Carolina and the US Environmental Protection Agency Memorandum of Agreement dated December 6,
1983 and as subsequently amended.
If any parts, measurement frequencies or sampling requirements contained in this general permit
are unacceptable to you, you have the right to submit an individual permit application and letter requesting
coverage under an individual permit. Unless such demand is made, this decision shall be final and
binding. Please take notice this permit is not transferable. Part II, E.4. addresses the requirements to be
followed in case of change of ownership or control of this discharge.
The Authorization to Construct is issued in accordance with Part III, Paragraph 2 of NPDES
Permit No. NCG550000, and shall be subject to revocation unless the wastewater treatment facilities are
constructed in accordance with the conditions and limitations specified in Permit No. NCG550000.
In the event that the facilities fail to perform satisfactorily, including the creation of nuisance
conditions, the Permittee shall take immediate corrective action, including those as may be required by this
Division, such as the construction of additional or replacement wastewater treatment or disposal facilities.
The Asheville Regional Office, telephone number 704/251-6208, shall be notified at least forty -
Eight (48) hours in advance of operation of the installed facilities so that an in -place inspection can be
made. Such notification to the regional supervisor shall be made during the normal office hours from 8:00
a.m. until 5:00 p.m. on Monday through Friday, excluding State Holidays.
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Emplo; Lt. 50% recycled/ 10% post -consumer paper
- Permit No. NCG550000
Authorization to Construct
Frank Evans
November 8,1993
Page 2
Upon completion of construction and prior to operation of this permitted facility, a certification
must be received• from a professional engineer certifying that the permitted facility has been installed in
accordance with the NPDES Permit, the Certificate of Coverage, this Authorization to Construct and the
approved plans and specifications. Mail the Certification to the Permits and Engineering Unit, P.O. Box
29535, Raleigh, NC 27626-0535.
A copy of the approved plans and specifications shall be maintained on file by the Permittee for the
life of the facility.
The sand media of the primary and secondary sandfilter must comply with the Division's sand
specifications. The engineer's certification will be evidence that this certification has been met.
A leakage test shall be performed on the septic tank and dosing tank to insure that any exfiltration
occurs at a rate which does not exceed twenty (20) gallons per twenty-four (24) hour per 1,000 gallons of
tank capacity. The engineer's certification will serve as proof of compliance with this condition.
Failure to abide by the requirements contained in this Authorization to Construct may subject the
Permittee to an enforcement action by the Division of Environmental Management in accordance with
North Carolina General Statute 143-215.6A to 143-215.6C.
The issuance of this permit does not preclude the Permittee from complying with any and all
statutes, rules, regulations, or ordinances which may be required by the Division of Environmental
Management or permits required by the Division of Land Resources, the Coastal Area Management Act or
any Federal or Local other governmental permit that may be required.
If you have any questions or need additional information, please contact 919/733-5083, telephone
number 919/733-5083.
Sincerely,
Original Si nedBs
Coleen H.
A. Preston Howard, Jr., P.E.
cc: Yancey County Health Department
Asheville Regional Office, Water Quality
Training and Certification Unit
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT, HEALTH, AND NATURAL RESOURCES
DIVISION OF ENVIRONMENTAL MANAGEMENT
CERTIFICATE OF COVERAGE
GENERAL PERMIT NO. NCG550009
TO DISCHARGE DOMESTIC WASTEWATERS FROM SINGLE FAMILY RESIDENCES AND OTHER
DISCHARGES WITH SIMILIAR CHARACTERISTICS UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provision of North Carolina General Statute 143-215.1, other lawful standards and
regulations promulgated and adopted by the North Carolina Environmental Management Commission, and the
Federal Water Pollution Control Act, as amended,
Mr. Frank Evans
is hereby authorized to construct and operate a 360 GPD wastewater treatment facility consisting of a septic tank, a
primary sand filter, secondary sandfilter, chlorinator, chlorine contact tank, cascade aerator, dechlorination and
associated appurtenances with the discharge of treated wastewater from a facility located at the
Evans Residence
on NCSR 1427
Yancey County
to receiving waters designated as Little Crabtree Creek in the French Broad River Basin
in accordance with the effluent limitations, monitoring requirements, and other conditions set forth in Parts I, II, III
and 1V hereof.
This certificate of coverage shall become effective December 10,1993
This Certificate of Coverage shall remain in effect for the duration of the General Permit.
Signed this day, December 10,1993
Original Signed i Bs
Coleen H
A. Preston Howard, 3r.R.E., Director
Division of Environmental Management
By Authority of the Environmental Management Commission
r'
ENGINEERS CERTIFICATION FOR CONSTRUCTION OF TREATMENT FACILITIES
I, as a duly registered Professional Engineer in the State
of North Carolina, having been authorized to observe (periodically, weekly, full time)
the construction of
the project, f o r
the Project Name Location
Permittee hereby state that, to the best of my abilities, due care and diligence was
used in the observation of the construction such that the construction was observed
to be built within substantial compliance and intent of the approved plans and
specifications.
Signature Registration No.
Date
• :.. Ar----7 to.0 sit L...
- t p.-„,-,r,,e-o_fi,
7 hORM C.gROLINA VtRtiatiAGEliENT
WE: a
PERT NO.
REVIEW ENGINEER: ,
S 79•39.f
CONCRETE
HEADWALL
N08•18'F-19.45*
Rny
0165'
a•
1
•'Y•.1Ci)ti4 Nor .
•
• .titer "Y.7 �..:' •s�•R' ••� -•l;. •YiL'w't�•ti 4:ti� �..::
•.
a
L.
•?.9•c.
•
s eO.2o•oLp
130.0r U.S /9E
kLZ. /127
STEPS
Wc r Ns�
Bin
S 83'4T' E --��
( paved ) 110.86'
• groove/ parking
t48 Acres
4176• • •
�NgZ3,2W
�--N 85'59' W
BY COMMUTE GEOMETRY
3%pnt
3 )o
rest err
ROCK 1
• RETAINING
WALL
r•
1•
It
•.
1•
to
•
•
•
.
.
•
rwo sroRr
GARAGE
+t + Parr
R"
3"
r''
r fee
SERVICE
t POLE •
N
r'
Jv SccamilsRY
Vitt v Fa., f«t
COL* R,iNAt°it.
•
air
�� Qvt tl µ?
54.
.
\�
AN,
• I.
.0
•
CREE/rC 11+ .•
56.34' • • 47.64'
N 89'4T W
.•
!Oe
Fr
I
1 O „ ,
itir,
• neolri
• t• Pail.l'.1'
• r •
I
.mow'.••
•
IT -820
75
.4 Creek
7? -ff�F141
tp
tfl
• r
17130"
owlen
385
•
FrAwc.xvi..451 151411aLlkia•Ls
Zii ti I
t!z3
b
t", iq •
• +•I
,
• •
••
. r ••-1 .
,atenson—GEoLoG,CwL •VnrEr. NESTOt •0•04•1w-1990
ROAD ri AccIFir.,Ti' J .•
•
Windom`'
3976
55'
•hN
..a
W
Id
n73
t
3972
•`�/ .-•
• jI
• i • I
3971 •N.
.4• 1
387 000m.E 82 0 15
35° 52' 30"
(TVA 200-NE) "-
SOC PRIORITY PROJECT: Yes No X
IF YES, SOC NUMBER
NOV 2 4 1993
TO: PERMITS AND ENGINEERING UNIT
WATER QUALITY SECTION
ATTENTION: Mack Wiggins
DATE: November 19, 1993
NPDES STAFF REPORT AND RECOMMENDATION
COUNTY Yancey
PERMIT NUMBER NCG550009
PART I - GENERAL INFORMATION
CrR-Af-er. U« —
1. Facility and Address: Frank Evans Residence
Rt. 6, Box 114
Burnsville, North Carolina 28714
2. Date of Investigation: August 3, 1993
3. Report Prepared By: Michael R. Parker
4. Persons Contacted and Telephone Number:
Frank Evans
704/682-2015
5. Directions to Site: From the intersection of U.S. Highway 19E and
North Carolina Secondary Road 1427, travel east on NCSR 1427 0.35
mile. The site is located on the right behind the residence.
6. Discharge Point(s), List for all discharge points:
Latitude: 35054'56" Longitude: 82°15'47"
Attach a USGS map extract and indicate treatment facility site and
discharge point on map.
U.S.G.S. Quad No. D9NE U.S.G.S. Quad Name Burnsville, N.C.
7. Site size and expansion area consistent with application?
X Yes
No If No, explain:
8. Topography (relationship to flood plain included): System will
be installed in flat area approximately 50 feet from stream.
Page 1
PLOTTED
9. Location of nearest dwelling: Approximately 200 feet.
10. Receiving stream or affected surface waters: Little Crabtree
Creeek
a. Classification: C-trout
b. River Basin and Subbasin No.: 040306
c. Describe receiving stream features and pertinent downstream
uses: fishing, fish and wildlife propagation, wading,
irrigation
PART II - DESCRIPTION OF DISCHARGE AND TREATMENT WORKS
1. a. Volume of wastewater to be permitted 0.0001 MGD (Ultimate
Design Capacity)
b. What is the current permitted capacity of the Wastewater
Treatment facility?
c. Actual treatment capacity of the current facility (current
design capacity
d. Date(s) and construction activities allowed by previous
Authorizations to Construct issued in the previous two years:
NA
e. Please provide a description of existing or substantially
constructed wastewater treatment facilities:
f. Please provide a description of proposed wastewater treatment
facilities: It is proposed to install a 1000 gallon septic
tank and construct a primary sand filter 6 ft. X 70 ft. X 3
ft. a secondary sand filter 3 ft. X 70 ft. x 3 ft. a chlorine
contact tank and chlorinator and cascade aerator.
Dechlorination should also be provided.
g-
Possible toxic impacts to surface waters: NA
h. Pretreatment Program (POTWs only):
in development approved
should be required not needed
2. Residuals handling and utilization/disposal scheme: Solids will be
removed by a septic tank hauler.
a. If residuals are being land applied, please specify DEM
Permit Number
Residuals Contractor
Telephone Number
b. Residuals stabilization: PSRP PFRP OTHER
Page 2
c. Landfill:
d. Other disposal/utilization scheme (Specify):
3. Treatment plant classification (attach completed rating sheet):
Class I
4. SIC Codes(s): 4952
Wastewater Code(s) of actual wastewater, not particular facilities
i.e., non -contact cooling water discharge from a metal plating
company would be 14, not 56.
Primary 04 Secondary
Main Treatment Unit Code: 46
PART III - OTHER PERTINENT INFORMATION
1. Is this facility being constructed with Construction Grant Funds
or are any public monies involved. (municipals only)? No
2. Special monitoring or
None
3. Important SOC, JOC,
indicate)
limitations (including toxicity) requests:
or Compliance Schedule dates: (Please
Submission of Plans and Specifications
Begin Construction
Complete Construction
Date
4. Alternative Analysis Evaluation: Has the facility evaluated all
of the non -discharge options available. Please provide regional
perspective for each option evaluated.
Spray Irrigation: There is not enough area with set back distances
from house, road and stream.
Connection to Regional Sewer System: Regional sewer is
approximately 1/2 to 3/4 mile away and cost prohibitive.
Subsurface: Yancey County Sanitarians looked at site and turned it
down due to high ground water.
Other disposal options: No other option than a discharging system
appears to be economically feasible at this time.
5. Other Special Items:
Page 3
f
PART IV - EVALUATION AND RECOMMENDATIONS
Mr. Frank Evans has made application for an NPDES permit to
discharge wastewater from a residence into Little Crabtree Creek.
The Yancey County Health Department has turned down the site due
to high groundwater and no other alternative appears to be
economically feasible.
Mr. Evans has prepared sketches for the proposed system and since
the proposed discharge is to trout waters dechlorination facilities are
needed.
It is recommended that the permit be issued as long as
dechlorination facilities are provided.
I.�
Signature of Report reparer
Writer Qual'ty Re ional Supervisor
7E
Date
RATING SCALE FOR CLASSIFICATION OF WATER POLLUTION CONTROL SYSTEMS
Name of Facility: fti.AN1. EL/ANS.
12e s ;
Owner or Contact Person:
Mailing Address: fe4. / Vog. //9
County: c.1�o�vLe cam.
Present Classification:
NPDES Per. No. NC SSO o9
0,Nsh/t.. ,/U.c. 2J7/V
Telephone: 70'71
New Facility ✓ Existing Facility
Per. No.WQ Health Dept.Per No.
Rated by: /Vl i .r e.1 2. 7,4i .---- Telephone: 7o'/zs/-6Z.O., Date:
Reviewed by: n _ Health Dept.
Regional Office
Central Office
ORC: Grade:
Nondisc.
Check Classification(s): Subsu
Wastewater Classification: (Circle One)
Spray Irrigation
II III IV
Telephone:
Telephone:
Telephone:
Telephone:
Land Application
Total Points:
IN -PLANT PROCESSES AND RELATED CONTROL EQUIPMENT WHICH ARE AN INTEGRAL PART OF INDUSTRIAL PRODUCTION SHALL NOT BE
CONSIDERED WASTE TREATMENT FOR THE PURPOSE OF CLASSIFICATION. ALSO SEPTIC TANK SYSTEMS CONSISTING ONLY OF SEPTIC TAM(
AND GRAVITY NITRIFICATION LINES ARE EXEMPT FROM CLASSIFICATION.
SUBSURFACE CLASSIFICATION
(check all units that apply)
1. septic tanks
2. pump tanks
3. siphon or pump -dosing systems
4. sand filters
5. grease trap/interceptor
6oil/water separators
7gravity subsurface treatment and disposal:
8. pressure subsurface treatment and disposal:
SPRAY IRRIGATION CLASSIFICATION
(check all units that apply)
1. preliminary treatment (definition no. 32 )
2. lagoons
3. septic tanks
4. pump tanks
5. pumps
6. sand filters
7. grease trap/interceptor
8. oil/water separators
9.disinfection
10. chemical addition for nutrient/algae control
11. spray irrigation of wastewater
in addition to the above classifications, pretreatment of wastewater in excess of these components shall
be rated using the point rating system and will require an operator with an appropriate dual certification.
LAND APPLICATION/RESIDUALS CLASSIFICATION (Applies only to permit holder)
1. Land application of biosolids, residuals or contaminated soils on a designated site.
WASTEWATER TREATMENT FACILITY CLASSIFICATION
The following systems shall be assigned a Class 1 classification, unless the flow is of a significant quantity or the technology is unusually
complex, to require consideration by the Commission on a case -by -case basis: (Check if Appropriate)
1. OiVwater Separator Systems consisting only of physical separation, pumps and disposal;
2. Septic Tank/Sand Fitter Systems consisting only of septic tanks, dosing apparatus, pumps.sand filters, disinfection
and direct discharge;
3. Lagoon Systems consisting only of preliminary treatment, lagoons, pumps, disinfection, necessary chemical treatment for
algae or nutrient control, and direct discharge;
4. Closed -loop Recycle Systems;
5. Groundwater Remediation Systems consisting only of oiVwater separators, pumps, air -stripping, carbon adsorption, disinfection
and disposal;
6. Aquaculture operations with discharge to surface waters;
7. Water Plant sludge handling and back -wash water treatment;
8. Seafood processing consisting of screening and disposal.
9._Single-family discharging systems, with the exception of Aerobic Treatment Units, will be classified if permitted after July 1,
1993 or if upon inspection by the Division, it is found that the system is not being adequately operated or maintained. Such
systems will be notified of the classification or reclassification by the Commission, In writing.
4-0/11.4 R44.424„,_
- in(oln
:'.: Palm" 1 •
•� �,�,1• ,f-
• ♦p
028
i3r� 1,..e
1(1011, �a
•
�
v
r
+
., .UP
Trailer
Park
'7 L
,J
•
1) 1)
hh t 'l�
1f17F` r e e� �� • T •. ilef
. �.ITEtipVW.AMV.
t Mitchel \ • • •� •. ,'f
s+• ...; .Tan so r
�' `• ' 3,Ca + • • / • f , ♦
s.
La J : Vh l�r(. / ` Oh;
" - : `:.r(
~i, 5 , ��. , �-o 1'r LR-248 ( r.:,\ __ S " railer. . � .
�; , ,� _ "-294 .,� ------ a
•
> . . 7
.C' er ek -.-.
:,l
BANKS CEM
t , GCr
\♦.
h Mtn
383 1 7' 30"
9
• •L� •1 _ ;
7 (,,
Dkmoo
rat:,1 1�
A 22:
1,)
Bowlerisc Creek
QM LW" 823
•
•
384
ML 821 3aoc3�
.,,V t ewe t ,
R oo
g ons Pyr�r�id
4908` �„�'�tki
y 38� N1 t COCK? ..I , •'k.K!
UU .
Windom
f;I
3976
55'
3973
3972
Demo al
3971000" N
Iuerock Knob=14e59 -�
v,> 1990 • 387^ E. 35° tl J' ;0.,
82°1
lrvn 200 -Nr,