HomeMy WebLinkAboutNC0079740_Compliance Evaluation Inspection_20221013ROY COOPER
Governor
ELIZABETH 5. BISER
5ecrefvey
RICHARD E. ROGERS, JR.
Director
Ricky C Duncan
City of Kings Mountain
PO Box 429
Kings Mountain, NC 28086
Dear Mr. Duncan:
NORTH CAROL! NA
Entilironmrrtlral Qualify
October 13, 2022
Subject: Compliance Evaluation Inspection
T.J Ellison WTP
NPDES Permit No. NC0079740
Cleveland County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the
subject facility on October 11, 2022, by Ori Tuvia. Newt Henson's cooperation during the site visit
was much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy
of the enclosed repot.
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
Cc: MRO Files (Laserfiche)
Sincerely,
-DocuSigned by:
Iz 014e4V H
-F161 FB69A2D84A3...
Andrew H. Pitner P.G., Assistant Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
16.L�r ort��
State of North Carolina 1 Environmental Quality 1 Water Resources 1 Water Quality Regional Operations
Mooresville Regional Office 1 610 East Center Avenue, Suite 301 1 Mooresville, North Carolina 28115
704 663 1699
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 I5
21IIIIII
NPDES yr/mo/day Inspection
I 3 I NC0079740 111 121 22/10/11 117
Type
18110
IIIIIIIIIII
Inspector Fac Type
19 I S I 201
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 731 I 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Ellison WTP
1432 Oak Grove Rd
Kings Mountain NC 28086
Entry Time/Date
11:30AM 22/10/11
Permit Effective Date
19/01/01
Exit Time/Date
12:10PM 22/10/11
Permit Expiration Date
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Newt E. Henson/ORC/704-482-7131/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Newt E. Henson,PO Box 429 Kings Mountain NC
280860429/Su pervisor/704-482-7131 / No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and
Ori A Tuvia
Signature(s)
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
by:
—-- DWR/Division of Water Quality/704-663-1699/
10/12/2022
BB057A2DE017498...
,—DocuSigned
`—
Signature of Man
Andrew Pitne
emWeittl9AeFkliiewer Agency/Office/Phone and Fax Numbers Date
A4.44414,1 H PR/MRO WQ/704-663-1699 Ext.2180/ 10.13.22
F161 FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0079740 111 121 22/10/11
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0079740
Inspection Date: 10/11/2022
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The subject permit expires on 8/31/2023.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ • ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
Comment: The records reviewed during the inspection were organized and well maintained.
DMRs, COCs, ORC logs, and Calibration logs were reviewed for the period April 2022
through June 2022.
Page# 3
Permit: NC0079740
Inspection Date: 10/11/2022
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: Field analyses (pH and total residual chlorine) are performed under the on -site
laboratory certification #5597. Water Tech Labs (total suspended solids, trubidity ,
total nitrogen and total phosphorus), Pace and Toxcity (metals, toxicity) have also been
contracted to provide analytical support. The laboratory instrumentation used for field
analyses appeared to be properly calibrated/verified and documented
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ El • El
Is sample collected below all treatment units? • ❑ El El
Is proper volume collected? • El El El
Is the tubing clean? ❑ El • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 El El • El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El ❑ El
representative)?
Comment: The subject permit requires effluent grab sampling.
Upstream / Downstream Sampling
Is the facility sampling performed as required by the permit (frequency, sampling type,
and sampling location)?
Comment:
Yes No NA NE
• ❑ ❑ ❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El El El
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable DOME
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The NPDES treatment system includes a dechlorination unit, primary settling tank,
overflow tank, and sludge dewatering system. A polymer is added to the influent of the
settling tank to enhance settling. The NPDES facilities appeared to be properly
operated and well maintained. The facility has been upgraded adding dechlornartion
contact chamber, SCADA system and flow meter
Page# 4
Permit: NC0079740
Inspection Date: 10/11/2022
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ • ❑
Is storage appropriate for cylinders? ❑ ❑ ■ ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ • ❑
Are the tablets the proper size and type? ❑ ❑ • ❑
Comment: Liquid sodium thiosulfate is added (via dosage pump) for dechlorination prior to the
settling tank. The dechlorination pump system is only activated during discharge
events.
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
Page# 5
Permit: NC0079740
Inspection Date: 10/11/2022
Owner - Facility: Ellison WTP
Inspection Type: Compliance Evaluation
Solids Handling Equipment Yes No NA NE
Comment: Dewatered alum sludge is transported (by facility staff) to the County Landfill for final
disposal.
Page# 6