Steve Sharpe
Iredell-Statesville Schools
350 Old Murdock Road
Troutman, NC 28166
SUBJECT: Compliance Evaluation Inspection
North Iredell High School WWTP
NPDES Permit No. NC0037371
Iredell County
Dear Mr. Sharpe:
NORTH CAROLINA
Environmental Quality
October 28, 2022
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on October 12, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge
(ORC) of our findings by forwarding the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
DILLORIN
_E
Sincerely,
,-DocuSigned by:
A4.144w H 1%.14 4
F161 FB69A2D84A3...
Andrew H. Pitner, P.G.
Acting Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
L
NPDES yr/mo/day Inspection Type Inspector Fac
3 I NC0037371 111 121 22/10/12 117 1810I 191 S I 2011
Type
21
1
1 1
1 1
1
1
1
1
11
1 1 1 I I
I 1 1
1
1
1
1
I
I I
I I
I I 1
1
1
1 11
1 1 1 I 1
P6
Inspection
67I2.0
Work Days
Facility Self -Monitoring
I 70I4
Evaluation Rating
I 71IN
B1
I 72
QA
I N I
731
1
I I
Reserved
74 751
1
I
I I
I
I
I
180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
North Iredell High School
156 Raider Rd
Olin NC 28660
Entry Time/Date
09:50AM 22/10/12
Permit Effective Date
19/04/01
Exit Time/Date
10:53AM 22/10/12
Permit Expiration Date
24/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
David Thomas McDaniel//336-880-1115 /
Todd Robinson/Area Manager/252-235-8809 /
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
R Dale Ladd,350 Old Murdock Rd Troutman NC 281669699//704-873-3755/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
-Docusiyned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 10/28/2022
"-A61696D9OCC3437...
Signature of Man
Andrew Pitn
tsta,,@aldeviewer Agency/Office/Phone and Fax Numbers Date
rA44I4 4/ H P4411WR/MRO WQ/704-663-1699 Ext.2180/ 10/28/2022
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0037371 111 121 22/10/12
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0037371
Inspection Date: 10/12/2022
Owner - Facility: North Iredell High School
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El • ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? • El El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff
on 7/16/20.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
El El El El
• ❑ ❑ ❑
Page# 3
Permit: NC0037371
Inspection Date: 10/12/2022
Owner - Facility: North Iredell High School
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge Monitoring Reports (eDMRs) were reviewed from September 2021 through
August 2022. Daily maximum effluent fecal coliform violations were reported in
December 2021 and June 2022. A daily maximum effluent BOD violation was also
reported in May 2022. The Division has previously addressed these limit violations
through the issuances of either Notice of Violations (NOVs) or NOV/civil penalty
assessments.
If effluent samples are collected and analyzed at different locations then the ORC and
staff must ensure that the collection and analysis times are documented to verify
compliance with the 15-minute holding time requirement (Reference: 40 CFR 136.3,
Table Ill
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: On -site field analyses (pH, temperature and total residual chlorine) are performed
under Environlink's field laboratory certification #5212. Statesville Analytical has also
been contracted to perform analyses of all permit -required parameters except field.
The ORC and staff must ensure the calibration/verification times (total residual chlorine
meter) and all applicable field meter serial numbers are documented in the calibration
logs.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ❑ ❑ ■ ❑
Is the tubing clean? ❑ ❑ ■ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: The subject permit requires effluent grab samples.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Yes No NA NE
Page# 4
Permit: NC0037371
Inspection Date: 10/12/2022
Owner - Facility: North Iredell High School
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be adequately treating wastewater at the
time of the inspection. Process control measurement are being performed and
documented.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment:
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? ■ ❑ ❑ ❑
Page# 5
Permit: NC0037371
Inspection Date: 10/12/2022
Owner - Facility: North Iredell High School
Inspection Type: Compliance Evaluation
Aeration Basins
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The 30-minute settleability test performed during the inspection was approximately 700
ml/L with a clear supernate.
One of the blower/motor units was not in service. A cracked belt was replaced during
the inspection and several air filters needed cleaning and/or replacement. The ORC
and permittee must ensure all equipment is properly maintained at all times.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? ■ ❑ ❑ ❑
Number of tubes in use? 3
Is the level of chlorine residual acceptable? • ❑ ❑ ❑
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? • ❑ ❑ ❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Page# 6
Permit: NC0037371
Inspection Date: 10/12/2022
Owner - Facility: North Iredell High School
Inspection Type: Compliance Evaluation
De -chlorination
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The flow meter is calibrated annually and was last calibrated in December
Delta Systems Environmental.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable solids or foam.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
2021 by
Yes No NA NE
• ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The facility is equipped with an aerated sludge holding tank. Lentz Septic Tank Service
has been contracted to remove sludge on an as -needed basis.
Page# 7