Loading...
HomeMy WebLinkAboutNC0033782_Inspection_20221027ROY COOPER Governor ELIZABETH S. RISER Secretary RICHARD E. ROGERS, JR. Director Phillip Williams Public Schools of Gates County PO Box 125 Gatesville, NC 27938-0125 NORTH CAROLINA Environmental Quoiity October 27, 2022 SUBJECT: Compliance Inspection Report Gatesville Elementary School WWTP NPDES WW Permit No. NC0033782 Gates County Dear Permittee: The North Carolina Division of Water Resources conducted an inspection of the Gatesville Elementary School WWTP on 10/19/2022. This inspection was conducted to verify that the facility is operating in compliance with the conditions and limitations specified in NPDES WW Permit No. NC0033782. The findings and comments noted during this inspection are provided in the enclosed copy of the inspection report entitled "Compliance Inspection Report". If you should have any questions, please do not hesitate to contact Robbie Bullock with the Water Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at robert.e.bullock@ncdenr.gov. ATTACHMENTS Cc: Laserfiche Sincerely, RQbo t Te.4-444 Robert Tankard, Assistant Regional Supervisor Water Quality Regional Operations Section Washington Regional Office Division of Water Resources, NCDEQ L D E North Carolina Department of EnNronmental Quality I Dlvlslon of Waler Resources Washington Regional Office 1 943 Washington Square Mall I Washington, North Carolina 27889 252.946.6481 United States Environmental Protection Agency EPA Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code NPDES yr/mo/day Inspection 1 IN I 2 LI 3 I NC0033782 111 121 22/10/19 117 Type 18 I O I I I 1 1 1 Inspector Fac Type 191 S I 20I 21 1 1 1 1 1 1 1 1 1 1 1 1 I I I I I I I I I I' I I I I I 1 1 1 1 I I I I r6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 671 I 70 I I 711 172 I N I 73 _ I 74 71 I I I I I I I I 180 Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) Gatesville Elementary School WWTP NC Hwy 37 us hwy 158 Gatesville NC 27938 Entry Time/Date 10:OOAM 22/10/19 Permit Effective Date 18/04/01 Exit Time/Date 10:45AM 22/10/19 Permit Expiration Date 23/03/31 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Harrell Randolph Lowe/ORC/252-357-1440/ Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Robert T EWell,PO Box 125 Gatesville NC 279380125//252-357-1440/2523571961 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date Robert E Bullock DWR/WARO WQ/252-948-3843/ 10/27/2022 i66i a Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date RottilT.. DWR/WARo/252-948-3921 10/27/2022 EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# 1 3I NPDES yr/mo/day N C 0033782 111 121 22/ 10/ 19 I17 Inspection Type 18 [j (Cont.) 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) The review period for this inspection was June 2017 through August 2022. Over the review period Four Notice of Deficiencies, One Notice of Violation and One Civil Penalty Assessment was issued to the facility. The current permit is set to expire on March 31, 2023. A renewal application has been submitted and the existing permit will remain effective until a new permit is issued. On April 7, 2022 the greenhouse cover was destroyed when a storm producing a tornado passed through. Gates County Schools has been in contact with Bob DeWeese (Department of Public Instruction) to see if the recirculation sand filters will operate efficiently with no cover. The estimate to replace the cover is $75,000. The school has been in Compliance with permitted limits since the cover has been destroyed. One potential issue with not adding the cover back is the permitted weekly flow limit of 5,000 gallons per day. Rain will add hydraulic flow to the system which could potentially violate the NPDES permitted weekly flow limit. Page# 2 Permit: NC0033782 Inspection Date: 10/19/2022 Owner - Facility: Gatesville Elementary School WWTP Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ � ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new IN❑ ❑ ❑ application? Is the facility as described in the permit? • ❑ ❑ ❑ # Are there any special conditions for the permit? • ❑ ❑ ❑ Is access to the plant site restricted to the general public? • ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑ Comment: The current permit is set to expire on March 31, 2023. A renewal application has been submitted and the existing permit will remain effective until a new permit is issued. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 3 Permit: NC0033782 Inspection Date: 10/19/2022 Owner - Facility: Gatesville Elementary School WWTP Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Is a copy of the current NPDES permit available on site? • ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ El MI ❑ Comment: Harrell Lowe is the ORC with Randy Harrell as the backup ORC. The January 2022 DMR was spot checked for accuracy with no discrepancies found Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ■ ❑ ❑ ❑ • ❑ Comment: Gates County Schools is field parameter certified (#5637) with all other samples sent to Environment 1 for analysis Septic Tank Yes No NA NE (If pumps are used) Is an audible and visual alarm operational? ❑ ❑ ❑ • Is septic tank pumped on a schedule? • ❑ ❑ ❑ Are pumps or syphons operating properly? • El El El Are high and low water alarms operating properly? El El El • Comment: Septic tanks are pumped yearly Sand Filters (Low rate) (If pumps are used) Is an audible and visible alarm Present and operational? Is the distribution box level and watertight? Is sand filter free of ponding? Is the sand filter effluent re -circulated at a valid ratio? # Is the sand filter surface free of algae or excessive vegetation? # Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1) Comment: There was some minor ponding on the day of inspection Disinfection - UV Are extra UV bulbs available on site? Yes No NA NE ❑ ❑ ❑ • • ❑ ❑ ❑ Yes No NA NE Page# 4 Permit: NC0033782 Inspection Date: 10/19/2022 Owner - Facility: Gatesville Elementary School WWTP Inspection Type: Compliance Evaluation Disinfection - UV Yes No NA NE Are UV bulbs clean? • ❑ ❑ ❑ Is UV intensity adequate? ■ ❑ ❑ ❑ Is transmittance at or above designed level? • ❑ ❑ ❑ Is there a backup system on site? ❑ • ❑ ❑ Is effluent clear and free of solids? • ❑ ❑ ❑ Comment: There is no backup disinfection. Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Comment: An inline water meter is used for recording effluent flow Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ • ❑ Effluent Sampling Yes No NA NE Is composite sampling flow proportional? ❑ ❑ • ❑ Is sample collected below all treatment units? • ❑ ❑ ❑ Is proper volume collected? ■ ❑ ❑ ❑ Is the tubing clean? ❑ ❑ • ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑ degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑ representative)? Comment: Effluent samples are Grab samples Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Comment: Yes No NA NE Page# 5