HomeMy WebLinkAboutNC0003417_Application_20220525('DUKE
ENERGY®
May 13, 2022
Sergei Chernikov, PhD
Industrial Permitting Branch
NC Division of Water Resources
1617 Mail Service Center
Raleigh, NC 27699-1617
Subject: NPDES permit modification request
H.F. Lee Energy Complex
NC0003417
Wayne County
Dear Dr. Chernikov,
Duke Energy Progress, LLC
H.F. Lee Energy Complex
1199 Black Jack Church Roaa
Goldsboro, NC 27530
RECEIVED
202022
NCDEQ/DWR/NPDES
Duke Energy Progress, LLC (Duke Energy) hereby requests modification of the subject NPDES
permit to include NPDES coverage of the Cooling Pond Seeps upon expiration or termination of
Special Order by Consent (SOC) - WQ S 18-006 and to update the modified compliance
boundary map as recently approved by the North Carolina Division of Water Resources on
2/23/2022.
1) Duke Energy is requesting addition of a special condition in the NPDES permit to
provide permit coverage for the minor release of pollutants from areas of seepage
around the site's 545 acre cooling pond.
Background
In 2014 Duke Energy conducted a comprehensive evaluation of all potential wastewater
bason areas of seepage at the H.F. Lee Energy Complex. The areas of the survey included
the site's ash basins and the wastewater cooling pond.
Areas of seepage associated with the ash basins and cooling pond are currently covered and
regulated by a Consent Order EMC SOC WQ S 18-006 between the North Carolina
Environmental Management Commission and Duke Energy (the SOC). Upon completion of
the SOC, regulatory oversight of seeps associated with the ash basin will be transferred to the
sites groundwater corrective action plan (CAP) for continued monitoring and regulatory
oversight.
The groundwater CAP does not address the areas of seepage associated with the cooling
pond. The cooling pond will continue to support the Combined Cycle Facility past the
closure of the SOC. The wastewater cooling pond was historically used during coal fire
operations but did not receive wastewater streams from any coal ash wastewater processes.
The cooling pond continues to be an active operational component for the natural gas fired
combined cycle plan and will be so for the foreseeable future with no current plan for
closure. The cooling pond currently has two permitted outfalls: Outfalls 002 and Outfall
002A.
There are 21 areas of minor seepages identified around the cooling pond's 4.63 mile
perimeter dike: (CPS01-CPS-21). These areas are depicted around the cooling pond on
Attachment A Map - Cooling Pond Seeps. A list of these seeps and generalized areas of
latitude and longitude are also in Attachment A. Chemical testing of the cooling pond
seepage areas has revealed some contain minor concentrations of pollutants. During the
2021 seep sampling event, 6 of the 21 cooling pond seep areas exhibited sufficient flow to
obtain a sample for analysis. These sample results are provided in Attachment B - October
2021 Cooling Pond Sample Results.
Collectively, the observed volume of seepage flow is very low compared to the volume of
other permitted wastewater discharges at the site. The sample result table in Attachment B
demonstrates the total flow of the sampled seeps is approximately 0.1 % of the average flow
from the ash pond at Outfall 001.
REQUESTS
1. Duke Energy requests inclusion of these cooling pond seepage areas in the NPDES
Permit through reference in a special condition to assure complete and appropriate
permit coverage. Duke Energy requests the existing instream monitoring requirements
upstream and downstream of the site along with required inspections of the seepage areas
in close proximity to the cooling pond dam in accordance with North Carolina Dam
Safety requirements be deemed sufficient to monitor any influence from these areas.
2. Duke Energy requests the updated compliance boundary map approved by the
North Carolina Division of Water Resources staff on 2/23/2022 be included in the
modified NPDES permit.
A copy of the updated compliance boundary map along with correspondence from
Division approving the updated compliance boundary is included for reference. An
electronic copy of the map can be provided upon request.
A check in the amount of $1,030 is included with this submittal to cover the required permit
modification fee. Should you have any questions about this request, please feel free to
contact Joyce Dishmon at (336)623-0238.
eff'} apk
Superintendent Maintenance
H.F. Lee Energy Complex
Attachments
Cc: Mike Graham
Sharat Gollamudi
Shannon Langley — via email
Joyce Dishmon/FileNet — via email
Attachment A
Location map of Cooling Pond Seeps
NPDES permit modification request
H.F. Lee Energy Complex
May 2022
A
cps-) T
%DUKE
°Nr-ENERGY
synTerra
GRAPHIC SCAL
325 0 3]s 6E0
BN FEED
ATE.. 01%31 . .
OILCSEO EN C. PONCE
ARPROWO BY II FERRI
wwwsvnterracoro.com
LEGEND
ONSTRUCTED SEEP
y rREAM SURFACE WATER LOCATION PER SOC
A NPDES OUTFALL LOCATION
- ACTIVE ASH BASIN WASTE BOUNDARY
L. SOC INSPECTION AREA
— LAY OF LAND AREA BOUNDARY
— - DUKE ENERGY PROGRESS PROPERTY LINE
STREAM (A)AEC NRTR)
SURFACE WATER FLOW DIRECTION
WETLAND (AMEC NRTR)
NOTES,
SOC SPEOAL ORDER By CONSENT
ARE BSI BOOM
B TNF WATERS OF THE UEDELINEATION SHOWN ON IBIS IMP NAS NOT BEEN APPROVED B '
ENGINEERSY US ARMY WETLANDS ASEAMS BOUNDARIES WERE OBTAINED FR'•
LEE EN :5CO PMEOATETIVOlAAr AID „l'NDTRAWDATES RECEI RDEr %AMN ECa W.t
aOALL BOUNDARIES ARE APPROXIMATE
s PROPERTY ENBEP BOUNDARY PROVIDED BY DUNE ENERGY PROGRESS
OTE IMAGERY OBTAINED FROM Feb COLLECTED BETWEEN NOVEMBER t AND
ST ]Bt9
I DRAWING NAS BEEN BET WITH A PROJECTION OF Nrnrw �AROUNA STATE PLANE OcwD�N
svSTEM FlP9lAOINAOBBI
FIGURE 2-1
EXISTING SEEP LOCATIONS AND INSPECTION AREAS
COOLING POND SEEP REPORT
H.F. LEE ENERGY COMPLEX
GOLDSBORO, NORTH CAROLINA
Seep ID
Number
CPS-01
CPS-02
CPS-03
CPS-04
CPS-05
CPS-06
CPS-07
Approximate
Location Coordinates
Latitude Longitude
35.37924
35.37901
35.37895
35.37902
35.37998
35.37179
35.37177
- 78.07377
-78.07298
-78.06270
-78.06707
- 78.06574
-78.06642
- 78.06661
Attachment A
518-006
Duke Energy Progress, LLC — H. F. Lee Energy Complex, p.5
Description
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Receiving
Waterbody
Neuse River
Neuse River
Neuse River
Neuse River
Neuse River
Neuse River
Neuse River
Receiving
Waterbody
Classification
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
*Location previously investigated as a seep. Monitoring has not indicated the presence of coal combustion residuals.
** Seep dispositioned via repair and/or non -flowing condition to potentially reach WOTUS, or other, as noted.
Monitoring shall be conducted at the approximate locations indicated on the attached site map.
All monitoring shall be conducted per the requirements found in Attachment B of this Order.
SOC Monitoring
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
lnstream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Interim Action Levels
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
Attachment A
S 18-006
Duke Energy Progress, LLC — H. F. Lee Energy Complex, p.6
Seep ID
Number
Approximate
Location Coordinates
Latitude Longitude
CPS-08 35.37711-78.06780
Description
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
CPS-09 35.36922 -78.07880
CPS-10 35.36840 -78.08125
CPS-11 35.36829 -78.08141
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
CPS-12 35.36816 -78.08156
CPS-13 35.37972 -78.07540
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
CPS-14 35.37963 -78.07527
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Receiving
Waterbody
Neuse River
Neuse River
Neuse River
Neuse River
Receiving
Waterbody SOC Monitoring
Classification
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
WS-IV; NSW
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Neuse River
WS-IV; NSW
Neuse River
Neuse River
WS-IV; NSW
WS-IV; NSW
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Instream
monitoring of the
Neuse River
Interim Action Levels
N/A — 2B Standards
Apply
N/A— 2B Standards
Apply
N/A— 2B Standards
Apply
N/A — 28 Standards
Apply
N/A — 26 Standards
Apply
N/A — 2B Standards
Apply
N/A — 2B Standards
Apply
*Location previously investigated as a seep. Monitoring has not indicated the presence of coal combustion residuals.
** Seep dispositioned via repair and/or non -flowing condition to potentially reach WOTUS, or other, as noted.
Monitoring shall be conducted at the approximate locations indicated on the attached site map.
All monitoring shall be conducted per the requirements found in Attachment B of this Order.
Seep ID
Number
Attachment A
518-006
Duke Energy Progress, LLC — H. F. Lee Energy Complex, p.7
Approximate
Location Coordinates
Latitude
Longitude
Description
CPS-15 35.37962 -78.07460
CPS-16 35.37942 -78.07423
CPS-17
CPS-18
CPS-19
Receiving
Waterbody
Receiving
Waterbody
Classification
SOC Monitoring
Interim Action Levels
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Neuse River
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
35.37465 -78.06165
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
35.37195 -78.06605
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
35.37192 -78.06625
CPS-20 35.37202
CPS-21 35.36983
WS-IV; NSW
Instream
monitoring of the
Neuse River
N/A — 2B Standards
Apply
Neuse River
WS-IV; NSW
Instream
monitoring of the
Neuse River
N/A — 2B Standards
Apply
Neuse River
WS-IV; NSW
Instream
monitoring of the
Neuse River
Neuse River
WS-IV; NSW
N/A — 2B Standards
Apply
Instream
monitoring of the N/A — 2B Standards
Neuse River Apply
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
-78.06630
Neuse River
WS-IV; NSW
Instream
monitoring of the
Neuse River
N/A — 2B Standards
Apply
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
-78.07580
Seep from the berm surrounding the cooling
pond. Not a seep emanating from the active ash
basin.
Neuse River
WS-IV; NSW
Instream
monitoring of the
Neuse River
Neuse River
WS-IV; NSW
N/A — 2B Standards
Apply
Instream
monitoring of the
Neuse River
*Location previously investigated as a seep. Monitoring has not indicated the presence of coal combustion residuals.
** Seep dispositioned via repair and/or non -flowing condition to potentially reach WOTUS, or other, as noted.
Monitoring shall be conducted at the approximate locations indicated on the attached site map.
All monitoring shall be conducted per the requirements found in Attachment B of this Order.
N/A — 2B Standards
Apply
Attachment B
October 2021 Cooling Pond Sample Results
NPDES permit modification request
H.F. Lee Energy Complex
May 2022
Reporting Units
Attachment B - October 2021 Cooling Pond Samples Data
FIELD PARAMETERS
S.U.
Deg C
umhos/cm
mg/L
mV
mV
NTUs _
ANALYTICAL RESULTS (TOTAL CONCENTRATION)
mg/L mg/L
mg/L mg/L ug/L
FIELD PARAMETERS
ANALYTICAL RESULTS (TOTAL CONCENTRATION)
Location
ID
Sample
Collection
Date
pH
Temperature
Specific
Conductance
Dissolved
Oxygen
Oxidation
Reduction
potential
Eh
Turbidity
Flow
Arsenic
Barium
Boron
Bromide
Cadmium
Calcium
Chloride
Chromium
Copper
Fluoride
Hardness
Lead
filtered
Z
Z
Z
Z
Z
Z
Z
Z
TOT
TOT
TOT
Z
TOT
TOT
Z
i,
TOT
TOT
Z
Z
TOT
CPS-01
10/18/2021
7.1
22
292
3.40
-114
91
15.6
3.5
13.3
42
64
350
<0.1
10.4
28
<1
<2
0.37
42.5
<0.2
CPS-02
10/18/2021
7.0
23
267
1.67
-102
103
7.9
1.5
11.6
41
63
340
<0.1
9.37
27
-
<1
<2
0.36
39.6
<0.2
CPS-09
10/19/2021
6.7
17
328
4.25
-31
174
42.4
5
4.8
52
60
370
<0.1
8.26
28
<1 -
<2
0.49
49.1
<0.2
CPS-18
10/19/2021
7.0
17
237
5.85
125
330
79.1
2.8
1.7
35
57
340
<0.1
8.62
26
<1
<2
0.31
37.4
<0.2
CPS-20
10/19/2021
7.0
19
232
4.48
-20
185
39.2
7
2.23
43
51
340
<0.1
8.36
27
1.09
<2
0.35
37.8
1.02
CPS-21
10/19/2021
7.0
13
287
8.20
-17
188
28.8
3.5
<1
23
54
370
<0.1
8.75
31
<1
<2
0.59
46.7
<0.2
Reporting Units
FIELD PARAMETERS
ANALYTICAL RESULTS (TOTAL CONCENTRATION)
S.U. Deg C umhos/cm I mg/L mV mV NTUs I GPM
mg/L ug/L - ug/L mg-N/L mg/L ug/L mg/L ug/L mg/L mg/L ug/L
FIELD PARAMETERS
ANALYTICAL RESULTS (TOTAL CONCENTRATION)
Location
ID
Sample
Collection
Date
pH
Temperature
Specific
Conductance
Dissolved
Oxygen
Oxidation
Reduction
Potential
Eh
Turbidity
Flow
Magnesium
Mercury
Nickel
Nitrate
+ Nitrite
Oil and
grease
Selenium
Sulfate
Thallium
Total
Dissolved
Solids
Total
Suspended
Solids
Zinc
filtered
Z
Z
Z
Z
Z
Z
Z
Z
TOT
TOT
TOT
Z
Z
TOT
Z
TOT
Z
Z
TOT
CPS-01
10/18/2021
7.1
22
292
3.40
-114
91
15.6
3.5
4.04
0.00117
<1
0.06
<5
<1
<0.1
<0.2
143
10
<5
CPS-02
10/18/2021
7.0
23
267
1.67
-102
103
7.9
1.5
3.92
0.00134
<1
0.06
<5
<1
<0.1
<0.2
145
33
<5
CPS-09
10/19/2021
6.7
17
328
4.25
-31
174
42.4
5
6.9
0.00302
<1
0.08
<5
<1
<0.1
<0.2
150
46
<5
CPS-18
10/19/2021
7.0
17
237
5.85
125
330
79.1
2.8
3.86
<0.0005
<1
0.14
<5
<1
10
<0.2
141
19 R1
<5
CPS-20
10/19/2021
7.0
19
232
4.48
-20
185
39.2
7
4.12
0.01
<1
0.09
<5
<1
4.4
<0.2
135
80
<5
CPS-21
10/19/2021
7.0
13
287
8.20
-17
188 _
28.8
3.5
_ 6.04
<0.0005
<1
0.09
<5
<1
<0.1
<0.2
151
7.6
<5
Reporting Units
FIELD PARAMETERS
ANALYTICAL RESULTS (DISSOLVED CONCENTRATION)
S.U. Deg C umhos/cm mg/L mV mV NTUs GPM
ug/L ug/L ug/L ug/L ug/L ug/L ] ug/L
FIELD PARAMETERS
ANALYTICAL RESULTS (DISSOLVED CONCENTRATION)
Location
ID
Sample
Collection
Date
pH
Temperature
Specific
Conductance
Dissolved
Oxygen
Oxidation
Reduction
potential
Eh
Turbidity
Flow
Arsenic
Cadmium
Chromium
Copper
Lead
Nickel
Zinc
filtered
Z
Z
Z
Z
Z
Z
Z
Z
DIS
DIS
DIS
DIS
DIS
DIS
DIS
CPS-01
10/18/2021
7.1
22
292
3.40
-114
91
15.6
3.5
11.3
<0.1
<1
<2
<0.2
<1
<5
CPS-02
10/18/2021
7.0
23
267
1.67
-102
103
7.9
1.5
11.4
<0.1
<1
<2
<0.2
<1
<5
CPS-09
10/19/2021
6.7
17
328
4.25
-31
174
42.4
5
2.74
<0.1
<1
<2
<0.2
<1
<5
CPS-18
10/19/2021
7.0
17
237
5.85
125
330
79.1
2.8
<1
<0.1
<1
<2
<0.2
<1
<5
CPS-20
10/19/2021
7.0
19
232
4.48
-20
185
39.2
7
1.82
<0.1
<1
<2
<0.2
<1
<5
CPS-21
10/19/2021
7.0
13
287
8.20
-17
188
28.8
3.5
<1
<0.1
<1
<2
<0.2
<1
<5
Dishmon, Joyce Martin
From: Smith, Eric G <eric.g.smith@ncdenr.gov>
Sent: Wednesday, February 23, 2022 10:29 AM
To: Toepfer, John R
Cc: Sullivan, Ed M; Davies, Scott E.; Costner, Brandy F; Campbell, Ted; Wang, Shuying; Harbison, Joanna
A; Hart, William; Rice, Eric; Chernikov, Sergei; Giri, Poonam a; Benzoni, Francisco J; Hanchey, Matthew
F.; Poupart, Jeff
Subject: [EXTERNAL] Duke Energy: Compliance Boundary Approvals
Attachments: 2019_07_22 Rogers Energy Complex Revised Boundary.pdf; 2019_10_09 Allen Steam Station Updated
Boundary.pdf; 2019-09-17 Duke Energy Mayo Land Acquisition.pdf; 2020_10_22 Buck Steam Station
Updated Boundary Submittal.pdf; 2021-02 Asheville Property Acquistion.pdf; Duke subittal of HF Lee
Compliance Boundary Change - October 2020.pdf;
DukeEnergy_BelewsCreek_UpdatedAshBasinComplianceBoundary_20200311.pdf; 07_26_21 Marshall
Steam Station Updated Boundary Submittal.pdf
*** CAUTION! EXTERNAL SENDER *** STOP. ASSESS. VERIFY!! Were you expecting this email? Are grammar
and spelling correct? Does the content make sense? Can you verify the sender? If suspicious report it, then do
not click links, open attachments or enter your ID or password.
John:
The following proposed compliance boundary updates were submitted to DEQ by Duke Energy since 2019 (also
attached):
• Allen Steam Station — submitted 10/9/19
• Asheville Steam Electric Plant — submitted 2/10/21
o DEQ understands that Duke has documentation of ownership for the land under 1-26 that is included in
the updated compliance boundary map. DEQ will approve this proposed change to the compliance
boundary upon receipt of that documentation.
• Belews Creek Steam Station — submitted 3/11/20
• Buck Combined Cycle Station — submitted 10/22/20
• James E. Rogers Energy Complex (Cliffside) — submitted 7/22/19
• H. F. Lee Energy Complex — submitted 10/16/20
• Marshall Steam Station — submitted 7/26/21
• Mayo Steam Electric Plant — submitted 9/17/19
DEQ hereby approves the proposed changes to the compliance boundary at each of these sites. These maps will be
included in the facility NPDES permit the next time the permit is renewed or modified.
Additional Compliance Boundary Issues
The following issues are currently being reviewed by DEQ and will be handled in a separate correspondence:
• For the Cape Fear Steam Electric Plant, a different configuration of the compliance boundary was included in the
updated Comprehensive Site Assessment Report (submitted December 1, 2020) than is depicted in the current
NPDES permits.
• For the W. H. Weatherspoon Power Plant, a question exists regarding whether the Cooling Pond has a
compliance boundary.
-Eric G. Smith
1
Eric G. Smith
Environmental Program Consultant
Ground Water Resources Section
Division of Water Resources
Department of Environmental Quality
919 707 3669 office
eric.q.smith(a�ncdenr.gov
512 N. Salisbury St
1636 Mail Service Center
Raleigh, NC 27699-1636
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
2
Eric G. Smith
Environmental Program Consultant
Ground Water Resources Section
Division of Water Resources
Department of Environmental Quality
919 707 3669 office
eric.q.smith(c�ncdenr.gov
512 N. Salisbury St
1636 Mail Service Center
Raleigh, NC 27699-1636
Email correspondence to and from this address is subject to the
North Carolina Public Records Law and may be disclosed to third parties.
2
(� DUKE
ENERGY
October 16, 2020
Mr. S. Daniel Smith
Director of Water Resources
North Carolina Department of Environmental Quality
1636 Mail Service Center
Raleigh, North Carolina 27699-1636
410 S. Wilmington Street.
Raleigh, NC 27601
Mailing Address
Mail Code NC 15
Raleigh, NC 27601
919-546-7863
Subject: Duke Energy Progress, LLC. Updated Ash Basin Compliance Boundary for the H.F. Lee
Energy Complex, Wayne County, North Carolina, NPDES Permit No. NC0003417
Dear Mr. Smith:
Duke Energy completed a property purchase nearby to the H.F. Lee Energy Complex on September 15,
2020. Per 15A NCAC 02L .0107 (c), this letter serves as notification of the change to the ash basin
compliance boundary due to this land purchase. Attached you will find an updated compliance
boundary to reflect the new property boundary. This information is also being provided to the
Washington Regional Office.
If you have any questions or need any clarification regarding the information provided, feel free to contact
me at iohn.toepfertaiduke-energy.com or at 919-546-7863 at your convenience.
Respectfully submitted,
ohn Toepfer, P.E.
Lead Engineer, Duke Energy EHS CCP
Waste & Groundwater Programs
Attachments: Figure 1-2B, Site Layout Map
cc: Rick Bolich, Eric Smith and Steve Lanter - NCDEQ Central Office
Will Hart and David May - NCDEQ Washington Regional Office
Ed Sullivan, Tyler Hardin, Matt Hanchey, Joyce Dishmon — Duke Energy
• /
•
••
•• /
J
IMW-4S
IMW-4BC
•
ILIMW-7Sj
•
IMW-6S}
f
JIABMW-1
IIABP.''r; 1
•
IMW-3S ^.
IMW-3BC
•
•
•
•0
•
•
'• ..
t
IABMW-2
IABMW-2S
•
•
•
•
♦'
•
•••
(, DUKE
ENERGY
'ROGRESS
•
I
�•• ,
�•• ••ter
•• •• •
..
• •• -�.
1. .►i 0
GRAPHIC SCALE
250 0 250 500
IN FEET)
synTerra
DRAWN BY: C. CURRIER
REVISED BY: C. CURRIER
CHECKED BY:
APPROVED BY:
PROJECT MANAGER: C. PONCE
DATE: 10/07/2020
DATE: 10/07/2020
DATE: 10/07/2020
DATE: 10/07/2020
www.synterracorp.com
•
1•
LEGEND
0 MONITORING WELL IN ASH POREWATER
Q) MONITORING WELL IN SURFICIAL FLOW ZONE
O MONITORING WELL IN CAPE FEAR FLOW ZONE
• BACKGROUND MONITORING WELL
1J PIEZOMETER IN SURFICIAL FLOW ZONE
♦ NPDES OUTFALL LOCATION
PURCHASED PARCELS
WASTE BOUNDARY
ASH BASIN COMPLIANCE BOUNDARY
FORMER COAL FIRED POWER PLANT
DUKE ENERGY PROGRESS PROPERTY LINE
- STREAM (AMEC)
WETLAND (AMEC)
SURFACE WATER FLOW DIRECTION
NOTES:
1 NPDES - NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
2 THE WATERS OF THE US SHOWN ON THIS MAP HAVE NOT BEEN APPROVED BY THE US
ARMY CORPS OF ENGINEERS. WETLANDS AND STREAMS BOUNDARIES WERE OBTAINED
FROM AMEC FOSTER AND WHEELER(AMEC) NATURAL RESOURCES TECHNICAL REPORT FOR
H F. LEE ENERGY COMPLEX DATED JANUARY 20. 2014 AND UPDATES RECEIVED FROM AMEC
IN MAY 2017
3 ALL BOUNDARIES ARE APPROXIMATE.
4 PROPERTY BOUNDARY PROVIDED BY DUKE ENERGY PROGRESS.
5 AERIAL PHOTOGRAPHY OBTAINED FROM TERRASEVER ON JUNE 18. 2019. AERIAL WAS
COLLECTED ON JANUARY 9. 2019.
6 DRAWING HAS BEEN SET WITH A PROJECTION OF NORTH CAROLINA STATE PLANE
COORDINATE SYSTEM FIPS 3200 (NAD83)
FIGURE 1-2B
SITE LAYOUT MAP
GROUNDWATER MONITORING WELLS
INACTIVE ASH BASINS
2020 COMPREHENSIVE SITE ASSESSMENT UPDATE
H.F. LEE ENERGY COMPLEX