HomeMy WebLinkAboutNC0047597_Report_19871210North Carolina Division Of Environmental Management
Water Quality Section / Technical Services Branch
Intensive Survey Unit
10 December 1987
MEMORANDUM
To: Trevor Clemen
Thru: Jay Sauber rl
From: Howard Bryant
11C
Subject: Durham Farrington WWTP SOD Longterm
Date Collected: 27 July 1987 (1235)
Collector: Howard Bryant
Mu) Hoe k
Setup: 27 July 1987
(1505)
Day BOD NH3 TKN NOX TOT N Reps
0 1.8 2.4 10 12.4
5 3.8 8
8 7.2 8
10 8.8 0.03 1.0 11 13.3 7
15 10.5 0.03 1.0 11 12.0 7
20 11.9 0.04 1.0 12 13.0 6
25 12.8 5
30 13.6 0.04 0.9 12 12.9 5
40 14.7 4
60 17.0 4
70 17 6 0.01 0.9 13 13.9 4
82 18.4 3
Comments: Initial high oxygen--14.0 mg/1 average.
Cary Lab BOD5: 3.4 mg/1. pH: 7.0
Total phosphorus: 5.8 mg/1.
Total residue: 350 mg/1.
Suspended residue: 12 mg/1.
Test evaluation: good.
North Carolina Division Of Environmental Management
Water Quality Section / Technical Services Branch
Intensive Survey Unit
10 December 1987
MEMORANDUM
To: Trevor Clement
Thru: Jay Sauber J.
From: Howard Bryant !¢ a4-7-4
Subject: Durham Farrington WWTP BOD Longterm
Date Collected: 27 July 1987 (1235)
Collector: Howard Bryant
Setup: 27 July 1987
(1440)
Day BOD NH3 TKN NOX TOT N Reams
0 1.80 2.4 10 12.4
5 4.8 0.68 0.2 11 11.2 7
10 10.7 0.03 2.1 12 14.1 7
15 12.5 0.03 2.1 12 14.1 6
20 13.7 0.04 0.9 12 12.9 5
. 25 14.8 4
30 15.6 0.04 0.9 12 12.9 4
40 17.2 3
47 18.2 3
60 19.5 3.
70 20.1 0.01 0.9 12 -12.9 3
82 20.8 2
Comments: Samples in BOD bottles were aerated with oxygen to levels
ranging from 8.0 to 9.2 mg/1 (average:8.7) in order to compare 5-day BOD
with samples aerated to a higher oxygen concentration--13.0 to 15.2 mg/1
(average 14.0). The set of samples with the initial higher DO had an average
5-day BOD of 3.8 mg/1. The set of samples with the lower initial DO had an
average 5-day BOD of 4.8 mg/1.