HomeMy WebLinkAboutWQ0007349_Compliance Evaluation Inspection_20221004ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Nicole Johnston, Executive Director
Yadkin Valley Sewer Authority
P.O. Box 828
Elkin, NC 28621
NORTH CAROLINA
Environmental Quality
October 4, 2022
SUBJECT: Compliance Evaluation Inspection
Yadkin Valley Sewer Authority Residuals Land Application Program
Permit No. WQ0007349
Surry County
Dear Ms. Johnston:
On September 22, 2022, Division of Water Resources staff Caitlin Caudle conducted a
compliance evaluation inspection. A review of the source generating facility, records, and
application fields was completed. Zach Key, US Biosolids, and Todd Coe, YVSA, were
present during the review of the source generating facility. Mr. Key and David Key, US
Biosolids, were present during the review of the application fields. Application was not
occurring during the time of inspection. This review reflected compliance with the subject
permit.
Please refer to the enclosed inspection report for additional comments and observations.
If you have any questions, please contact me or Caitlin Caudle at the letterhead address
or phone number, or by email at lon.snider(a_ncdenr.gov or caitlin.caudle(a)_ncdenr.gov.
Sincerely,
FDocu Siiggned by:
L oti l . JMAts'
145B49E225C94EA..
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ-WSRO
Enc: Inspection Report
Cc: Zack Key, US Biosolids (electronic copy)
Surry County Environmental Health (electronic copy)
Laserfiche File WQ0007349
WSRO Electronic Files
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
NoanicaaouNn
oep.m.m or em�nmen� Qualm
336.776.9800
Compliance Inspection Report
Permit: WQ0007349 Effective: 06/13/19 Expiration: 02/28/25 Owner: Yadkin Valley Sewer Authority
SOC: Effective: Expiration: Facility: Yadkin Valley Sewer Authority RLAP
County: Surry 211 Marion Rd
Region: Winston-Salem
Elkin NC 28621
Contact Person: Zach D Key Title: Phone: 336-957-7871
Directions to Facility:
System Classifications: LA,
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
NC0020567 Yadkin Valley Sewer Authority - Yadkin Valley Sewer Authority WWTP
Inspection Date: 09/22/2022 bnCV&"Fifn�Ye. 09:03AM Exit Time: 10:56AM
Primary Inspector: Caitlin CaudleL(±v, l�D& Phone: 336-776-9699
968199D49D_
Secondary Inspector(s): 10/4/2022
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Land Application of Residual Solids (503)
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Sampling Land Application Site Pathogen and Vector Attraction
Storage
(See attachment summary)
Page 1 of 5
Permit: WQ0007349 Owner -Facility: Yadkin Valley Sewer Authority
Inspection Date: 09/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
On September 22, 2022, Division of Water Resources staff Caitlin Caudle conducted a compliance evaluation inspection. A
review of the source generating facility, records, and application fields was completed. Zach Key, US Biosolids, and Todd
Coe, YVSA, were present during the review of the source generating facility. Mr. Key and David Key, US Biosolids, were
present during the review of the application fields. Application was not occurring during the time of inspection. This review
reflected compliance with the subject permit.
An email was sent on September 22, 2022, requesting the following information by October 3rd:
• YVSA TCLP
• YVSA 30 day bench test
• Field inspection forms for the application event
This information was received on October 3, 2022. Mr. Key stated that he will be conducting another 30 day bench scale
test as results were not satisfactory.
Other observations:
• Residuals were being hauled from the Yadkin Valle Sewer Authority WWTP.
• Influent ❑ Bar Screen ❑ Grit Chamber ❑ Oxidation Ditch (has an anoxic zone) ❑ Clarifiers (2) ❑ CCC OR Sludge
Thickening Basin ❑ Sludge Holding Tanks
• Two 200,000 gallon storage tanks store residuals. The tanks are open to the atmosphere and have aeration. The tanks
have 3-4 months of storage.
• A composite grab is used for all sample parameters.
• Nutrient and metals were sampled on 3/15/2022.
• Fecal samples were collected on 3/3/2022.
• PAN was calculated to be 28.186 Ibs PAN/dry ton.
• The trucks are top loaded on a paved parking lot.
• 28 loads have been hauled so far.
Field Observations:
WK-CM-1 B
Last applied on 9/21/2022
Access restriction signs were present
Fescue pasture, 141 Ibs/ac PAN
Cattle were restricted
The field was flagged with all buffers
Application was even with no ponding or runoff
Residuals were visible on the surface, surface application via broadcast is used
Page 2 of 5
Permit: WQ0007349 Owner -Facility: Yadkin Valley Sewer Authority
Inspection Date: 09/22/2022 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Distribution and Marketing
❑
Land Application
Record Keeping
Yes No NA NE
Is GW monitoring being conducted, if required?
❑
❑ 0 ❑
Are GW samples from all MWs sampled for all required parameters?
❑
❑ 0 ❑
Are there any GW quality violations?
❑
❑ 0 ❑
Is GW-59A certification form completed for facility?
❑
❑ 0 ❑
Is a copy of current permit on -site?
❑
❑ ❑
Are current metals and nutrient analysis available?
0
❑ ❑ ❑
Are nutrient and metal loading calculating most limiting parameters?
0
❑ ❑ ❑
a. TCLP analysis?
0
❑ ❑ ❑
b. SSFA (Standard Soil Fertility Analysis)?
0
❑ ❑ ❑
Are PAN balances being maintained?
0
❑ ❑ ❑
Are PAN balances within permit limits?
0
❑ ❑ ❑
Has land application equipment been calibrated?
❑
❑ ❑
Are there pH records for alkaline stabilization?
❑
❑ 0 ❑
Are there pH records for the land application site?
0
❑ ❑ ❑
Are nutrient/crop removal practices in place?
0
❑ ❑ ❑
Do lab sheets support data reported on Residual Analysis Summary?
0
❑ ❑ ❑
Are hauling records available?
0
❑ ❑ ❑
Are hauling records maintained and up-to-date?
0
❑ ❑ ❑
# Has permittee been free of public complaints in last 12 months?
0
❑ ❑ ❑
Has application occurred during Seasonal Restriction window?
0
❑ ❑ ❑
Comment:
Pathogen and Vector Attraction
Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
0
❑ ❑ ❑
Class A, all test must be <1000 MPN/dry gram
❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
❑ ❑ ❑
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
❑
❑ ❑ ❑
c. pH records for alkaline stabilization (Class B)
❑
❑ ❑ ❑
Temperature corrected
❑
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
❑
❑ ❑ ❑
Page 3 of 5
Permit: WQ0007349 Owner -Facility: Yadkin Valley Sewer Authority
Inspection Date: 09/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine
e. Time/Temp on: ❑ ❑ ❑ ❑
Digester (MCRT) ❑
Compost ❑
Class A lime stabilization ❑
f. Volatile Solids Calculations ❑ ❑ ❑ ❑
g. Bench -top Aerobic/Anaerobic digestion results 0 ❑ ❑ ❑
Comment:
Treatment
Yes No NA NE
Check all that apply
Aerobic Digestion
❑
Anaerobic Digestion
Alkaline Pasteurization (Class A)
❑
Alkaline Stabilization (Class B)
❑
Compost
❑
Drying Beds
❑
Other
❑
Comment:
Sampling Yes No NA NE
Describe sampling:
Is sampling adequate? 0 ❑ ❑ ❑
Is sampling representative? 0 ❑ ❑ ❑
Comment:
Land Application Site
Yes No NA NE
Is a copy of the permit on -site during application events?
❑
❑ ❑
Is the application site in overall good condition?
❑ ❑ ❑
Is the site free of runoff/ponding?
❑ ❑ ❑
If present, is the application equipment in good operating condition?
❑
❑ ❑
Are buffers being maintained?
❑ ❑ ❑
Are limiting slopes buffered?
10% for surface application
❑ ❑ ❑
18% for subsurface application
❑
❑ ❑
Are there access restrictions and/or signs?
❑ ❑ ❑
Is the application site free of odors or vectors?
❑ ❑ ❑
Have performance requirements for application method been met?
For injection?
❑
❑ 0 ❑
Page 4 of 5
Permit: WQ0007349 Owner -Facility: Yadkin Valley Sewer Authority
Inspection Date: 09/22/2022 Inspection Type: Compliance Evaluation Reason for Visit: Routine
For incorporation?
Does permit require monitoring wells?
Have required MWs been installed?
Are MWs properly located w/ respect to RB and CB?
Are MWs properly constructed (including screened interval)?
Is the surrounding area served by public water?
If Annual Report indicates overapplication of PAN, are wells nearby that may be impacted?
Are soil types consistent w/ Soil Scientist report/evaluation?
Is the water table greater than 173' bls.
Is application occurring at the time of the inspection?
Comment: There is no public water in the area. Application was not taking place.
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑❑■❑
❑■❑❑
❑❑■❑
■❑❑❑
■❑❑❑
❑■❑❑
Page 5 of 5