HomeMy WebLinkAboutNC0062961_Permit Issuance_20071107NPDES DOCYHENT SCANNING COVER SHEET
NC0062961
Tynecastle WWTP
NPDES Permit:
Document Type:
Permit Issuance
Wasteload Allocation
Authorization to Construct (AtC)
Permit Modification
Complete File - Historical
Engineering Alternatives (EAA)
Correspondence
Owner Name Change
Compliance
Instream Assessment (67b)
Speculative Limits
Environmental Assessment (EA)
Document Date:
November 7, 2007
Thies document Is printed on reuse paper - ignore any
cozntent on the reYerse aide
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Coleen H. Sullins, Director
Division of Water Quality
November 7, 2007
Mr. Robert C. Schwebke
RCS Properties, Inc.
4501 Tynecastle Highway #7
Banner Elk, NC 28604
Subject: Issuance of NPDES Permit NC0062961
Shoppes of Tynecastle WWTP
Avery County
Dear Mr. Schwebke:
Division personnel have reviewed and approved your application for renewal of the subject permit.
Accordingly, we are forwarding the attached NPDES discharge permit. This permit is issued pursuant
to the requirements of North Carolina General Statute 143-215.1 and the Memorandum of Agreement
between North Carolina and the U.S. Environmental Protection Agency dated May 9, 1994 (or as
subsequently amended).
This final permit includes no significant changes from the draft permit sent to you on September 12,
2007; however, you are reminded of the following changes in its terms from those found in your existing
permit:
• The facility description has been updated to reflect the recent improvements made to the WWTP
pursuant to Authorization to Construct 06961A01. The description establishes the WWTP's current
design capacity to be 0.03 MGD.
• The permitted flow limit has been changed to reflect the new 0.03 MGD design capacity of the
facility.
• Daily maximum limits for ammonia have been added to the permit. Since December 2002, the
Division has been adding daily maximum limits for ammonia to permits with monthly average limits
in order to conform to federal NPDES regulations.
• Monitoring and limits for total residual chlorine have been removed from the permit as a result of
ultraviolet (UV) disinfection being installed at the WWTP. However, a condition has been added to
the permit describing actions you must take should the UV system not function properly. If the UV
system fails and chlorine compounds are used as an alternate means of disinfection, daily monitoring
and a 28 µg/L daily maximum limit will apply to the discharge. Please note that minor changes
have been made to the wording of this condition, but its content remains the same as stated in the
draft.
!�1 Carolina
,7Vatura!!y
North Carolina Division of Water Quality 1617 Mail Service Center Raleigh, NC 27699-1617 Phone (919) 733-7015 Customer Service
Internet: www.ncwaterquality.org Location: 512 N. Salisbury St. Raleigh, NC 27604 Fax (919) 733-2496 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper
Mr. Robert C. Schwebke
NPDES Permit NC0062961 Renewal
p. 2
If any parts, measurement frequencies or sampling requirements contained in this permit are
unacceptable to you, you have the right to an adjudicatory hearing upon written request within thirty
(30) days following receipt of this letter. This request must be in the form of a written petition,
conforming to Chapter 150B of the North Carolina General Statutes, and filed with the Office of
Administrative Hearings (6714 Mail Service Center, Raleigh, North Carolina 27699-6714). Unless
such demand is made, this decision shall be final and binding.
Please note that this permit is not transferable except after notice to the Division. The Division may
require modification or revocation and reissuance of the permit. This permit does not affect the legal
requirements to obtain other permits which may be required by the Division of Water Quality or permits
required by the Division of Land Resources, the Coastal Area Management Act or any other Federal or
Local governmental permit that may be required.
If you have any questions concerning this permit, please contact Bob Sledge at telephone number (919)
733-5083, extension 547.
Sincerely,
0/
Coleen H. Sullins
cc: Central Files
Asheville Regional Office/Surface Water Protection Section
NPDES Unit
Permit NC0062961
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provisions of North Carolina General Statute 143-215.1, other lawful standards
and regulations promulgated and adopted by the North Carolina Environmental Management
Commission, and the Federal Water Pollution Control Act, as amended,
RCS Properties, Inc.
is hereby authorized to discharge wastewater from a facility located at the
Shoppes of Tynecastle WWTP
NC Highway 105
Banner Elk
Avery County
to receiving waters designated as the Watauga River in the Watauga River Basin
in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts
I, II, III and IV hereof.
This permit shall become effective December 1, 2007.
This permit and authorization to discharge shall expire at midnight on September 30, 2012.
Signed this day November 7, 2007.
Coleen H. Sullins, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit NC0062961
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES Permits issued to this facility, whether for operation or discharge are hereby
revoked. As of this permit issuance, any previously issued permit bearing this number is no longer
effective. Therefore, the exclusive authority to operate and discharge from this facility arises under the
permit conditions, requirements, terms, and provisions included herein.
RCS Properties, Inc. is hereby authorized to:
1. Continue to operate an existing 0.030 MGD package wastewater treatment system with the
following components:
• Surge Tank
• Anoxic Tank
• Dual Aeration Basins
• Dual Clarifiers
• Aerated Sludge Holding Tank
• Ultraviolet Disinfection
The facility is located in Banner Elk at the Shoppes of Tynecastle off NC Highway 105 in Avery
County.
2. Discharge from said treatment works at the location specified on the attached map into the Watauga
River, classified B-Trout-HQW waters in the Watauga River Basin.
Latitude: 36°07' 16"
Longitude: 81°50'05"
Quad # C11SE
Receiving Stream: Watauga River
Stream Class: B-Tr-HQW
Subbasin: 04-02-01
NC0062961 - RCS Properties - Shoppes of Tynecastle
Avery County
O(.eDIDIC3
Permit NC0062961
A. (1.) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS - FINAL
During the period beginning on the effective date of this permit and lasting until expiration, the
Permittee is authorized to discharge from outfall 001. Such discharges shall be limited and monitored
by the Permittee as specified below:
EFFLUENT
CHARACTERISTICS
LIMITS
MONITORING REQUIREMENTS
Monthly
Average
Daily
Maximum
Measurement
Frequency
Sample Type
P yP
Sample Location
Flow
0.030 MGD
Continuous
Recording
Influent or Effluent
BOD, 5-day (20°C)
30.0 mg/L
45.0 mg/L
Weekly
Composite
Effluent
Total Suspended Residue
30.0 mg/L
45.0 mg/L
Weekly
Composite
Effluent
NH3as N
(April 1— October 31)
2.3 mg/L
11.5 mg/L
Weekly
Composite
Effluent
NH3as N
(November 1 — March 31)
4.4 mg/L
22.0 mg/L
Weekly
Composite
Effluent
Dissolved Oxygen2
Weekly
Grab
Effluent, Upstream
& Downstream
Fecal Coliform (geometric mean)
200/100 ml
400/100 ml
Weekly
Grab
Effluent
Temperature (QC)
Daily
Grab
Effluent
Temperature (2C)
Weekly
Grab
Upstream &
Downstream
pH3
Weekly
Grab
Effluent
Footnotes:
1. Upstream = 50 feet above discharge; Downstream = 200 feet below discharge.
2. The daily average dissolved oxygen effluent concentration shall not be less 5.0 mg/L.
3. The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
See Condition A. (2.) for instructions should the facility's permitted UV system fail and an alternate
means of disinfection is required. Total Residual Chlorine monitoring requirements and limits are
applicable if chlorine compounds are used for disinfection.
Permit NC0062961
A. (2.) TEMPORARY MEANS OF DISINFECTION
In the event that the wastewater treatment plant's ultraviolet (UV) disinfection system should fail,
underperform, or otherwise be removed from effective service, the permittee or his agent should
immediately inform the Surface Water Protection Section staff of the Winston-Salem Regional Office
of this development and discuss temporary, alternate means for disinfection of the effluent.
If chlorine compounds are used as temporary means of disinfection, the total residual chlorine (TRC)
concentration of the effluent must be monitored on a daily basis while this method of disinfection is in
use and values must be reported on the discharge monitoring report. TRC in the effluent may not
exceed 28 µg/L; therefore, dechlorination methods may also be necessary to ensure protection of water
quality in the receiving stream.
Use of a disinfection system other than the permitted UV system during circumstances not deemed as
emergency and/or temporary (replacement of lamps, lamp cleaning or maintenance, etc.) will be
considered a violation of the terms of this permit.
ASHEV[LLE ASHEVILLE
CITIZEN - TIMES
VOICE OF THE MOUNTAINS •ClTIZEN-TIMES. VOICE OF THE MOUNTAINS • CITIZEN-TIMES.com
14 O. Henry Avenue • P.O. Box 2090 • Asheville, NC 28802.828-252-5611 • FAX 828-253-5092
PUBLIC NOTICE
STATE OF NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT
COMMISSIONMPDES UNIT
1617 MAIL SERVICE CENTER
RALEIGH, NORTH CAROLINA 27699-1617
NOTIFICATION OF INTENT TO REISSUE A
NPDES WASTEWATER GENERAL PERMIT
On the basis of thorough staff review and appli
cation of NC General Statute 143.21, Public law
92-500 and other lawful standards and regula '
Lions, the North Carolina Environmental Man
agement Commission proposed to issue a Nation
al Pollutant Discharge Elimination System
(NPDES) General Permit to the person(s) listed
below effective 45 days from the publish date of
this notice.
Written comments regarding the proposed per
mit will be accepted until 30 days after the pub-
lish date of this notice. All comments received
prior to that date are considered in the final de-
terminations regarding the permit. The Directo
of the NC Division of Water Quality may decide
to hold a public hearing for the proposed permi
should the Division receive a significant degree
of public interest.
Copies of the draft permit and other supporting
information on file used to determine conditions
present in the draft permit are available upon re
quest and payment of the costs of reproduction
Mail comments and/or requests for information
to the NC Division of Water Quality a1 the above
address, or call Dina Sprinkle (919) 733-5083, ex
tension 363, at the Point Source Branch. Please
include the NPDES permit number (attached) in
any communication. Interested persons may also
visit the Division of Water Quality at 512 N. Salts
bury Street, Raleigh, NC 27604-1148 between the
hours of 8:00 a.m. and 5:00 p.m. to review infor
motion on file.
The Adams Apple Homeowners Association, Inc
has applied for renewal of NPDES permi
NC0042358 for the Adams Apple Condominiums
WWTP in Avery County. This permitted facility
discharges treated wastewater to the Watauga
River in the Watauga River Basin. Currently
ammonia nitrogen and total residual chlorine are
water quality limited, This discharge may affec
future allocations in this portion of the wasl
ershed.
RCS Properties, Inc. has applied for renewal o
NPDES permit NC0062961 for the Shoppes of Ty
necastle WWTP in Avery County. This permitted
facility discharges Treated wastewater to the WO
tauga River in the Watauga River Basin. Cur
rentiy, ammonia nitrogen is water quality lim
ited. This discharge may affect future allocations
in this portion of the watershed.
September 16, 2007 (3940)
AFFIDAVIT OF PUBLICATION
BUNCOMBE COUNTY
SS.
NORTH CAROLINA
Before the undersigned, a Notary Public of said
County and State, duly commissioned, qualified and
authorized by law to administer oaths, personally
appeared Cory Kordupel, who, being first duly
sworn, deposes and says: that she is the Legal
Billing Clerk of The Asheville Citizen -Times,
engaged in publication of a newspaper known as
The Asheville Citizen -Times, published, issued,
and entered as First class mail in the City of
Asheville, in said County and State; that she is
authorized to make this affidavit and sworn
statement; that the notice or other legal
advertisement, a true copy of which is attached
hereto, was published in The Asheville Citizen -
Times on the following date: September 16th, 2007.
And that the said newspaper in which said notice,
paper, document or legal advertisement was
published was, at the time of each and every
publication, a newspaper meeting all of the
requirements and qualifications of Section 1-597 of
the General Statues of North Carolina and was a
qualified newspaper within the meaning of Section
1-597 of the General Statues of North Carolina.
Signed this 17th, day of September 2007.
07/ 1L�
(Signature of pe>rSon making affida
Sworn to and subscribed before me the 17th, day of
(Notary Pul>>ic)
My Co emission expires the 3`d day of Sept:TM
2008.
JOVE p '..
-( :
"VC O�`a
OMBE O ,,.
IWC Calculations
Shoppes of Tynecastle
NC0062961
Prepared By: Bob Sledge, NPDES Unit
Enter Design Flow (MGD):
Enter s7Q10(cfs):
Enter w7Q10 (cfs):
0.03
0.1
0.1
Residual Chlorine
7010 (CFS)
DESIGN FLOW (MGD)
DESIGN FLOW (CFS)
STREAM STD (UG/L)
UPS BACKGROUND LEVEL (l
IWC (To)
Allowable Conc. (ugll)
Fecal Limit
(If DF >331; Monitor)
(If DF <331; Limit)
Dilution Factor (DF)
NPDES Servor/Current Versions/IWC
0.1
0.03
0.0465
17.0
0
31.74
54
Ammonia (NH3 as N)
(summer)
7010 (CFS)
DESIGN FLOW (MGD)
DESIGN FLOW (CFS)
STREAM STD (MG/L)
UPS BACKGROUND LEVEL
IWC (To)
Allowable Conc. (mgll)
Ammonia (NH3 as N)
(winter)
7Q10 (CFS)
200/100m1 DESIGN FLOW (MGD)
DESIGN FLOW (CFS)
STREAM STD (MG/L)
3.15 UPS BACKGROUND LEVEL
IWC (%)
Allowable Conc. (mg/I)
0.1
0.03
0.0465
1.0
0.22
31.74
2.7
0.1
0.03
0.0465
1.8
0.22
31.74
5.2
9/10/2007
Permits, Permits, & More Permits
Subject: Permits, Permits, & More Permits
From: Bob Sledge <Bob.Sledge@ncmail.net>
Date: Wed, 25 Jul 2007 11:12:53 -0400
To: Wanda Frazier <Wanda.Frazier@ncmail.net>, Jim Reid <Jitn.Reid@ncmail.net>
Hi Wanda & Jim,
I wanted to ask some questions about some permits. I'm not sure who might be
responsible for them at this time, but y'all are shown on BIMS as the last inspectors
to visit these facilities. These are supposed to be expedited permits, but it seems
I can't help but make them more difficult than they ought to be. I thank you in
advance for your feedback regarding goofy questions.
NC0062961 Shops of Tynecastle Avery County
I found an 2005 AtoC in the file upgrade of the facility. Their renewal application
suggests these changes have been made, but I didn't find a copy of the engineer's
certification that construction was completed. First of all, should I update the
facility description as set forth in the AtoC? On the limits page, should the flow
limit be reduced from 0.04 to 0.03 MGD since the AtoC states it will have a lower
design flow?
The new construction notes installation of UV disinfection. There is no mention of a
back-up system. That being the case, our policy would say there is no need to even
keep a parameter listing for TRC with a footnote stating monitoring would be required
only if it is used. However, there still seems to be concern around here as to how
to potentially deal with those occasions when a UV system would fail.
I'm going to suggest that we add a condition to the permit that would require the
permittee to call the regional office upon their knowledge of the UV system failing
(I'd say this is already a term of the permit). At the same time, the SWP staff
could discuss with the permittee any plans that ought to be made to implement a
temporary, alternate means of disinfection. Such plans could be site and
circumstance specific, with factors such as flow, receiving stream, control mechanism
and length of time the UV system is anticipated to be down being taken into account.
It may be the region's determination that an alternate means would potentially do
more harm than good. Such a determination would not release the permittee from
compliance with fecal coliform limits. What do you think? Is such a term necessary?
I've got a couple of other permits with the same circumstance in the Winston-Salem
Region. I'm asking them to comment on the same proposal.
NC0042358 Adams Apple Condominiums Avery County
My basic question here is do you want to keep Temperature monitoring frequencies for
upstream and downstream monitoring at "daily?" The rules would only call for weekly,
but it's probably not a big deal to us or them either way. An associated question is
where are the designated up and downstream monitoring sites. I've found information
in the file that states either 50 or 100 feet above or below the discharge. If we're
requiring the monitoring, we ought to put the location in the permit. Where do you
think it should be?
NC0065889 Indian Creek Resort Transylvania County
This one has the same major issue as that for NC0062961 noted above.
The only other question I have is why they insist on having an individual, as opposed
to an entity, named as permittee. I've got a call into their consultants asking
about that.
NC0063312 Cedar Creek Racquet Club Jackson County
Another one with UV disinfection, so the same question as for the other two.
1 of 2 9/10/2007 9:34 AM
Water Quality Lab and Operations, Inc.
P.O. Box 1167/ 1522 Tynecastle Highway
Banner Elk, NC 28604
Ph. 828-898-6277 Fax 828-898-6255
N.C. Division of Water Quality
1617 Mail Service Center
Raleigh, NC 27699-1617
Water Quality Lab and Operations
1522 Tynecastle Highway
Banner Elk, NC 28604
NC DENR/DWQ/Point Source Branch
Att: Mrs. Carolyn Bryant
Tynecastle
April 30, 2007
Mrs. Bryant,
Tynecastle permit renewal was completed by Jadd Brewer at Water Quality Lab and
Operations, Inc. located in Banner Elk, NC. If you have any questions at all feel free to
contact myself, Jadd Brewer at 828-898-6277.
Added Information
The bio excess solids when removed from the wastewater treatment plant will be hauled
directly to the Town of Boone wastewater treatment plant.
4;'Qis
Jadd Brewer
Water Quality Lab and Operations, Inc.
NPDES APPLICATION FOR PERMIT RENEWAL- SHORT FORM D
To be filed only by privately -owned dischargers of 100% domestic wastewater (<1 MGD flow)
N. C. Department of Environment and Natural Resources
Division of Water Quality / NPDES Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
http: / /h2o.enr.state.nc.us/ NPDES /
North Carolina NPDES Permit Number
1. Contact Information:
Facility Name
Owner Name
Street Address
City
State / Zip Code
Telephone Number
Fax Number
e-mail Address
Operator Name
Street Address
City
State / Zip Code
County
Telephone Number
NC00 47aq( /
Please print or type
o�6,e ? 5eni eA
570 Tyf/ c.¢s7«
.e34s€414EQ �GK
,�-C. noof<
(fags)
0.ij'x // 7
e74x/445e_ �Gk
( 8�8' ► :?s64.2;7
2. Location of facility producing discharge:
Check here if same as above
Facility Name (If different from above)
Street Address or State Road
City
State / Zip Code
County
3. Reason for application:
Expansion/Modification *
r����OC'9�,j
8 2005 _•
Existing Unpermitted Discharge
Renewal New Facility
* Please provide a description of the expansion/modification:
�E�Li}C/�t/6 A'i5T/•!�6 �JL,vJ7 uii T/re ,-'/ , 1C/rr'66
,..›t.¢.r/T ,7ri a t/ Pi5,'." G./7AV "M/D sEa/Ei 049-O.(.
Page 1 of 3 Version 12/02
NPDES APPLICATION FOR PERMIT RENEWAL- SHORT FORM D
To be filed only by privately -owned dischargers of 100% domestic wastewater (<1 MGD flow)
4. Description of the existing treatment facilities (list all installed components with
capacities):
'( SC.el.-eN, �¢6.P4 /7 Gl�.ei�CATio 5I'Il66E
4,49, ;€4/47v vJ Pee/94e2 ei r>.1rlo.v/ „Cco v „.4./T
/,S "06.64//,76D .o.0 p /#i 2 ' , DA�.Q.¢TiA)6 .¢T 5 vvO-7vv�f'P!)
5. Description of wastewater (check all that apply
Type of Facility Generating Wastewater
Industrial Number of Employees
Commercial Number of Employees
Residential Number of Homes
School Number of Students/Staff
Other
/6ad
5-
Describe the source(s) of wastewater (example: subdivision, mobile home park, etc.):
-5/N8LE fdA1/L�/ 'low5 i¢N /t7 3ffOP/0/.eie
6. List all permits, construction approvals and/or applications (check all that apply):
TPpe Permit Number Type Permit Number
RCRA Non -Attainment
UIC Ocean Dumping
NPDES Dredge/ Fill Permits
PSD Other
NESHAPS
7. Number of separate wastewater discharge pipes (wastewater outfalls):
eVifl
8. If the facility has multiple discharge outfalls, record the source(s) of wastewater for each
outfall:
Page 2 of 3 Version 12/02
rrNr co
•
Va u..: Yop
i ooert c... bcnweoke ar. t r lei
4tib-U142 p.2
NPDES APPLICATION FOR PERMIT RENEWAL- SHORT FORM D
To he Bled only tn' priv:,frlv•ownt_(1 dischargers of IOO' (I(rmcstir w%.Wtw zilcr I.:. MG1? flow)
9. Name of receiviul streamlMJ (/'rtrc,uic a ?Imp ytlu/urnr
� the exact ler,•r/hU►t U( ('r7e1/r our Hy;
- 4 Le
10. Is this facility located on Native American Lads? (check- or/t)
1 certify that 1 am familiar with the information contained in the application and that to
the beat of my knowledge and belief such information is true, complete, and accurate.
1 tinted Name of I'rrSrijt Signor;
Ti
1>;ue Signetf
Monti Carolina Ccsieraf Statute 143 21 h (1bx7) prrrsir, that Arty per5on wen knowingly rc,irtes ar y tatse srarnment represe' I?L:m. r+,
rCddCJiion u, ,ug orchratol, recinif. report. p,,rr. (II ;Aker document htam,u nKti4red ro be nt:wut,rned under /Vial,: 1 i• regulations of Ili
Environrn(:nlal Management C(xnnrrsston impicnrrnt,og that Adak. ai who 'Ascher,. tamtx:n- wdh. vI knowingly rendei:. If1;ioetr,to aw
retordnkt or mrurik my dewaic u+ method recoils! In I.;+: operated of mainidined under Anil.' it or regulations of lire [rtvn,irnaeniar
markotpr,rrnt Cu rn,, :on n;lritmenring Mai Adrffe shall be guilty ,if a misdemeanor puniglabfc ty a lino mum r:ua,r4 t1 O.(UJ of by
inyurs,x,ntert not k1 att,a,,.l r.is monee. or by 001h (1411 Si., rout provider., a puny It »e,d by a tined. nou ,ociu rr .wr 110 OCO a
i1r1(w .1j. rnrrll not more Iiwn b years. of tnlih ft• a r*mrt& oftcnse i
_Ii411:IIUTrt nt Appllr;;_lrtf r
VP+tirx, f 7/rr7
t abed
APR 26,2005 03:45?
b0EL9S9&?S
772 466 0142
VZE 60 SOOZ r9Z 2idV
page 2
FACT SHEET FOR EXPEDITED PERMIT RENEWALS
ine potential for expedited permit renewal
Reviewer/Date
/3642...b+
Permit Number
IklGa6 ED2Th i
Facility Name
Basin Name/Sub-basin number
w1J& A- k.c Or; - /bel- -Di-
Receiving Stream
0541A6-"t- V-wP"--
Stream Classification in Permit
13 --flL - CIJ
Does permit need NH3 limits?
�J
4( S L7 Au' --
Does permit need TRC limits?
ia. -C j L(.lc t r)
Does permit have toxicity testing?
_ p,3Q —
Does permit have Special Conditions?
pJ O
Does permit have instream monitoring?
`r"
Is the stream impaired (on 303(d) list)?
p-1'b
Any obvious compliance concerns?
Any permit mods since last permit?
5a - A_ ro c_ '—
Existing expiration dated
New expiration date
T f 5P 12.
New permit effective date
Miscellaneous Comments
\v1 Pc4i
YES % This is a SIMPLE EXPEDITED permit renewal (administrative
renewal with no changes, or only minor changes such as TRC, NH3,
YES
name/ownership changes). Include conventional WTPs in this group.
This is a MORE COMPLEX EXPEDITED permit renewal (includes
Special Conditions (such as EAA, Wastewater Management Plan), 303(d)
listed, toxicity testing, instream monitoring, compliance concerns, phased
limits). Basin Coordinator to make case -by -case decision.
YES This permit CANNOT BE EXPEDITED for one of the following reasons:
• Major Facility (municipal/industrial)
• Minor Municipals with pretreatment program
• Minor Industrials subject to Fed Effluent Guidelines (lb/day limits for BOD, TSS,
etc)
• Limits based on reasonable potential analysis (metals, GW remediation organics)
• Permitted flow > 0.5 MGD (requires full Fact Sheet)
• Permits determined by Basin Coordinator to be outside expedited process