HomeMy WebLinkAboutNCG030557_2022 DMR_20220708NCDEQ Division of Energy, Mineral and (Land Resources
Stormwater Discharge Monitoring Report (DMR) Form for NC6030000
Metal Fabrication
Click here for instructions
Complete, sign, scan and submit the DMR via the Stormwater NPDES Permit Data Monitoring Report (DMR) Upload form within
30 days of receiving sampling results. Mail the original, signed hard copy of the DMR to the appropriate DEMLR Regional Office.
Certificate of Coverage No. NCG030557
Person Collecting Samples: Timothy I Fernandez
Facility Name: Kidde Aerospace and Defense
Laboratory Name: Microbac Labs
Facility County: Wilson
Laboratory Cert. No.: 11
Discharge during this period:
Yes
No (if no, skip to signature and date)
Has your facility implemented mandatory Tier response actions this sample period for any benchmark exceedances? Yes No
If so, which Tier (I, II, or IH)? I&II
A copy of this DMR has been uploaded electronically via https://edocs.deci.nc.pov/Forms/SW-DMR Yes Lj No
Date Uploaded: 07/11/2022
Analytical Monitoring Requirements for Outfalls with Industrial Activities — Benchmarks in (Red)
Parameter
Parameter
Outfall1
Outfall2
Outfall
Outfall
Outfall
Code
N/A
Receiving Stream Class
C
C
N/A
Date Sample Collected MM/DD/YYYY
06/16/2022
06/16/2022
46529
24-Hour Rainfall in inches
.5
.5
C0530
TSS in mg/L (100 or 500)
201
229
00400
pH in standard units (6.0 — 9.0 FW,
6.9
7.0
6.8-8.5 SW)
Copper, total recoverable in mg/L
01119
10.010 FW, 0.0058 SW)
0.0116
0.0260
01051
Lead, total recoverable in mg/ L
<0 0160
<0.0160
(0.075 FW, 0.22 5W)
Zinc, total recoverable in mg/ L (0.126
01094
FW, 0.095 SW)
0.113
0.156
00340
Chemical Oxygen Demand (COD) in
194
136
mg/L (220)
00552
Non -Polar oil & Grease in mg/L (15)
<6.10
<6.02
* Outfalls to Outstanding Resource Waters (ORW), High Quality Waters (HQW), Trout Waters (Tr) and Primary Nursery Areas IPNA)
have a benchmark TSS limit of 50 mg/L. All other water classifications have a benchmark of 100 mg/L
FW (Freshwater) S (Saltwater)
Notes (optional): Tier 2 Response OF-1 (Cu & Zn over in Q3 2021 then 2 gtrs of no flow) - Tier 1 Response OF-2
"I certify by my signature below, under penalty of law, that this document and all attachments were prepared under my direction or supervision in
accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my
inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information
submitted is, to the best of my knowledge and belief, true, accurate, and complete_ l am aware that there are significant penalties for submitting
false information, including the possibility of fines and imprisonment for knowing violations."
Signature of Permittee or Delegated Authorized Individual
Email Address
8 as
Date
�26,,2- 7y*-/y8G
Phone Number