Ms. Stephanie Scheringer, Division Manager
Two Rivers Utilities
P.O. Box 1748
Gastonia, NC 28053
Subject: Compliance Evaluation Inspection
Long Creek WWTP
NPDES Permit No. NC0020184
Gaston County
Dear Ms. Scheringer:
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted at the
subject facility on August 30, 2022, by Ori Tuvia. The assistance and cooperation of David
Shellenbarger and Maurice Brothers during the site visit was much appreciated. Please advise the
staff involved with this NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions concerning this
report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
Sincerely,
DocuSigned by:
44 44cw H P;.xa.e4
F161FB69A2D84A3...
Andrew H. Pitner P.G., Assistant Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Cc: NPDES, MRO Files (Laserfiche)
NC DWR — Water Quality Regional Operations Section 610 East Center Avenue, Suite 301, Mooresville, NC 28115
Mooresville Regional Office Phone: (704) 663-1699 FAX: (704)-633-6040
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2
21IIIIII
NPDES yr/mo/day Inspection
L 3 I NC0020184 111 121 22/09/01 117
Type
18110
IIIIIIIIIII
Inspector Fac Type
19 I S I 201
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 731 I 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Long Creek WWTP
3000 Old Spencer Mountain Rd
Dallas NC 28034
Entry Time/Date
12:OOPM 22/09/01
Permit Effective Date
22/02/01
Exit Time/Date
02:30PM 22/09/01
Permit Expiration Date
27/01/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Mourice Kenith Brothers//704-214-9121 /
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Douglas E Barker,PO Box 1748 Gastonia NC 280531748/Senior Plant
Operator/704-866-6991/7049220619 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and
Ori A Tuvia
Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
1—DocuSigned by:
_-�� DWR/Division of Water Quality/704-663-1699/ 9/1/2022
\- BB 057A2DE017'198...
Signature of Ma
Andrew Pit
041MReviewer Agency/Office/Phone and Fax Numbers Date
rA4'44. 4 H P44.st WR/MRO WQ/704-663-1699 Ext.2180/ 9/1/2022
F161 FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0020184 111 121 22/09/01
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El El
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The subject permit expires on January 31, 2027
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ El El El
Comment: Records were reviewed for the period of March 2022 - June 2022, Lab results, Chain
of Custody, ORC Log, and Field parameter results taken including the calibration data
were complete and well organized.
Page# 3
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: Permit requires both influent composite samples and grab sampling.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: Permit requires both effluent composite samples (flow proportional) and grab sampling.
Aliquot verification taken during the inspection pulled 200 ml
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, MODE
and sampling location)?
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Lab instrument appeared to be well maintained and calibrated
Yes No NA NE
• ❑ ❑ ❑
Page# 4
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility appeared to be properly operated and well maintained. The operations
staff incorporate a comprehensive process control program with all documentation
being properly documented and maintained on -site. The facility is equipped with a
SCADA system to assist the operations staff with the monitoring of treatment processes
and units.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ❑
b.Mechanical •
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? ■ ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ El El
Is the unit in good condition? • El El El
Comment: Screenings and grit are disposed at the county landfill
Grit Removal Yes No NA NE
Type of grit removal
a.Manual ❑
b.Mechanical •
Is the grit free of excessive organic matter? • El El El
Is the grit free of excessive odor? • El El El
# Is disposal of grit in compliance? • ❑ ❑ ❑
Comment: Screenings and grit are disposed at the county landfill
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Yes No NA NE
Page# 5
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? • ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? • El El El
Comment:
Primary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ ❑ ❑
Are weirs level? ❑ • ❑ ❑
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? ■ ❑ ❑ ❑
Is scum removal adequate? • ❑ ❑ ❑
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? • ❑ ❑ ❑
Is the sludge blanket level acceptable? ■ ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • ❑ ❑ ❑
Comment: Two of three primaries were in service (all operational). At the time of the inspection the
weires were uneven
Nutrient Removal Yes No NA NE
# Is total nitrogen removal required? • ❑ ❑ ❑
# Is total phosphorous removal required? • ❑ ❑ ❑
Type Biological
# Is chemical feed required to sustain process? • ❑ El El
Is nutrient removal process operating properly? • El El El
Comment: The facility, combined with Eagle Road WWTP, are required to comply with a summer
(April 1 - October 31) effluent total nitrogen loading limit as well as winter (November 1
— March 31) effluent total nitrogen loading limit. The combined facilities also have a
year around effluent total phosphorus loading limit. Nutrient removal is performed
biologically and chemically (alum)
Page# 6
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: 3 of the 4 aeration tracks were in operation during the inspection (4th was out for
maintenance)
Chemical Feed Yes No NA NE
Is containment adequate? • ❑ ❑ ❑
Is storage adequate? ■ ❑ ❑ ❑
Are backup pumps available? • ❑ ❑ ❑
Is the site free of excessive leaking? • ❑ ❑ ❑
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: 3 of the 4 aeration tracks were in operation during the inspection (4th was out for
maintenance)
Page# 7
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Down flow
Is the filter media present? • ❑ El El
Is the filter surface free of clogging? • ❑ ❑ ❑
Is the filter free of growth? • ❑ ❑ ❑
Is the air scour operational? • ❑ ❑ ❑
Is the scouring acceptable? • ❑ ❑ ❑
Is the clear well free of excessive solids and filter media? ■ ❑ ❑ ❑
Comment: 5 of 8 tertiary filters were in service
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: One ton cylinders are stored outside together under cover
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
1000-0006-7367
Yes No NA NE
Gas
• ❑ ❑ ❑
▪ ❑ ❑ ❑
❑ ❑ • ❑
Page# 8
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The influent and effluent flow meters are calibrated/verified twice per year
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Comment: Right of way was not maintained. Effluent appeared clear with no floatable solids or
foam
Lagoons Yes No NA NE
Type of lagoons?
# Number of lagoons in operation at time of visit? 2
Are lagoons operated in? Series
# Is a re -circulation line present? ❑ ❑ • ❑
Is lagoon free of excessive floating materials? • ❑ ❑ ❑
# Are baffles between ponds or effluent baffles adjustable? ❑ ❑ • ❑
Are dike slopes clear of woody vegetation? • ❑ ❑ ❑
Are weeds controlled around the edge of the lagoon? • ❑ ❑ ❑
Are dikes free of seepage? • ❑ ❑ ❑
Are dikes free of erosion? • ❑ ❑ ❑
Are dikes free of burrowing animals? ❑ ❑ • ❑
Page# 9
Permit: NC0020184
Inspection Date: 09/01/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Lagoons Yes No NA NE
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple ❑ ❑ • ❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth? El El El
Is the lagoon surface free of weeds? ■ ❑ ❑ ❑
Is the lagoon free of short circuiting? ❑ ❑ • ❑
Comment:
Anaerobic Digester
Type of operation:
Is the capacity adequate?
# Is gas stored on site?
Is the digester(s) free of tilting covers?
Is the gas burner operational?
Is the digester heated?
Is the temperature maintained constantly?
Is tankage available for properly waste sludge?
Yes No NA NE
Fixed cover
• ❑ ❑ ❑
Comment: Waste activated sludge (WAS ) is thickened in a DAF unit prior to being pumped to
thediqesters. The facility is equipped with six anaerobic digesters (4-primary, 3 in
operation and 2-secondary). Bio-solids are land applied by a contracted company
(EMA) under the authority of Permit No. WQ0OO1793.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The facility is equipped with three standby generators that are placed under load at
leat once per month (peak shaving/storm events)
Page# 10