Loading...
HomeMy WebLinkAboutWQCSD0219_Letter_20220822ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director Aqua North Carolina, Inc Attn: Shannon V. Becker, President 202 Mackenan Drive Cary, NC 27511-6447 NORTH CAROLINA Environmental Quality August 22, 2022 Subject: Compliance Evaluation Inspection Melbille Heights Collection System Permit Number: WQCSD0219 Randolph County Dear Mr. Becker: Ron Boone, of the Winston-Salem Regional Office (WSRO) of the NC Division of Water Resources (DWR), conducted a compliance evaluation inspection (CEI) of the subject wastewater collection system on August 4t", 2022. Inspection findings are detailed in the attached compliance inspection report. If you have any questions or concerns regarding the inspection, please contact Mr. Boone by phone at 336-776-9690, or by email at ron.boone@ncdenr.gov. Thank you for your attention to this matter. Sincerely, DocuSiiggned by: 1 _.49E225CMEA... Lon T. Snider, Regional Supervisor Water Quality Regional Operations Section Winston-Salem Regional Office Division of Water Resources, NCDEQ Attachments: 1. Compliance Inspection Report DffNorth Carolina Department of Environmental Quality I Division of Water Resources oan caaouNn Winston-Salem Regional Office 1 450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105 M336.776.9800 oep.m.m or em�nmen� Qualm Permit: WQCSD0219 SOC: County: Randolph Region: Winston-Salem Compliance Inspection Report Effective: 03/01/00 Expiration: Owner : Aqua North Carolina Inc Effective: Expiration: Facility: Melbille Heights Collection System Contact Person: Randy Simmons Title: Directions to Facility: System Classifications: Primary ORC: Secondary ORC(s): On -Site Representative(s): Related Permits: Inspection Date: 08/04/2022 Entry Time 02:OOPM Primary Inspector: Ron Boone DocuSigned by: Secondary Inspector(s): °",a& B°OfLe, B20FMD5F2A3460... Certification: Phone: 336-992-9000 Phone: Exit Time: 03:OOPM Phone: 336-776-9690 8/19/2022 Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling Permit Inspection Type: Deemed permitted collection system management and operation Facility Status: Compliant ❑ Not Compliant Question Areas: Miscellaneous Questions (See attachment summary) Page 1 of 4 Permit: WQCSD0219 Owner - Facility: Aqua North Carolina Inc Inspection Date: 08/04/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Ron Boone, of the Winston-Salem Regional Office of the NC Division of Water Resources, conducted a compliance evaluation inspection of the Melbille Heights WWCS on 8/4/22. The assistance and cooperation of Shelby Check was greatly appreciated. Inspection findings are detailed below. NC Administrative Code 15A NCAC 02T .0403, requires the following for deemed permitted collection systems such as Melbille Heights: (1) The collection system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters and to prevent any contravention of groundwater standards or surface water standards. The system appears to be sufficiently operated and maintained in accordance with all requirements. (2) A map of the collection system shall have been developed and shall be maintained. The collection system map was reviewed and found to be sufficient. (3) An operation and maintenance plan, including pump station inspection frequency, preventative maintenance schedule, spare parts inventory, and overflow response shall have been developed and implemented. The O&M and Spill Plans were reviewed and found to be sufficient. (4) Pump stations that are not connected to a telemetry system shall be inspected by the permittee or its representative every day, 365 days per year, unless the permittee demonstrates that daily inspections are not necessary because the pump station has sufficient storage capacity, above the elevation at which the pump activates, to justify a longer inspection interval. In no case shall the inspection interval exceed seven days. Pump stations that are connected to a telemetry system shall be inspected once per week. There are no pump stations within the collection system. (5) High -priority sewers shall be inspected by the permittee or its representative once every six -months, and inspections shall be documented. Records of the inspections of HPSs were complete and current. (6) A general observation by the permittee or its representative of the entire collection system shall be conducted once per year. The general observation requirement is met in conjunction with the jetting program. (7) Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 02B .0506(a), and public notice shall be provided as required by G.S. 143-215.1C. No SSOs have been reported from the system in the past three years. (8) A Grease Control Program shall be in place as follows: (B) For privately owned collection systems, the Grease Control Program shall include bi-annual distribution of grease education materials to users of the collection system by the permittee or its representative. Newsletters which include the FOG information are distributed twice per year. Documentation of the activities is accomplished by dating the newsletters and keeping copies of them on file in Aqua's home office. Page 2 of 4 Permit: WQCSD0219 Owner - Facility: Aqua North Carolina Inc Inspection Date: 08/04/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine (9) Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment accessibility. ROWs are maintained as required. Contractor invoices for the work are kept as records of the activities. (10) Documentation of compliance with Subparagraphs (a)(1) through (a)(9) of this Rule shall be maintained by the collection system owner for three years with the exception of the map, which shall be maintained for the life of the system. Required documentation was available and found to be complete, compliant, and current. Page 3 of 4 Permit: WQCSD0219 Owner - Facility: Aqua North Carolina Inc Inspection Date: 08/04/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Page 4 of 4