July 9, 2022
Subject: Compliance Evaluation Inspection
Crooked Creek Collection System
Collection System Permit Number WQCSD0173
Wake County
Dear Mr. Becker:
On June 14, 2022, Colleen Cohn of the Raleigh Regional Office (RRO) conducted an inspection
at the subject facility. The cooperation of Lorrie Stagner and Brandon Cummings was greatly
appreciated. During the inspection, the following items were noted:
1. Aqua North Carolina, Inc., hereafter referred to as Aqua, operates a deemed collection
system pursuant to 15 NCAC .02T .0403.
2. The system includes two (2) duplex pump stations and approximately 31,828 feet of force
main and 10,871 feet of gravity main line. The average daily flow to the Johnson Pond
Lift Station is 37,460 gallons per day, and the average daily flow to the Sawyer's Mill
Lift Station is 37,674 gallons per day. Both pump stations had telemetry, operable
audible and visual alarms, and standby emergency generators.
3. Per Ms. Stagner and Mr. Cummings, the system does not have any high -priority lines.
4. All wastewater flow is conveyed to and treated at the Crooked Creek Wastewater
Treatment Plant (NC0062715).
5. Pump station weekly inspections and logbooks are being maintained as required. Both of
the system's two (2) pump stations (Johnson Pond and Sawyer's Mill) were observed
during the inspection. The system appeared to be well maintained. Very little grease was
observed in the wet wells. All emergency generators started when power was cut to the
pumps. Audible and visible alarms were operational at both pump stations when the high-
water float was lifted. Emergency contact information signs were posted and legible.
6. The Johnston Pond Lift Station Manhole was inspected. No blockages or significant
grease accumulation was observed. Manhole cover was at grade.
NORTH E, CAROLINA
Department
ofM Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office I 3800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Crooked Creek Collection System WQCDS0173
July 9, 2022
7. The Sawyer's Mill Lift Station Manhole was inspected. No blockages or significant
grease accumulation was observed. Some gravel was observed in the channel. Manhole
cover was at grade.
8. No Sanitary Sewer Overflows (SSO) have been identified or reported in the last 12
months. The last reported SSO for the system was in 2007.
9. Right-of-ways were last maintained June 9, 2022. Records of maintenance were available
in the operator's logbooks.
10. A review of the records indicates the following:
a) Per Ms. Stagner and Mr. Cummings, a GIS map of the system is actively size, flow
direction, and line material. A print-out map depicting manholes and pump stations
was available for review during the inspection.
b) Records are centrally maintained by Aqua for the facility's spare parts inventory,
annual system observation, and cleaning. Ms. Stagner and Mr. Cummings stated
that all gravity main lines were cleaned in June 2022, and are scheduled to be
cleaned every 5 years. An annual general observation of the entire system
observation is conducted over the course of day to day operations. An electronic
overflow response plan is accessible by employees.
c) Grease control educational materials are distributed bi-annually as required with
utility bills. It was last distributed in March 2022.
If you have questions concerning this report, please contact Colleen Cohn at 919-791-4258 or
Colleen.Cohn@ncdenr.gov.
Sincerely,
FDocuSigned by:
httALSSA, f, llil.a tAlta
B2916E6AB32144F...
Vanessa Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachments: Compliance Inspection Report
cc: Laserfiche
£ D_E
NORTHCAROLINA
Department of Environmental Deal
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office I 3800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Compliance Inspection Report
Permit: WQCSD0173 Effective: 03/01/00 Expiration:
SOC: Effective: Expiration:
County: Wake
Region: Raleigh
Owner : Aqua North Carolina Inc
Facility: Crooked Creek Collection System
Contact Person: Sam Pegram Title: Salem Glen Subdivision (WQCF. Phone: 336-215-4133
Directions to Facility:
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s): Lorrie Stagner
Brandon Cummings
Related Permits:
Inspection Date: 06/14/2022
Primary Inspector: Colleen Cohn
Secondary Inspector(s):
Entry Time 09:10AM
DocuSigned by:
�FBCB8277092044D...
Exit Time: 10:OOAM
7/7/2022 Phone: 919-791-4258
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: Compliant Not Compliant
Question Areas:
▪ Miscellaneous Questions
II Spills/Response Plan
▪ Manholes
(See attachment summary)
▪ General
▪ Inspections
▪ Pump Stations
▪ Grease Control
▪ Lines
Page 1 of 6
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Permit: WQCSD0173 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 06/14/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
On June 14, 2022, Colleen Cohn of the Raleigh Regional Office (RRO) conducted an inspection at the subject facility. The
cooperation of Lorrie Stagner and Brandon Cummings was greatly appreciated. During the inspection, the following items
were noted:
1. Aqua North Carolina, Inc., hereafter referred to as Aqua, operates a deemed collection system pursuant to 15 NCAC
.02T .0403.
2. The system includes two (2) duplex pump stations and approximately 31,828 feet of force main and 10,871 feet of
gravity main line. The average daily flow to the Johnson Pond Lift Station is 37,460 gallons per day, and the average daily
flow to the Sawyer's Mill Lift Station is 37,674 gallons per day. Both pump stations had telemetry, operable audible and
visual alarms, and standby emergency generators.
3. Per Ms. Stagner and Mr. Cummings, the system does not have any high -priority lines.
4. All wastewater flow is conveyed to and treated at the Crooked Creek Wastewater Treatment Plant (NC0062715).
5. Pump station weekly inspections and logbooks are being maintained as required. Both of the system's two (2) pump
stations (Johnson Pond and Sawyer's Mill) were observed during the inspection. The system appeared to be well
maintained. Very little grease was observed in the wet wells. All emergency generators started when power was cut to the
pumps. Audible and visible alarms were operational at both pump stations when the high-water float was lifted. Emergency
contact information signs were posted and legible.
6. The Johnston Pond Lift Station Manhole was inspected. No blockages or significant grease accumulation was
observed. Manhole cover was at grade.
7. The Sawyer's Mill Lift Station Manhole was inspected. No blockages or significant grease accumulation was observed.
Some gravel was observed in the channel. Manhole cover was at grade.
8. No Sanitary Sewer Overflows (SSO) have been identified or reported in the last 12 months. The last reported SSO for
the system was in 2007.
9. Right-of-ways were last maintained June 9, 2022. Records of maintenance were available in the operator's logbooks.
10. A review of the records indicates the following:
a) Per Ms. Stagner and Mr. Cummings, a GIS map of the system is actively maintained by Aqua depicting manholes,
pump station locations, right of ways, line size, flow direction, and line material. A print-out map depicting manholes and
pump stations was available for review during the inspection.
b) Records are centrally maintained by Aqua for the facility's spare parts inventory, annual system observation, and
cleaning. Ms. Stagner and Mr. Cummings stated that all gravity main lines were cleaned in June 2022, and are scheduled
to be cleaned every 5 years. An annual general observation of the entire system observation is conducted over the course of
day to day operations. An electronic overflow response plan is accessible by employees.
c) Grease control educational materials are distributed bi-annually as required with utility bills. It was last distributed in
March 2022.
Page 2 of 6
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Permit: WQCSD0173 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 06/14/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General Yes No NA NE
# Is this system a satellite system? • ❑ ❑ ❑
# If Yes, what is system name or permit number? NC0062715
Is there a overall sewer system map? • ❑ ❑ ❑
Does the map include:
Pipe sizes • ❑ ❑ ❑
Pipe materials (PVC, DIP, etc) • ❑ ❑ ❑
Pipe location • ❑ ❑ ❑
# Flow direction • ❑ ❑ ❑
# Approximate pipe age ❑ ❑ ❑ •
# Pump station ID, location and capacity • ❑ ❑ ❑
# Force main air release valve location & type ❑ ❑ ❑ •
# Location of satellite connections ❑ ❑ ❑ •
Are system maintenance records maintained? • ❑ ❑ ❑
Comment: Aqua keeps electronic records at central location.
Grease Control Yes No NA NE
Is grease/sewer education program documented with req'd customer distribution? • El El El
# Are other types of education tools used like websites, booths, special meetings, etc? ❑ ❑ ❑ •
If Yes, what are they? (This can reduce mailing to annual.)
For public systems, is there a Grease Control Program via an ordinance/agreement? ❑ ❑ • ❑
If Yes, does it require grease control devices at applicable locations? ❑ ❑ • ❑
Is the Grease Control Program enforced via periodic inspections/records review? ❑ ❑ • ❑
Is action taken against violators? El El • El
Comment: FOG letter sent to customers with their monthly bill twice a year. Last mailed in March 2022.
Spills and Response Action Plan
# Is system free of known points of bypass?
If No, describe type of bypass and location
# Have there been any sewer spills in the past 3 years?
If Yes, were they reported to the Division if meeting the reportable criteria?
If applicable, is there documentation of press releases and public notices issued?
Are all spills or sewer related issues/complaints documented?
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
# If Yes, is there a corrective action plan?
Is a Spill Response Action Plan available?
Is a Spill Response Action Plan available for all personnel?
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Page 3 of 6
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Permit: WQCSD0173 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 06/14/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Does the plan include:
# 24-hour contact numbers
# Response time
# Equipment list and spare parts inventory
# Access to cleaning equipment
# Access to construction crews, contractors, and/or engineers
# Source of emergency funds
# Site sanitation and cleanup materials
# Post-overflow/spill assessment
Comment: SSO Reponse Plan kept electronically. Spare Parts kept at central location.
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Inspections Yes No NA NE
Are adequate maintenance records maintained? • ❑ ❑ ❑
Are pump stations being inspected at the required frequency? • ❑ ❑ ❑
Is at least one complete functionality test conducted weekly per pump station? • ❑ ❑ ❑
Is there a system or plan in place to observe the entire system annually? • El El El
Is the annual inspection documented? • ❑ ❑ ❑
# Does the system have any high -priority lines/locations? El • ❑ ❑
Are inspections of HPL documented at least every 6 months? ❑ ❑ • ❑
Are new lines being added to the HPL list when found or created? ❑ El • ❑
Comment: Lift stations connected to telemetry. Logsheets kept at both lift stations.
Lines/Right-of-Ways/Aerial Lines
Please list the Lines/Right of Ways/Aerial Lines Inspected:
Are right-of-ways and easements maintained for the full width for access?
If No, give details on temporary access:
Is maintenance documented?
Were all areas/lines inspected free of issues?
Comment: Right-of-ways last cleared June 9, 2022.
Manholes
Please list the Manholes Inspected:
Sawyer's Mill lift station manhole and Johnson Pond Lift Station manhole
Are manholes accessible?
# Are manhole covers/vents above grade?
Are manholes free of visible signs of overflow?
Are manholes free of sinkholes and depressions?
Are manhole covers present?
# Are manholes properly seated?
Yes No NA NE
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
Page 4 of 6
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Permit: WQCSD0173 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 06/14/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
# Are manholes in good condition?
# Are inverts in good condition?
Is flow unrestricted in manholes?
Are manholes free of excessive amounts of grease?
Are manholes free of excessive roots?
Are manholes free of excessive sand?
Are manhole vents screened?
Are vents free of submergence?
Are manholes free of bypass structures or pipes?
Comment: Some gravel noted in manhole at Sawyer's Mill Lift Station
Pump Stations
Please list the Pump Stations Inspected:
Sawyer's Mill and Johnson Pond
# Number of duplex or larger pump stations in system
# Number of vacuum stations in system
# Number of simplex pump stations in system
# Number of simplex pump stations in system serving more than one building
How many pump/vacuum stations have:
# A two-way "auto polling" communication system (SCADA) installed?
# A simple one-way telemetry/communication system (auto -dialer) installed?
For pump stations inspected:
Are they secure with restricted access?
Were they free of by-pass structures/pipes?
Were wet wells free of excessive grease/debris?
# Do they all have telemetry installed?
Is the telemetry system functional?
Is a 24-hour notification sign posted ?
Does the sign include:
Owner Name?
Pump station identifier?
# Address?
Instructions for notification?
24-hour emergency contact numbers?
Are audio and visual alarms present?
Are audio and visual alarms operable?
# Is there a backup generator or bypass pump connected?
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ •
• ❑ ❑ ❑
▪ ❑ ❑ ❑
Yes No NA NE
2
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 5 of 6
DocuSign Envelope ID: 4C67CDB4-DEE2-4B51-86A0-5DACOF7BC4A1
Permit: WQCSD0173 Owner - Facility:Aqua North Carolina Inc
Inspection Date: 06/14/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
If tested during inspection, did it function properly?
Is the back-up system tested at least bi-annually under normal operating conditions?
# Does it have a dedicated connection for a portable generator?
# Is the owner relying on portable units in the event of a power outage?
# If Yes, is there a distribution plan?
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
# Does Permittee have the approved percentage of replacement simplex pumps?
Is recordkeeping of pump station inspection and maintenance program adequate?
Do pump station logs include at a minimum:
Inside and outside cleaning and debris removal?
Inspecting and exercising all valves?
Inspecting and lubricating pumps and other equipment?
Inspecting alarms, telemetry and auxiliary equipment?
Comment:
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 6 of 6