HomeMy WebLinkAbout20220896 Ver 1_More Info Received_20220912EAGLE ENGINEERING September 7, 2022 NCDWR RE: Long Creek Village — Winston-Salem, NC DWR # 20220896 We are in receipt of your review comments for the construction documents associated with Long Creek Village, located on Mizpah Church Rd in Winston Salem, NC. Please find below responses to the requested information. NCDWR COMMENTS Contact: Sue Homewood 1) Please clarify if NCDOT or a local government will be assuming responsibility for the proposed roads. If either entity will be assuming future maintenance of the roads, please provide confirmation that they have reviewed the bottomless culvert design and will accept the roadway as designed. —> The City of Winston-Salem will own and maintain the internal subdivision streets. Documentation is provided with this letter that shows Winston-Salem will accept the BridgeCor product if it meets NCDOT standards. —> NCDOT is currently reviewing the BridgeCor product to ensure it meets their standards; documentation will be provided as soon as it is available. 2) Based on the Divisions previous experience with these structures, the shading that will occur under the proposed bottomless culvert will lead to the die -off of woody vegetation which provides the structure that keeps the stream banks intact. Erosion of stream banks then occurs leading to sediment loading in the stream, over -widening of the channel, and reductions in habitat heterogeneity will subsequently occur. Such reductions in stream function are considered as indirect impacts / losses of existing uses of the stream channel, and therefore justify compensatory mitigation pursuant to 15A NCAC 02H .0506(c). Please provide a stream mitigation plan for the total perennial stream losses from both direct and indirect impacts within the entire proposed project. —> While the total impacts for the project exceed 300 LF, the two culvert impacts only total 289 LF. The remaining impacts include riprap that will be installed flush with the existing stream channel temporary coffer dams used for installation. As noted in the response to comment #3, the riprap apron for the bottomless arch culvert has been shifted under the arch for stability. There is no anticipated functional loss of stream channel and the total impacts of the two culverts is less than 300 LF, therefore no stream mitigation shall be required. www.eagleonline.net 2013-A Van Buren Avenue Indian Trail, NC 28079 Ph 704 882 4222 Fax 866 775 0329 3) Please explain why a riprap apron is required in the stream downstream of the bottomless culvert. This would indicate that the culvert is expected to increase the velocity within the stream channel. As noted above, any functional loss to the stream channel as a result of installation of the bottomless culvert would be considered to be indirect and cumulative impacts and should be accounted as such in the application. - The riprap apron placed downstream of the bottomless culvert has been moved underneath the culvert arch for stability. The apron will be installed flush with the existing grade and will not result in functional loss of stream channel. There is no expected increase in velocity within the stream. 4) Please explain why Culvert #2 is not proposed to be buried within the stream channel. - Culvert #2 has been revised to a 72" pipe buried 1' below existing channel grade. 5) It appears that Wetland Impacts #3 and #4 could be completely avoided with a minor adjustment to the plans to shorten the road and remove lots 41 and 42, or to use retaining walls to minimize the fill to these areas. Given the total number of lots proposed for this development, please provide justification as to why the loss of only 2 lots is not practical. - The cul-de-sac has been shortened; two lots were removed & the grading was revised to eliminate the impacts to the two wetland areas (previously designated W-3 & W-4). The total wetland impact has been reduced from 0.484 acres to 0.244 acres. As you have any questions, please do not hesitate to contact our office. Sincerely, Eagle Engineering Inc. /RAA/Lexv Tito rn cq5 Lauren Thomas, PE Senior Project Manager www.eagleonline.net 2013-A Van Buren Avenue Indian Trail, NC 28079 Ph 704 882 4222 Fax 866 775 0329 I MUDDY CREEK \ \\ / / / /,7 ' i / 11 � � / � �// '/ ,/i/ \ / / /')/ / z WL:53 4 s 7i,156SF FEMA FLOOD WAY LIMITS FEMA 100-YR FLOODLINE FEMA 500-YR FLOODLINE WL:46 287SF �\ WL:50 1,019 SF WL:54 363 SF WL:58 70 SF WL:32 350 SF r WL:35 180 Sq 168 167* 166* 165* 164" WL:39 165 SF 170 EX. PROPERTY LINE 172 173 174 292 291 EX. WETLANDS - 176 177 PROP. SCM \(\ WL:59 N6 SF 242" 187* 188* 212 245* 246* • • PROP. • SCM • • • - 29,520SF------ 248* 206 20i" 249* SHEET W-1.3 ■ PROP. SCM 252" 253* WL:33 . .14,760 .. SHEET W-1.1 129 128** 126"* - MIZPAH CHURCH RD. PROP. SCM 25 \ PROP. BOTTOMLESS ARCH \ CULVERT W/ HEADWALLS \ — WL: 3 I 1,115 -` S - — \ 23 24 TRIBUTARIES OF MUDDY CREEK PROP. SCM SHEET W-1.2 S-5 trip t‘Ah. S-6 PROP. TRADITIONAL 72" CAP CULVERT W/ HEADWALLS ��... \I119I v-� j STREAM BUFFERS MEASURED FROM TOP OF BANK WL:44 ,355 S - - BOTTOMLESS ARCH CULVERT & HEADWALLS: (W-1A & W-18) WETLANDS IMPACTED = 6,829 SF (0.157 AC) S-1 = 87 LF (348 SF, INCLUDES 15 LF CLASS 1 RIPRAP INSTALLED FLUSH UNDERNEATH BAC) S-2 = 5 LF (20 SF) DOWNSTREAM TEMP. COFFER DAM S-3 = 20 LF (80 SF) UPSTREAM TEMP. COFFER DAM TOTAL = 112 LF (448 SF = 0.010 AC) TRADITIONAL PIPED CULVERT & HEADWALLS: (W-2) WETLANDS IMPACTED = 5,667 SF (0.130 AC) S-4 = 202 LF (303 SF) S-5 = 15 LF (22.5 SF) CLASS 1 RIPRAP APRON S-6 = 5 LF (7.5 SF) DOWNSTREAM TEMP. COFFER DAM S-7 = 15 LF (22.5 SF) UPSTREAM TEMP. COFFER DAM TOTAL = 237 LF (355.5 SF = 0.008 AC) \ 118 117 __ VESTAL RD. EXT. EX. PROPERTY LINE LAKE DR. - - EXISTING STREAM COVERED BY BOTTOMLESS ARCH CULVERT, TO REMAIN UNDISTURBED S-1, 2 & 3 TOTAL = 112 LF / 448 SF (0.010 AC) EXISTING STREAM TO BE IMPACTED BY PIPED CULVERT S-5, 6, 7 & 8 TOTAL = 237 LF / 355.5 SF (0.008 AC) EXISTING WETLANDS TO REMAIN UNDISTURBED - I/ r PROP. SCM It i I 1 1 1 GRAPHIC SCALE VESTAL RD. 09/08/2022 ISSUE ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS WETLAND CONSULTANT COMMENTS ADDRESS DWR COMMENTS I 03 m m DATE N O in 0 07/27/2022 09/08/2022 t'ii ":r Lc) SITE GRADING: (W-3) WETLANDS IMPACTED = 3,780 SF (0.087AC) (REFER TO SHEETS C-3.8 & C-6.7 FOR TEMP. COFFER DAM) EXISTING WETLANDS TO BE IMPACTED W-1 A, W-18, W-2 & W-3 = 10,609 SF (0.244 AC) 0 120' 240' ( IN FEET ) 1 inch = 120 ft. 875 870 865 860 855 850 845 843 -(l+ RIDGE BLUFF DR. WEST WALL PROP. GRADE STA:-0+28.01 ELEV:872.94 STA:0+33.28 ELEV:872.15 IJ-iIIiI_JIII 1 1 1 1 1 11111 I 11 I I I 7.6' WWI RCP 78 RCP 1■iM�����■■■I� RI Illi \ _ 8" SANITARY SEWER 1 1 1 1 1 PROP. \ '4- 1 1 1 1 1 1 1\ 1 I 1 1 1 1 1 I I 1 1� 1 I I I I I Ii ,L I I 1 \ ■ ■■■■■ 21' ■■■•___ -.I I 1 1 1 1 1 1 1 1 1 1 1 1 I IIII 1111 II IIIIII 11 111 11111111111111 IIII ?OP. MODULAR HEADWALL I I I 1 1 1 1 1 1 TO BE DESIGNED BY I I I I 1 1 1 1 1 1 1 STRUCTURAL ENGINEER I I 1 1 1 1 1 1 1 1 II II 11 111111111111 11 11 111111111111 IIII II 111111111111111 IIII 11 111111111111111 1 1 1 I I I I I I I I 1 1 1 1 1 I I I 1 1 1 1 1 1 IIII I 1111111111111111 IIII I IIIIIIIIIIIIIIIII IIII 1111111111111r PROP. BRIDGECOR 1 1 1 1 1 1 1 1 I_ CORRUGATED STEEL I I I STRUCTURAL (DESIGNED PLATE I BY CONTECH) I I I 1 1 1 1 1 1 1 1 1 1 1 IIII I 111111111 1 1 1 1 1 1 1 1 I IIII I 111111111 111111111 IIII I 11111111 IIII I 1 1 111 1111 II 11 11 1111 II I 111111111 II 11 11 1111 II I 111111111 11 I 44'-7" SPAN �111111111111111 1 1 11111L1 11/ T / EXIST. GRADE STA:-0+04.18 ELEV:844.00 890 880 870 860 850 840 830 820 875 870 865 860 855 850 845 843 + i'- -850 LIMITS OF EXIST. WETLANDS 0 PROP. PSDE an inn BW:848.43 TW:855.00 BW:847.51 TW:859.99 PROP. SECURITY FENCE AT TOP OF WALL (OWNER TO SELECT STYLE) BW:847.39 TW:865.00 (W-1A) 2,046 SF WETLANDS TO BE IMPACTED • N \\\' BW:847.82 • \ • 1 TW:871.30 \ 1 \ \ • 2•. CLASS 1 RIPRAP APRON TO BE \ \ , INSTALLED FLUSH W/ EX. GRADE •\ \ UNDERNEATH BOTTOMLESS CULVERT LIMITS OW \\\ \ TW:871.69 EXIST. WETLANDS • H i - r \10-BW:852.10 TW:857.00 (S-2) 5 LF (20 SF) BY DOWNSTREAM TEMPORARY COFFER DAM PROP. HEADWALL TO BE • DESIGNED BY OTHERS BW:850.49, TW:861.61 GRAPHIC SCALE 20' 40' ( IN FEET ) 1 inch = 20 ft. - 42 TW.872.02 BW:847.01 TW:872.13 BW:846.98 (W-1 B) 4,783 SF WETLANDS TO BE IMPACTED 50' PUBLIC RO• W -12 m c EXISTING WETLANDS TO BE IMPACTED W-1A & W-1B = 6,829 SF (0.157 AC) \\ PROP.\ GUARDRAIL . .0: PROP. 8" SANITARY SEWER A 1 1- -1_ 1 1 PROP. 8" WATER LINE PROP. STORM DRAINAGE + i (S-1) 87 LF (348 SF) STREAM COVERED BY BOTTOMLESS CULVERT (4' WIDE STREAM BED TO REMAIN UNDISTUREBD) BW:847.90 TW:871.29 - - EX:844.99 TW:871.65 TW:871.98 BW.851.36 TW:872.12 BW:853.99 6,532 EXISTING STREAM COVERED BY BOTTOMLESS ARCH CULVERT (BAC), TO REMAIN UNDISTURBED (4' BOTTOM WIDTH) S-1 = 87 LF (348 SF, INCLUDES 15 LF CLASS 1 RIPRAP INSTALLED FLUSH UNDERNEATH BAC) S-2 = 5 LF (20 SF) DOWNSTREAM TEMP. COFFER DAM S-3 = 20 LF (80 SF) UPSTREAM TEMP. COFFER DAM TOTAL = 112 LF (448 SF = 0.010 AC) RIDGE BLUFF DR. STREAM CENTERLINE 1 860 PROP. PSDE • le- BW:854.15 TW:857.00 • J BW- :851.00 TW:862.00 ' s • 550' w �X / 846=- /%'._.: ,o�' 0 / �- - I 2.7:1 PROP. HEADWALL TO BE \ I I I DESIGNED BY OTHERS J / • / _i //- EXIST. TRIBUTARY , OF MUDDY CREEK (S-3) 20 LF (80 SF) OF STREAM IMPACTED BY UPSTREAM TEMPORARY COFFER DAM BW:856.00 TW:865.00 BW:860.00 N TW:864.11 ' - -1- 875 870 865 860 855 850 845 843 -(l+ PROP. 50' PUBLIC R/W PROP. GRADE TOP OF WALL STA:1+97.11 RIDGE BLUFF DR. CENTERLINE TOP OF WALL - STA:1+24.93 STA:1+61.84 ELEV:872.79 ELEV:871.70 I VM ELEV:871.65 8" SS 18" RCP EXIST. GRADE TOP • OF CULVERT BOTTOMLESS CULVERT & HEADWALLS TO BE DESIGNED BY OTHERS ALONG STREAM CENTERLINE STA:1+19.90 ELEV:844.00 (S-1) 87 LF STREAM (STREAM COVERED BY BOTTOMLESS BED TO REMAIN UNDISTURBED) CULVERT STA:2+02.24 ELEV:845.00 i i i i i i i i i i i I I I I 1 1 1 I I I I I I I I I I I I I 1 1 i i i i i i i i i i i i i i i i RIDGE BLUFF DR. EAST WALL PROP GRADE STA:-0+28.27 IELEV:873.19 STA:0+33.22 ELEV:872.13 11 I I [ 1 1 1ilk ■1 - 1 PROP �- I 1 1 \ - 8„WR ATE L/NE _ ��� I I - pi , own MUlk ......._____ \ \ PROP. 8" SANITARY SEWER \ . -- I---- I F I ____L I I ROp 78"RCP IIII , I I I I __ll - - I I 1 I 11.1: I I I I I I' I III�IIII1iII IIIIIIII i PROP. 24'RCP 11 1 I I I I 1 1 I I I I I I l I I I I I I I I 1 I I - I I 1 I 1 I I 1 I I I I I I I I I I I I 11111 111111�1111I111 1 PROP. MODULAR HEADWA 1 1 1 1 1 1 1 TO BE DESIGNED BY STRUCTURAL ENGINEER 11 I 11 I I I I 1 11 I 11111 I IIIIIIIIIIII II I 1 1 1 1 1 1 1 1 1 1 1 I 11 11 III 111I111111 11111 IIII IIIIIIIIIIIIIIIIIII II II IIIIIIIIIIIIIIIIIIII II II IIIIIIIIIIIIIIIIII111 IIII IIIIIIIIIIIIIIIIII111 II II 1111I11111111111111111 II II IIIIIIIIIIIIIIIIII11111 lII 1111I11111 11111111111111 I Il'N_ IPROP. I BRIDGECOR I I I I I I I I I I I I I CORRUGATED STEEL - STRUCTURAL PLATE I I I 1 1 I I 1 1 I I 1 I I (DESIGNED BY CONTECH) 1 1 1 1 1 I I I 1 1 1 1 I I (I I I I I I I 1 1 1 III 1 111111111IIIIIIIIIIIIIIII III 1 111111111I1111111I111111I III IIIIIIIIIIIIIIIII111111 111 111�1111�1111111�11I"---1 III J,' 11111111I11111 I I I I 1 1 1 1 1 I_l...... S=So�.1- .. -- I _- • - • 44'-7" -• -- SPAN 1 -.-.-.-. 1 1 I 1 1 I• I I I.1 1 . Q�SWir49.27 �.� 11r,_.-.--.-.- Li.4 I �.�.�.�.�.� II I\ EXIST. GRADE -\_ STA:-0+00.00 ELEV:844.99 890 880 870 860 850 840 830 VERTICAL SCALE ( IN FEET ) 1 inch = 20 ft. GRAPHIC SCALE 0 20' 40' 820 ( IN FEET ) 1 inch = 20 ft. VERTICAL SCALE ( IN FEET ) 1 inch = 2 ft. 0 875 870 865 LL 860 855 850 845 843 +(l(I GRAPHIC SCALE 20' 40' ( IN FEET ) 1 inch = 20 ft. 09/08/2022 ISSUE ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS WETLAND CONSULTANT COMMENTS ADDRESS DWR COMMENTS I m m m m DATE N N in 0 07/27/2022 09/08/2022 14' ":} LC) Is, CO- 09 j O ErN • <Cz OJ • cam zzz dog � zzco 0(38 890 885 880 875 870 PROP. MC T STRU 865 863 (1+ VESTAL RD. EXT. NORTH WALL VESTAL RD. CL ELEV:887.97 EXT. 1 SEWER PROP. 8" SANITARY I I 7 - PROP. 24" RCP PROP. 24" RCP EXIST. GRADE \ TW:874.14 PROP. GRADE TW:874.24 I I I I I I I I I I I I I I I I I I I \ I I I I I I I I I I I I t \,I11111 II III�I 111111111� ``ll �I11 11111 11111111111 \1111111111111111111 1 1 1 1 1 1 1 1 1 IIIII III+IIIII/ II 1 11 II 11111 11 I f I 1 1 1 1 72" CORRUGATED )DULAR I 1 I ALUMINUM PIPE (8 GT 0 BE DESIGNEDHEADWALL BY 1 1 I BURIED 1' BELOW EX. CTURAL ENGINEER \ 1 1111 1 STA:0+50.00 EL EV:865.00 890 PROP. 8" WATER LINE 885 880 875 870 UGE) GRADE 865 863 +(JO 2.0: - 8W i sir on ':♦ MIL STREAM BUFFER 50' FROM TOP OF BANK 3,0:1, (S-5) 15 LF (22.5 SF) OF STREAM IMPACTED BY RIPRAP APRON & (S-6) 5 LF (7.5 SF) BY DOWNSTREAM TEMPORARY COFFER DAM BW:868.30 TW:873.42 (S-4) 202 LF (303 SF) OF STREAM IMPACTED BY PROPOSED CULVERT (W-2) 5,667 SF WETLANDS IMPACTED BY PROP. CULVERT PROP. STORM • DRAINAGE PIPE • \ PROP. 8" WATER LINE 120** EXISTING WETLANDS IMPACTED BY PROPOSED TRADITIONAL CULVERT W-2 = 5,667 SF (0.130 AC) EXISTING STREAM IMPACTED BY PROPOSED TRADITIONAL CULVERT (1.5' BOTTOM WIDTH) S-4 = 202 LF (303 SF) S-5 = 15 LF (22.5 SF) CLASS 1 RIPRAP S-6 = 5 LF (7.5 SF) DOWNSTREAM TEMP. COFFER DAM S-7 = 15 LF (22.5 SF) UPSTREAM TEMP. COFFER DAM TOTAL = 237 LF / 355.5 SF (0.008 AC) 900 B W:865.73 TW:873.36 PROP. SECURITY FENCE AT TOP OF WALL (OWNER TO SELECT STYLE) , BUFFER 100' FROM TOP , EXIST. TRIBUTARY • OF MUDDY CREEK • CLASS 1 RIPRAP APRON TO BE INSTALLED FLUSH W/ EX. GRADE I ' ' PROP. HEADWALL TO BE DESIGNED BY OTHERS TW:884.65 EX:867.14 TW:884.77 BW:872.56 \ 30,355 SF 0 VESTAL RD. EXT. CULVERT PROP. GRADE 890 TW:884.60 880 PROP. 50' PUBLIC R/W VESTAL RD. EXT. CL ELEV:888.04 -\ 8" SS- 8" WM-/i° EX:867.00 870 860 24" RCP 110.28' of 72" CAP @ 1.86% 900 890 880 TW:873.25 1- EX:864.97 870 (S-4) 202 LF STREAM IMPACTED BY PROP. CULVERT ti 860 PROP. HEADWALL TO BE DESIGNED BY OTHERS (S-7) 15 LF (22.5 SF) OF STREAM IMPACTED BY TEMPORARY COFFER DAM LIMITS OF EXIST. WETLANDS 0 GRAPHIC SCALE 20' 40' ( IN FEET ) 1 inch = 20 ft. VERTICAL SCALE ( IN FEET ) 1 inch = 20' ft. GRAPHIC SCALE 0 20' 40' 890 885 880 EXIST. 875 870 865 (1+ VESTAL RD. EXT. SOUTH WALL VESTAL RD. EXT. J CL ELEV:887.97 - PROP. GRADE TW:885.37 TW:885.40 PROP. 8" WATER LIA t _I I 1 A� Illi SEWER - PROP. 8" SANITARY U I NMI _ I I PROP. MODULAI I I 1 I I 1 TO BE DESIGNE STRUCTURAL El I 1 1 1 1 1 1 - 1 1 1 1 PROP. 24" RCP 1 1 1 1 1 1 1 1 1 I I I 11 I 1 I I 1 I 1 1 1 1 1 1 1 1 I PROP. 24" RCP I I I I 1 I I I 1 1 1 1 1 1 7 T` 1---� 111I111I111111111111 111 1111111111� 1111111 11 1111111111111111111 I I I 1 I I 1 1 I I i GRADE 1 1 1 1 1 1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 1 1 I I 1 1 I I I S875.5s I1 Q5 w•1 I I _ . _ . , = 1 1 I I I 1 1 I 1 1 1 1111111111111111 111 1 1 II 111111111111111111111 111 11 1 111 1I1I1I11I111 J l �._ .,•,,•,,•WSE=B/2.81 1 ri I-�1T1�- I-1 1 �i 1 QINSE = 871.88 I ► 1 1_ _ . f i 0 WSEI=871.09 1 1 1 . , , , , , •I .-.-._ 1 1111111111 L 1 1 72" CORRUGATED 1 1 ALUMINUM PIPE (8 GAL BURIED 1' BELOW EX. ( STA:0+59.56 ELEV:867.00 VERTICAL SCALE ( IN FEET ) 1 inch = 2 ft. 0 890 885 HEADWALL BY GINEER 880 875 870 GE) RADE 865 +u0 GRAPHIC SCALE 20' 40' ( IN FEET ) 1 inch = 20 ft. 09/08/2022 ISSUE ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS WETLAND CONSULTANT COMMENTS ADDRESS DWR COMMENTS 03 I 03 m m DATE N N Lo 0 07/27/2022 09/08/2022 'ii t Lc) if (S-7) 15 LF COFFER DAM (S-5) 15 LF RIPRAP & (S-6) 5 LF COFFER DAM ( IN FEET ) 1 inch = 20 ft. ( \ -- - 8 40 211 —Aix' \ \. N WL.51 '6` 29,520 SF z, - �11,4amp / amp �/ ow En sWI ,ror0 ®' • 840 — • (W-3) 3,780 SF WETLANDS TO BE IMPACTED sic LIMITS OF EXIST. WETLANDS (TO REMAIN UNDISTURBED) EXIST. TRIBUTARY OF MUDDY CREEK, BOTTOM WIDTH: 4.0' —� 850. / _44- 8111140, • - , • 181 ale -- - 1 ��P �J\O�� 860 i 7 PROP. SCM 4VET DETENTION POND- ftir •'♦ ??? ♦ r 4 \\ \ \ \ — �--, \�\ - �,---\ 1,44 • e,o \\ \\� 0 • • • -8W 8W LIMITS OF EXIST. WETLANDS (TO REMAIN UNDISTURBED) 14,760 SF 8w• 8W 8w \ maw \ imam mom 1 EXISTING WETLANDS TO BE IMPACTED BY SITE GRADING W-3 = 3,780 SF (0.087 AC) GRAPHIC SCALE 0 40' "38 80' ( IN FEET ) 1 inch = 40 ft. 811 • 09/08/2022 ISSUE ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS WETLAND CONSULTANT COMMENTS ADDRESS DWR COMMENTS I m m m DATE N N 0 07/27/2022 09/08/2022 (5 �r Ln N• W0U oz J CC z U W Czz U=O CD EL zz ONE 9.J 09 Iauren.thomas@eagleonline.net From: Matthew Gantt <matthewg@cityofws.org> Sent: Wednesday, August 3, 2022 2:23 PM To: Keith Huff; lauren.thomas@eagleonline.net Cc: 'Matt Kirchner'; 'Jeremy L. Roberts'; 'Haley Hardin'; 'Kayle Schmidt' Subject: RE: [EXTERNAL] Long Creek Village (22-0018) Hi Lauren, Our City Engineer, Robert Prestwood, will accept the use of the :ontech Bridgecc structural steel plate. It will also have to be approved for use by NCDOT. Supporting documentation will need to be provided. As previously noted, we may not issue the driveway permit without final sealed plans for the culverts. Thanks, Matt MENSalvni ONE TEAM Committed to Excellence Matthew E. Gantt, PE 141 Senior Civil Engineer Bryce A. Stuart Municipal Building 101 East First Street Winston-Salem, NC 27101 Office: 336-747-6846 Email: matthewg@cityofws.org All e-mails including attachments sent to and from this address are subject to being released to the media and the public in accordance with the North Carolina Public Records Law. From: Keith Huff <keithh1@cityofws.org> Sent: Wednesday, August 3, 2022 2:05 PM To: lauren.thomas@eagleonline.net Cc: Matthew Gantt <matthewg@cityofws.org>; 'Matt Kirchner' <MKirchner@eagleonline.net>; 'Jeremy L. Roberts' <jroberts@eagleonline.net>; 'Haley Hardin' <haley.hardin@eagleonline.net>; 'Kayle Schmidt' <kayle.schmidt@eagleonline.net> Subject: RE: [EXTERNAL] Long Creek Village (22-0018) Hi Lauren, I am going to speak with the City Engineer about the approval process for this request. Field Operations has purview over the mechanically stabilized slope sections of the code but not this section of the IDS. I will follow up with you ASAP. Thanks, Keith 1 From: lauren.thomas@eagleonline.net <lauren.thomas@eagleonline.net> Sent: Tuesday, August 2, 2022 9:31 AM To: Keith Huff <keithhl@cityofws.org> Cc: Matthew Gantt <matthewg@cityofws.org>;'Matt Kirchner'<MKirchner@eagleonline.net>; 'Jeremy L. Roberts' <jroberts@eagleonline.net>;'Haley Hardin'<haley.hardin@eagleonline.net>;'Kayle Schmidt' <kayle.schmidt@eagleonline.net> Subject: RE: [EXTERNAL] Long Creek Village (22-0018) * * * CAUTION! EXTERNAL SENDER * * * STOP. EVALUATE. VERIFY. Were you expecting this email? Does the content make sense? Can you verify the sender? If the email is suspicious: Do not click links or o . en attachments. Click the Report Message button in Outlook to notify Information Systems. Good morning, Keith, I am requesting another exception for Long Creek Village for the use of a structural steel plate bottomless culvert. Please see the attached letter outlining the request. Thank you, Lauren Thomas, P.E. Eagle Engineering, Inc. Senior Project Manager I Civil Division (704)-893-1262 - Direct (704)-882-4222 - Office lauren.thomas©eagleonline.net 2013 Van Buren Avenue, Suite A Indian Trail, NC 28079 www.eagleonline.net Any attached files are for information use only. Eagle Engineering, Inc. (EEI) assumes no responsibility for the accuracy or the validity of any electronic data. All construction should follow signed and sealed construction documents. The content of this email is the confidential property of EEI and should not be copied, modified, retransmitted, or used for any purpose except with EEI's written authorization. If you are not the intended recipient, please delete all copies and notify us immediately. From: Matthew Gantt <matthewg@cityofws.org> Sent: Monday, August 1, 2022 2:07 PM To: lauren.thomas@eagleonline.net Subject: RE: [EXTERNAL] Long Creek Village (22-0018) Hi Lauren, The use of the structural steel plate would need to be approved by our Stormwater Director, Keith Huff. He may be reached at (336) 747-6962 or at keithhl@cityofws.org. For Engineering, we need to have the completed design submitted in conjunction with the driveway permit drawings. Thanks, Matt 2 litsionSalein ONE TEAM Committed to Excellence Matthew E. Gantt, PE 11) Senior Civil Engineer Bryce A. Stuart Municipal Building 101 East First Street Winston-Salem, NC 27101 Office: 336-747-6846 Email: matthewg@cityofws.org All e-mails including attachments sent to and from this address are subject to being released to the media and the public in accordance with the North Carolina Public Records Law. From: lauren.thomas@eagleonline.net <lauren.thomas@eagleonline.net> Sent: Monday, August 1, 2022 11:08 AM To: Matthew Gantt <matthewg@cityofws.org> Subject: [EXTERNAL] Long Creek Village (22-0018) *** CAUTION! EXTERNAL SENDER *** STOP. EVALUATE. VERIFY. Were you expecting this email? Does the content make sense? Can you verify the sender? If the email is suspicious: Do not click links or o . en attachments. Click the Re . ort Messa e button in Outlook to notif Information S stems. Hey Matt, We are working through the comments for Long Creek Village. Regarding the first comment you provided, the bottomless culvert is proposed as the Contech Bridgecor structural steel plate. Will that be an acceptable product? I see in the IDS manual that all metal pipe should be CAP, but it isn't clear if that applies to the bottomless culvert as well. Contech will design the bottomless culvert, and a third party structural engineer will design the retaining walls at each culvert. Is it ok for us to make a resubmittal of the civil plans to address all other comments, and once we have full design documents for the culvert & walls, we can submit that info for final approval? Thank you, Lauren Thomas, P.E. Eagle Engineering, Inc. Senior Project Manager I Civil Division (704)-893-1262 - Direct (704)-882-4222 - Office lauren.thomas©eagleonline.net 2013 Van Buren Avenue, Suite A Indian Trail, NC 28079 www.eagleonline.net Any attached files are for information use only. Eagle Engineering, Inc. (EEI) assumes no responsibility for the accuracy or the validity of any electronic data. All construction should follow signed and sealed construction documents. The content of this email is the confidential property of EEI and should not be copied, modified, retransmitted, or used for any purpose except with EEI's written authorization. If you are not the intended recipient, please delete all copies and notify us immediately. 3 ../ / / ../ / .../ / / Ai ../ / / / / / / / / / / i✓- / c /•& / / // / / / / / / / / �_- / // // / / / / / - -/ • FINAL GRADE ONCE HEADWALL IS INSTALLED (TOP ELEV = 872) s • PROP. SANDBAG COFFERDAMS TO PREVENT BACKFLOW DOWNSTREAM OF CULVERT PROP. SILT BAG / FOR DEWATERING WORK AREA _/' PROP. WORK AREA DEWATERING PUMP /, / / / / / // // /' / / -/ /-,-'*--- .„....- ..// / PROP. TIMBER MAT FOR INITIAL STREAM & WETLAND CROSSING, TYP. (REF. DETAIL ON C-6.7) �jQ-Q�Q�C DO'® • SILT FENCE, TYP. (NCDEQ STD. 6.62) ROCK FILTER BERM, TYP. (NCDEQ STD. 6.55) USE STAPLES AS NEEDED TO SECURE HOSE IN PLACE PROP. FLEXIBLE . PUMP HOSE PROP. WATER PUMP , 4E- PROP. SANDBAG COFFERDAMS TO BLOCK FLOW UPSTREAM OF CULVERT DIRECTION OF EX. STREAM FLOW HIGH HAZARD SILT FENCE / - BELOW WALL W/ STONE OUTLET CONSTRUCTION SEQUENCE FOR DRY CULVERT INSTALLATION: TIMBER MAT INSTALLATION: 1. INSTALL TEMPORARY TIMBER MATS AT STREAM AND WETLAND CROSSINGS AS SHOWN TO PROVIDE CONSTRUCTION EQUIPMENT ACCESS TO THE WORKING AREAS. 2. REFER TO DETAIL & NOTES ON SHEET C-6.7. 3. DISTURBANCE OF THE STREAMS AND WETLAND AREAS SHALL BE MINIMIZED DURING TIMBER MAT INSTALLATION. 4. ORIENTATION OF CROSSING MAY CHANGE IN ORDER TO TIE INTO ACCESS ROAD. CLEAR DISTANCE FROM STREAM TO REMAIN 5+ FEET. 5. MODIFICATION TO CROSSING MAY BE REQUIRED TO ACCOMMODATE LARGER/HEAVIER EQUIPMENT. THE CLEAR DISTANCE FROM STREAM WILL NOT CHANGE. 6. PROPER EROSION CONTROL DEVICES TO PREVENT MATERIAL FROM ENTERING STREAM AND WETLAND AREAS AND TO PROTECT STREAM BANK SHALL BE INSTALLED AND MAINTAINED. COFFERDAM INSTALLATION: 1. INSTALL UPSTREAM SAND BAG COFFER DAMS. LAY THICK MIL POLY SHEETING ALONG THE STREAM BED BEFORE PLACING SANDBAGS. EXCESS PLASTIC SHOULD BE FOLDED OVER THE SAND BAGS IN THE UPSTREAM DIRECTION AND ANOTHER LAYER OF SAND BAGS PLACED ON TOP OF THE PLASTIC TO HELP SEAL THE DAM FROM INFILTRATION. 2. EXTEND PLASTIC ALONG THE STREAM BOTTOM AS FAR UPSTREAM AS PRACTICABLE TO INCREASE THE FLOW LENGTH OF SUBSURFACE FLOW & PREVENT FLOW FROM GOING BENEATH THE SAND BAG COFFERDAM. * NOTE: IF INDUSTRIAL SAND BAGS ARE USED, ADDITIONAL SMALL SAND BAGS MAY BE PLACED IN BETWEEN LARGE SAND BAGS TO HELP SEAL THE WORK AREA. 3. ONCE THE UPSTREAM COFFERDAM IS SECURED, DIVERT UPSTREAM FLOWS AROUND THE COFFERDAM AREA BY USING A BYPASS PUMP. THIS WATER SHOULD BE DISCHARGED DIRECTLY INTO THE STREAM CHANNEL BELOW THE DOWNSTREAM COFFERDAM. AT THE PUMP OUTLET, HIGH VELOCITY (>5 FPS) WATER BEING DISCHARGED BACK INTO THE STREAM HAS THE POTENTIAL TO ERODE THE STREAM SUBSTRATE & CAUSE A TURBIDITY RELEASE. IMPLEMENT SCOUR PREVENTION MEASURES AT THE DISCHARGE SITE TO REDUCE ENERGY AT THE POINT OF DISCHARGE AND PREVENT ELEVATED TURBIDITY LEVELS. 4. INSTALL DOWNSTREAM SAND BAG COFFERDAM IN THE SAME MANNER AS THE UPSTREAM COFFERDAM. THE DOWNSTREAM COFFERDAM ACTS AS A SAFEGUARD AGAINST FAILURE OF THE UPSTREAM COFFERDAM AND TO CONTROL DOWNSTREAM BACKWATER SITUATIONS. 5. ONCE BOTH COFFERDAMS ARE INSTALLED, DEWATER THE AREA BETWEEN THE COFFERDAMS USING A PUMP TO CREATE A "DRY" WORK AREA (SEE NOTES FOR DEWATERING). IF THE WATER IS TURBID FROM DISTURBANCE CAUSED BY THE INSTALLATION OF THE COFFERDAMS, THE WATER SHOULD BE PUMPED TO A TEMPORARY SILT BAG TO ALLOW FILTRATION TO OCCUR. IF THE WATER INSIDE OF THE COFFERDAMS VISUALLY APPEARS TO BE AS TURBID AS THE WATER FLOWING INTO THE UPSTREAM COFFERDAM, IT CAN BE PUMPED DOWNSTREAM OF THE DOWNSTREAM COFFERDAM. 6. COFFERDAMS ARE SUBJECT TO A SMALL DEGREE OF LEAKAGE. A PUMP SHOULD BE PLACED IN THE WORK AREA TO CATCH & EVACUATE ACCUMULATING WATER TO THE TEMPORARY SILT BAG MENTIONED IN STEP 5. STONE SILT FENCE OUTLET, TYP. i 850 DEWATERING: 1. AFTER THE COFFERDAMS ARE INSTALLED, IT IS NECESSARY TO DEWATER THE WORK AREA. THIS WATER SHOULD BE PUMPED INTO A TEMPORARY SILT BAG FOR FILTRATION BEFORE DISCHARGING BELOW THE DOWNSTREAM COFFERDAM AND BACK INTO THE STREAM. 2. A SILT BAG MADE OF FILTER FABRIC SHALL BE USED TO FILTER TURBID WATER. PLACE THE SILT BAG ON 8" OF NO. 5 OR 57 STONE OR ON WOOD PALLETS. USE AN ADEQUATE NUMBER OF PALLETS TO FULLY ELEVATE THE ENTIRE SILT BAG ABOVE NATURAL GROUND. ENSURE THE PUMP PRESSURE DOES NOT EXCEED FILTER MEDIA PRESSURE RATING. 3. THE SILT BAG SHOULD BE LOCATED CLOSE TO THE WORK AREA WITH ADEQUATE VEGETATION BETWEEN IT AND THE STREAM TO PROVIDE ADDITIONAL FILTRATION. (THESE SILT BAGS ARE SHOWN IN PLAN VIEW BUT SHOULD BE PLACED IN THE BEST LOCATION BASED ON FIELD CONDITIONS AT THE CONTRACTORS DISCRETION.) 4. WHEN PUMPING DIRTY WATER TO THE SILT BAGS: • HOSES SHALL BE SET UP BETWEEN THE SILT BAG AND THE WORK AREA PUMP BETWEEN THE COFFERDAMS TO BE DEWATERED. • THE 'DIRTY WATER' PUMP(S) WILL THEN BE STARTED AND THE WATER WILL BE PUMPED TO THE SILT BAG. 6. EVACUATE ANY FISH OR WILDLIFE FROM THE DEWATERED WORK AREA AND PUMP IT DRY AS SOON AS POSSIBLE. 7. IF THERE IS LEAKAGE AROUND THE COFFERDAM OR UPWELLING IN THE WORK AREA, POCKETS WILL BE EXCAVATED IN THE WORK AREA TO COLLECT THE WATER. THIS WATER SHALL BE PUMPED INTO THE SILT BAG FOR FILTRATION PRIOR TO ITS RELEASE BACK INTO THE STREAM. CLEAN CRUSHED STONE SHALL BE PLACED AROUND THE WORK AREA PUMP INTAKE TO FURTHER MINIMIZE SUSPENDED SEDIMENTS FROM BEING PUMPED INTO THE SILT BAG. PROP. SANDBAG COFFERDAMS TO PREVENT BACKFLOW DOWNSTREAM OF CULVERT PROP. SILT BAG FOR DEWATERING - / WORK AREA ./ FINAL GRADE ONCE HEADWALL IS INSTALLED (TOP ELEV = 873) \ / / / / / -r / � / -- / EXIST. WETLANDS , / / / ' / DIRECTION OF EX. / / / / / 1*-404.--.�STREAM FLOW / / / / / / PROP. PUMP OUTFLOW . 110vffirl/ w / -� PROP. 72" CORRUGATED ALUMINUM PIPE CULVERT • // �/, / / ,/, // Yr j- O / DIRECTION OF EX. CULVERT INSTALLATION: 1. ONCE THE COFFERDAMS ARE IN PLACE AND THE WORK AREA IS DRY, CONSTRUCTION OF THE CULVERTS MAY BEGIN. THE BOTTOMLESS CULVERT, PIPED CULVERT & HEADWALLS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. THE SIZE & ELEVATION OF THE REQUIRED FOOTINGS ARE TO BE DESIGNED BY OTHERS. FURTHER DETAIL OF SPECIFIC INSTALLATION INSTRUCTIONS FOR THE CULVERTS AND RETAINING WALLS WILL BE PROVIDED WITH THE DESIGN DOCUMENTS UNDER SEPARATE COVER. 2. AS BACKFILL IS PLACED, SLOPES SHALL BE IMMEDIATELY STABILIZED WITH SEEDING & EROSION CONTROL MATTING. 3. AT THE END OF EACH WORK DAY, SILT FENCE SHALL BE PLACED ALONG THE EDGE OF DISTURBANCE TO DETER SEDIMENT FROM ENTERING THE STREAM. 4. SILT FENCE OUTLET WITH ADDITIONAL HORSESHOE ROCK DAM SHALL BE PLACED AT THE BOTTOM OF SLOPES TO FILTER WATER AS IT EXITS THE DISTURBED AREA. COFFERDAM REMOVAL: 1. AFTER THE BOTTOMLESS CULVERTS ARE INSTALLED, BACKFILL IS PLACED, AND SLOPES ARE STABILIZED, THE COFFERDAMS CAN BE REMOVED TO RESTORE STREAM FLOW THROUGH THE CULVERTS. 2. THE DIVERSION PUMP SYSTEM WILL BE STOPPED AND THE UPSTREAM COFFERDAM SHOULD SLOWLY BE BREACHED. THE FIRST FLUSH OF DIRTY WATER WILL BE CAPTURED BY THE WORK AREA 'DIRTY WATER' PUMP, WHICH WILL THEN PUMP THE WATER INTO THE SILT BAG. 3. WHEN THE WATER BEHIND THE REMAINING INTACT COFFERDAM IS VISUALLY SIMILAR, THAT DAM SHALL BE BREACHED. 4. THE REMAINDER OF THE UPSTREAM COFFERDAM AND THE DIVERSION PUMP SYSTEM SHALL BE REMOVED. SAND BAG COFFERDAMS SHALL BE REMOVED BY HAND. 5. ONCE WATER FLOW IS RESTORED TO THE AREA INSIDE OF THE NEW CULVERT, RESTORATION OF THE CONSTRUCTION SITE SHALL BEGIN. COMPLETE FINAL STABILIZATION TREATMENTS, RESTORATION OF ANY TEMPORARY WORK AREAS, AND REBUILD THE ROADWAY ON TOP OF THE NEW CULVERT. 6. AREAS STEEPER THAN 2H:1 V SHALL BE LINED WITH RIPRAP. ALL OTHER SLOPES SHALL BE VEGETATED WITH SEED MIX THAT ALLOWS FOR RAPID GROWTH AND STABILIZATION AS WELL AS PLANTS THAT HAVE SUBSTANTIAL ROOT SYSTEMS FOR STABILIZATION THAT TAKE LONGER PERIODS TO BE ESTABLISHED. ROCK FILTER BERM, TYP. (NCDEQ STD. 6.55) SILT FENCE, TYP. (NCDEQ STD. 6.62) / - STONE SILT FENCE OUTLET, TYP. I PROP. SANDBAG COFFERDAMS TO BLOCK FLOW UPSTREAM /, y ...... OF CULVERT PROP. TIMBER MAT FOR INITIAL STREAM & WETLAND CROSSING, TYP. (REF. DETAIL ON C-6.7) PROP. WATER PUMP PROP. PUMP INFLOW / / / / / / / / / EROSION CONTROL LEGEND DESCRIPTION SYMBOL ON PLANS POROUS BAFFLES (NCDEQ 6.65) LIMITS OF DISTURBANCE DRAINAGE AREA DELINEATION SILT FENCE (NCDEQ 6.62) TEMPORARY DIVERSION DITCH (NCDEQ 6.20) FLEXIBLE SLOPE DRAIN (NCDEQ 6.32) RIPRAP ROCK CHECK DAM (NCDEQ 6.63) STONE SILT FENCE OUTLET LOD r TD > LOD GRAPHIC SCALE 0 20' 40' ( IN FEET ) 1 inch = 20 ft. \\IIIII/t1/ GI N Eti 1 1 1 1 1, 'bJ/08/2022 ISSUE ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS DWR COMMENTS I m m m m DATE N CV 0 N CV N CO 09/08/2022 (' (0 N. LONG CREEK VILLAGE BHR LAND HOLDINGS, LLC 4389 INDIAN TRAIL FAIRVIEW RD INDIAN TRAIL, NC 28079 ( C-3.8 Sheet 11/4 a03 ONIMVUa MIVaNVIS HSI1DN3 SHEET 1 OF 1 1607.01 / / / / / CLASS "A" STONE 8 IN. MIN. DEPTH SO NOTES: 1. PROVIDE TURNING RADIUS SUFFICIENT TO ACCOMMODATE LARGE TRUCKS 2. LOCATE ENTRANCE(S) TO PROVIDE FOR UTILIZATION BY ALL CONSTRUCTION VEHICLES. 3. MUST BE MAINTAINED IN A CONDITION WHICH WILL PREVENT TRACKING OR DIRECT FLOW OF MUD ONTO STREETS. PERIODIC TOPDRESSING WITH STONE WILL BE NECESSARY. 4. ANY MATERIAL TRACKED ONTO THE ROADWAY MUST BE CLEANED UP IMMEDIATELY. 5. LOCATE GRAVEL CONSTRUCTION ENTRANCE AT ALL POINTS OF INGRESS AND EGRESS UNTIL SITE IS STABILIZED. PROVIDE FREQUENT CHECKS OF THE DEVICE AND TIMELY MAINTENANCE. 6. NUMBER AND LOCATION OF CONSTRUCTION ENTRANCES TO BE DETERMINED BY THE ENGINEER. 7. USE CLASS 'A' STONE OR OTHER COARSE AGGREGATE APPROVED BY THE ENGINEER. NOTE: PLACE FILTER FABRIC BENEATH STONE O o Q Q H .:c LI_Ja1--1Z 00co_ cc a U Q o H- c,, 1- 0 -J CC 0000Occ j°c H- 1 0_-1 w - o cc 0 LL ENGLISH STANDARD DRAWING SHEET 1 OF 1 1607.01 Steel post Wire fence 24" e9 8' max. standard strength fabric with wire fence 6' max. extra strength fabric without wire fence 18-24" 8" down & 4" forward along the trench 4 Plastic or wire ties Natural ground Filter fabric Wire fence Filter Steel fabric post • • • • . • '•. • .: • • • 4 • •' ••• min•.• • • • • • • ••. • • • • . •.• • 24" ▪ ...•••• •.• . • • • • • • • • • • •. ••• e .• Figure 6.62a Installation detail of a sediment fence. ••. •• Cross -Section View Backfill trench and compact thoroughly T 8" min Natural ground vpslope- STEEL POST WIRE FENCING (IF APPLICABLE) WOVEN FILTER FABRIC GENERAL NOTES: 4' MAX. -I I 1III-I :III=III=1I1= -1 El 11mmIIj 11 IIE CLASS 1 OR 2 RIP -RAP WITH 4 INCHES OF WASHED STONE ON UPSTREAM FACE I -III -II -1 I -III -I 1 b I 1=11 11=11 I� 11=11 k it 11111 IT 1 1-111 IT 1 1--111 IT I 1--111Trl lEl 1 IE I lE11 IE I lE11 1E 1111111 E _,III-111-111=1 I I -I 11=1 I I -I 11=1 I I-1 1. SEDIMENT FILTER OUTLET SHALL BE 16 INCHES HIGH BUT NO TALLER THAN 18 INCHES. 2. CLASS 1 OR 2 RIP -RAP SHALL BE USED AND COVERED WITH 4 INCHES OF NCDOT #5 OR #57 WASHED STONE ON THE UPSLOPE SIDE. 3. POSTS SHALL BE NO MORE THAN 4 FEET APART. 4. SITE OUTLETS AT ANY POINT SMALL CONCENTRATED FLOWS ARE ANTICIPATED AND AT THE DIRECTION OF THE INSPECTOR. 5. ONE ACRE MAXIMUM DRAINAGE AREA PER OUTLET. CLASS 1 OR 2 RIP -RAP MAINTENANCE NOTES: 1' MIN. STEEL POST WASHED STONE ,,,,/-(NCDOT #5 OR #57) FLOW II II 11-11 11 11 11 n n nIf ' 111111 1. FILTER OUTLETS SHALL BE INSPECTED BY THE FINANCIALLY RESPONSIBLE PARTY OR HIS AGENT IMMEDIATELY AFTER EACH RAINFALL AND AT LEAST DAILY DURING PROLONGED RAINFALL. ANY REPAIRS NEEDED SHALL BE MADE IMMEDIATELY. 2. THE STONE SHALL BE REPLACED PROMPTLY AFTER ANY EVENT THAT HAS CLOGGED OR REMOVED IT. 3. SEDIMENT DEPOSITS SHOULD BE REMOVED WHEN DEPOSITS REACH HALF THE HEIGHT OF THE BARRIER. ANY SEDIMENT DEPOSITS REMAINING IN PLACE AFTER THE SILT FENCE OUTLET IS REMOVED SHALL BE DRESSED TO CONFORM TO THE EXISTING GRADE, PREPARED AND SEEDED. TEMPORARY CONSTRUCTION ENTRANCE PVC End Cap Arm Assembly PERSPECTIVE VIEW PVC Elbow Water Surface 4- "C" Enclosure Water Entry Unit PVC Vent Pipe Schedule 40 PVC Pipe PVC Tee r WPM. PVC End Cap PVC Pipe Z" Holes in Underside Flexible Hose Schedule 40 PVC Pipe limPlori PVC Tee Orifice Plate Bottom Surface END VIEW FRONT VIEW Inlet zone 25% of surface area 5'Crest Width Inflow Structure Ri pra p or Slope Drain Earthen embankment with stabilized side slopes TEMPORARY SILT FENCE First Chamber 25% of surface area e • NCDEQ STD. 6.62 Second Chamber 25% of surface area Outlet zone i Baffles Ili Ofi 111 111 kip I41 4IIIII► 4 Ago 2590 of surface area Skimmer Dewatering Device Emergency Spillway TEMPORARY SILT FENCE OUTLET Drape baffle material over wire strand and secure with plastic ties at posts and on wire every 12" 9 Gauge Min High -.0***iv Tension Wire Strand Shall Be Secured To Post To Support Baffle Material 1=I1=II=II=1I=11 Baffle Material 4' Max. Extend 9 gauge wire to basin side or installT-post to anchor baffle to side of basin and secure to vertical post � 3' MIN * %�ris,stkr'77);? Variable Depth r+ iy �1��A l V�i; = = = _ • = Secure bottom of baffle to ground with 12" staples at 12" maximum spacing. * If the temporary sediment basin will be converted to a permanent stormwater basin of greater depth, the baffle height should be based on the pool depth during use as a temporary sediment basin. Note: Install three (3) coir fiber baffles in basins at drainage outlets with a spacing of 1/4 the basin Iength. Two (2) coir fiber baffles can be installed in the basins less than 20 ft in Iength with a spacing of 1/3 the basin Iength. 11 Gauge Landscaping Staple ,II • • 1 1 Baffle Materia I Steel Post 2'-0" Depth Baffle Material should be secured to the bottom and sides of basin using 12" landscape staples NCDEQ STD. 6.62 NCDEQ STD. 6.64 SKIMMER GRATE EXPANSION RESTRAINT INI■ININININININININININ1 SECTION HOOD NOTES: 1. INLET MAINTENANCE SHALL BE DOCUMENTED IN PROJECT LOG BOOK. 2. FILTER TYPES SHALL BE APPROVED BY THE CITY INSPECTOR PRIOR TO INSTALLATION. 3. FILTER BAGS MAY BE REMOVED WHEN SITE IS STABILIZED AT THE DIRECTION OF THE ENGINEER. 4. FILTER BAGS SHALL BE REMOVED PRIOR TO STREET ACCEPTANCE AND/OR CLOSE OUT OF GRADING PERMIT. 5. FILTER BAGS SHALL BE CLEANED OR REPLACED ON A REGULAR BASIS (NOT BE MORE THAN HALF FULL AT ANY TIME). 6. FILTER BAGS MAY BE INSTALLED IN EXISTING CITY OR NCDOT ROADS AS LONG AS STORM DRAINAGE IS NOT IMPEDED. GRATE 1" REBAR FOR BAG REMOVAL FROM INLET FILTER BAG DUMP LOOPS CATCH BASIN DEFLECTOR REQUIRED WHEN USED ON EXISTING MAINTAINED STREETS. DEFLECTOR SHALL BE PLACED SUCH THAT IT WILL NOT COMPLETELY OBSTRUCT STORM WATER FLOW FROM ENTERING VIA THE CURB OPENING. ENSURE NO MORE THAN 25% OF CURB OPENING IS OBSTRUCTED. OUTLET INSTALLATION WIRE FENCING OF APPLICABLE) WOVEN FILTER FABRIC I11-11-III III111E111E111-1.. _ IIIIII11 I III11 IIII III III III III III III III III III III 111- I1- 1111I-I I I I 11=1 11-1 I 1-1 11-1 11-1 I 11 1 1111E111E1 I 1-111-1 11-111-1 11-111-1 -I I -III .111111 111 111 i 111=III 111411I 11I1 111=1 11=111E1111 11=111. -111-1 111E NCDEQ STD. 6.65 BAFFLE PLACEMENT HARDWARE CLOTH BETWEEN POSTS AND COVERED BY STONE GENERAL NOTES: 1. SEDIMENT FILTER OUTLET AND HARDWARE CLOTH SHALL BE 16 INCHES HIGH BUT NO TALLER THAN 18 INCHES. 2. HARDWARE CLOTH SHALL BE ANCHORED TO THE STEEL POSTS SECURELY USING APPROPRIATE ANCHORS. HARDWARE CLOTH SHALL BE KEYED IN A MINIMUM OF 12 INCHES IN LENGTH AND BACKFILLED PROPERLY AS SHOWN IN ABOVE DETAIL. HARDWARE CLOTH TO BE SAME AS STD. 30.09 (19 GAUGE, 1/4" SPACING). 3. POSTS SHALL BE NO MORE THAN 4 FEET APART. 4. SITE OUTLETS AT ANY POINT SMALL CONCENTRATED FLOWS ARE ANTICIPATED AND AT THE DIRECTION OF THE INSPECTOR. STEEL POST HARDWARE CLOTH WASHED STONE (NCDOT #5 OR #57) FLOW ANCHOR SKIRT; EXCAVATE TRENCH AND COMPACT BACKFILL MAINTENANCE NOTES: 1. FILTER OUTLETS SHALL BE INSPECTED BY THE FINANCIALLY RESPONSIBLE PARTY OR HIS AGENT IMMEDIATELY AFTER EACH RAINFALL AND AT LEAST DAILY DURING PROLONGED RAINFALL. ANY REPAIRS NEEDED SHALL BE MADE IMMEDIATELY. 2. THE STONE SHALL BE REPLACED PROMPTLY AFTER ANY EVENT THAT HAS CLOGGED OR REMOVED IT. 3. SEDIMENT DEPOSITS SHOULD BE REMOVED WHEN DEPOSITS REACH HALF THE HEIGHT OF THE BARRIER. ANY SEDIMENT DEPOSITS REMAINING IN PLACE AFTER THE SILT FENCE OUTLET IS REMOVED SHALL BE DRESSED TO CONFORM TO THE EXISTING GRADE, PREPARED AND SEEDED. DIRECTION OF STREAM FLOW • 5' MIN. -T DIRECTION OF TRAVEL 12' MIN. BAFFLE DETAIL IN SEDIMENT BASIN • RIPRAP ACCESS ROAD PLACED ON EARTH EMBANKMENT & TYPE 4 ENGINEERING FABRIC 4k1'x14' STACKED TIMBER MATS ON RIPRAP BASE W/ TYPE 4 GEOTEXTILE • _L. 5' MIN. 4'x1' (VARIABLE LENGTH) TIMBER MATS W/ TYPE 2 FILTER FABRIC SECURED BELOW TOP OF STREAM BANK NOTES: f 1. TEMPORARY MAT CROSSINGS MAY BE USED AS A TEMPORARY BRIDGE OVER A STREAM OR WETLAND AREA TO ALLOW VEHICLES ACCESS TO THE WORK SITE. MATS SHOULD NOT BE PLACED IN A WAY THAT THEY RESTRICT THE NATURAL FLOW OF THE STREAM. 2. DURING INSTALLATION OF THE TEMPORARY MAT CROSSINGS, LIMIT EXCAVATION TO THE MINIMUM EXTENT REQUIRED TO ALLOW INSTALLATION AND REMOVAL OF THE CROSSING. 3. THE CENTERLINE OF THE CROSSING SHOULD ALIGN WITH THE CENTERLINE OF THE ROADWAY APPROACH ON BOTH SIDES FOR AT LEAST 50 FEET FROM EACH STREAM BANK. A SHORTER DISTANCE MAY BE APPROVED ON SITE -SPECIFIC BASIS IF PHYSICAL CONSTRAINTS PRECLUDE THE 50 FOOT MINIMUM. 4. AFTER CONSTRUCTING THE TEMPORARY CROSSINGS, STABILIZE ALL AREAS DISTURBED DURING INSTALLATION USING RIPRAP, VEGETATION OR OTHER APPROPRIATE MEASURES. 5. MATS SHOULD BE IN GOOD CONDITION TO ENSURE PROPER INSTALLATION, USE AND REMOVAL. 6. OPERATING HEAVY EQUIPMENT IN WETLANDS SHALL BE MINIMIZED, AND SUCH EQUIPMENT OTHER THAN FIXED EQUIPMENT (DRILL RIGS, FIXED CRANES, ETC.) SHALL NOT BE STORED, MAINTAINED, FUELED OR REPAIRED IN WETLANDS UNLESS THE EQUIPMENT IS BROKEN DOWN AND CANNOT BE EASILY REMOVED. 7. WOODY VEGETATION SHALL BE CUT AT OR ABOVE GROUND LEVEL AND NOT UPROOTED IN ORDER TO PREVENT DISRUPTION TO THE WETLAND SOIL STRUCTURE AND TO ALLOW STUMP SPROUTS TO REVEGETATE THE WORK AREA. 8. WHERE FEASIBLE, PLACE MATS IN A LOCATION THAT WOULD MINIMIZE THE AMOUNT NEEDED FOR THE WETLAND CROSSING. 9. MINIMIZE IMPACTS TO STREAM AND WETLAND AREAS DURING INSTALLATION, USE AND REMOVAL. 10. INSTALL ADEQUATE EROSION CONTROLS AT APPROACHES TO MATS TO PROMOTE A SMOOTH TRANSITION TO, AND MINIMIZE SEDIMENT TRACKING ONTO, THE MATS. 11. SELECT DECKING MATERIALS THAT ARE OF SUFFICIENT STRENGTH TO SUPPORT THE ANTICIPATED LOAD. 12. ENSURE COMPONENTS ARE BUTTED TIGHTLY AND FASTENED SECURELY TO PREVENT SOIL TRACKED ONTO THE BRIDGE FROM FALLING INTO THE STREAM/WETLANDS. 13. SECURELY ANCHOR THE BRIDGE AT ONE END USING STEEL CHAIN OR CABLE. ANCHORS MAY INCLUDE LARGE TREES, BOULDERS, OR DRIVEN STEEL ANCHORS. LIMITS OF WETLANDS • • • • MAINTENANCE NOTES: • • • • 16' MIN. L NCDEQ STD. 6.65 . / NOT TO SCALE 1. TEMPORARY MAT CROSSINGS SHOULD BE MONITORED TO ASSURE CORRECT FUNCTIONING OF THE MATS. 2. LOOK FOR ANY DEFECTS OR STRUCTURAL PROBLEMS REGULARLY. 3. MATS WHICH BECOME COVERED WITH SOILS OR CONSTRUCTION DEBRIS SHOULD BE CLEANED AND THE MATERIALS REMOVED AND DISPOSED OF IN AN UPLAND LOCATION. 4. THE MATERIAL SHOULD NOT BE SCRAPED AND SHOVELED INTO THE RESOURCE AREA. 5. MATS WHICH BECOME IMBEDDED MUST BE RESET OR LAYERED TO PREVENT MUD FROM COVERING THEM OR WATER PASSING OVER THEM. REMOVAL NOTES: 1. MATS SHOULD BE REMOVED BY "BACKING" OUT OF THE SITE, REMOVING THEM ONE AT A TIME. ANY RUTTING OR SIGNIFICANT INDENTATIONS IDENTIFIED DURING MAT REMOVAL SHOULD BE REGRADED IMMEDIATELY, TAKING CARE NOT TO COMPACT SOILS. 2. CROSSINGS SHOULD BE INSPECTED FOLLOWING MAT REMOVAL TO DETERMINE THE LEVEL OF RESTORATION REQUIRED. 3. SPECIAL PRECAUTIONS SHOULD BE TAKEN TO PROMPTLY STABILIZE AREAS OF DISTURBED SOIL NEAR WETLANDS AND STREAMS. MATTED AREAS WITHIN WETLANDS SHALL BE RESTORED TO THEIR ORIGINAL CONDITION AND ELEVATION. THIS MAY INVOLVE NATURAL REVEGETATION FROM EXISTING ROOT AND SEED STOCK OF NATIVE PLANT SPECIES. CONDITIONS MAY WARRANT PLANTING AND THE BROADCAST OF A WETLAND SEED MIX OVER THE MATTED AREA TO SUPPLEMENT THE EXISTING SEED AND RESTOCK. SEED MIXES AND VEGETATION SHALL CONTAIN ONLY PLANS SPECIES NATIVE TO THE AREA. THE USE OF MULCH IN WETLANDS SHALL CONSIST OF WEED -FREE MULCH TO MITIGATE THE RISK OF THE SPREAD OF INVASIVE PLANT SPECIES. \\\1111111111, \`\�a � N CA Ro••. /��'%/ Q .•• ,SS .. 2�•oE /O+ti-9, SEAL • _ 04550 '/1/IIIIIII �065/11/2022 ISSUE ADDRESS CITY OF WINSTON-SALEM COMMENTS; ADD PHASE 2 ADDRESS CITY OF WINSTON SALEM COMMENTS ADDRESS CITY OF WINSTON SALEM COMMENTS ♦ m I> I- CO k- CO I- CO DATE 05/06/2021 02/01/2022 N N 0 z Iiii m NI- 0, BHR LAND HOLDINGS, LLC 4389 INDIAN TRAIL FAIRVIEW RD ♦ INDIAN TRAIL, NC 28079 SILT SACK INLET PROTECTION STONE SILT FENCE OUTLET TIMBER MAT CROSSING Sheet C-6. 7