HomeMy WebLinkAboutNCG550227_CEI_20220904EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 N 52 NCG550227 22/08/04 C S31112171819 20
21 66
Inspection Work Days Facility Self-Monitoring Evaluation Rating B1 QA ----------------------Reserved-------------------
N67707172 73 74 75 80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
13 Foxhorn Court
13 Foxhorn Ct
Hendersonville NC 28791
Entry Time/Date Permit Effective Date
Exit Time/Date Permit Expiration Date
11:30AM 22/08/04 19/01/24
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
12:00PM 22/08/04 20/10/31
Name, Address of Responsible Official/Title/Phone and Fax Number
James Vargo,13 Foxhorn Ct Hendersonville NC 28791//828-489-7419/Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenance Effluent/Receiving Waters
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s)Agency/Office/Phone and Fax Numbers Date
Daniel J Boss DWR/ARO WQ/828-296-4658/
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page#1
DocuSign Envelope ID: FB1EED76-DB26-452C-AA69-CE85C7853671
9/7/2022
NPDES yr/mo/day
22/08/04
Inspection Type
C3111218
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On 8/4/2022, I (Daniel Boss) conducted a Compliance Evaluation Inspection of the Single Family
Residence wastewater facility at 13 Foxhorn Court. I met with owner James Vargo for the inspection.
Mr. Vargo was not certain of the location of all the components of his wastewater system. There was
no ponding anywhere on the surface of his yard, so it's unlikely that the sand filter system is failing.
The sand filter system should be located for maintenance purposes.
This system does not have a disinfection unit which is required under General Permit NCG550000
Part I B. Treatment System Requirements. Either a chlorinator, chlorine contact chamber, and
dechlorinator system; or an ultraviolet light disinfection system should be installed to meet this
requirement.
The effluent pipe was located and it was not discharging. However there are two white pvc pipes that
could be the effluent discharge, and it should be determined which pipe is the wastewater discharge
line.
NCG550227 17 (Cont.)
Page#2
DocuSign Envelope ID: FB1EED76-DB26-452C-AA69-CE85C7853671
Permit:NCG550227
Inspection Date:08/04/2022
Owner - Facility:
Inspection Type:
13 Foxhorn Court
Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Mr. Vargo provided a receipt showing the septic tank was pumped on 10/19/22.Comment:
Sand Filters (Low rate)Yes No NA NE
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re-circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re-circulated at a valid ratio? (Approximately 3 to 1)
The sand filter was not located, but there was no ponding in the area between the
septic tank and the discharge pipe.
Comment:
Disinfection-Tablet Yes No NA NE
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Page#3
DocuSign Envelope ID: FB1EED76-DB26-452C-AA69-CE85C7853671
Permit:NCG550227
Inspection Date:08/04/2022
Owner - Facility:
Inspection Type:
13 Foxhorn Court
Compliance Evaluation
Disinfection-Tablet Yes No NA NE
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorination?
There is no disinfection system.Comment:
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
The effluent pipe was not discharging at the time of the inspection.Comment:
Page#4
DocuSign Envelope ID: FB1EED76-DB26-452C-AA69-CE85C7853671