HomeMy WebLinkAboutWQ0020817_AX20 Inspect Rep 13Apr22_20220907AQWA
The clear leader.
AQWA Inc.
2604 Willis Court, Wilson, NC 27896
Phone: 252-243-7693 - Email: aqwatammysanders@gmail.com
Customer Name: Haddock
Address:
Permit No.
Arrival Time
Haddock - 604 Perfect Moment Dr (Lot 33) Durham, NC
11:10AM
Date of Inspection: 4/13/2022
System AX ID: AX-114125
County:
Departure Time
DWQ-Ral
01:10 PM
Inspection and Maintenance Checklist - AX20 (1, 2, or 3) Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank
Tank
At Site Tank 1
Tank 2 Inlet Readings
Sludge Scum
Sludge
1 Inlet Readings
1 Scum 12
Tank 1 Outlet Readings
0 Scum 8
Tank 2 Outlet Readings
Sludge Scum
Sludge
Tank Inspection Questions
Tank 1
Tank 2
Clean Effluent Filter:
Check for Influent or Effluent Blockages:
Inspect Tank/Riser for Leaks:
Cleaned
No Blockage
None Seen
Control Panel Inspection '
Check
Recircular
Pump
Pump Operates In Manual Mode: Yes
Rest
Pumps Recirculation Pump 1
1 Timer Settings
0.4 Dose 19.6
Pump 2 Timer Settings
Rest Dose
Pump 1 - Counters and Elapsed Time Meters
19540 CT 13.7
Pump 2 - Counters and Elapsed Time Meters
ETM CT
ETM
Verify
Conduit Seal: Verified
AX20 Treatment Pod(s) Inspection '
AX Treatment
Pod(S)
PO11PO2
Pod Inspection
Pod 1 mod 2
Pod 4
Inspect for Ponding or Bridging:
Check and Record Squirt Height:
Verify Orifice Position and Assess for Clogging:
Check for Odors:
Clean, Brush, Flush Lateral:
Recheck and Record Squirt Height:
Flush Pod Throroughly:
Inspect and Clean Vents:
None None
3 ft 3 ft
Adjusted Cleaned
None None
Done Done
3 ft 3 ft
Done Done
Cleaned Cleaned
Inspection and Maintenance Checklist - AX20 (1, 2, or 3) Sub Surface or Surface Drip Dispersal
• Recirculation Tank Inspection
Verify Inlet Flow: No Inflow
Sludge
Operating Properly
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 10 Sludge 0 Scum 8
Inspect Tank/Riser for Leakage:
Visually Check RSV and Liquid
Clean Biotube/Pump Vault Filter
Inspect Biotube/Pump Vault Filter
Pull Pump and Clean Screen:
None Seen Verify All Floats Work:
Level: Normal Verify Audible Alarm Works for High Water float:
Works Properly
Cartridge: Cleaned Verify Neat Wrap of Float and Pump Cords:
Checked
Cartridge: Ok Verify Conduit Seal:
Verified
Cleaned Verify No Leaking In Piping or Flex Hoses:
None Seen
Ultraviolet Disinfection Unit Inspection
Does System Have a UV?
How Many UV Disinfectant Units
Yes
Present? UV 1
Disinfect ion
After Disconnecting Power, Clean or Replace Bulb As Needed. Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Field Dosing Tank Inspection
Inspect for Tank/Riser Leakage:
Inspect Liquid: See Notes
None Seen
Sludge
Works Properly
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
Scum Sludge 0 Scum 4
Visually Check Liquid Level:
Verify No Leaks In Piping or Flex
Inspect Pump Intake:
Verify All Floats Work:
Normal Verify Audible Alarm Works for High Water float:
Hoses: None Seen Verify Neat Wrap of Float and Pump Cords:
Verified
Cleaned Delivery Rate at Start Up:
8.5
Operating Properly Verify Conduit Seal:
Verified
Drip Irrigation System Inspection
Areas Mowed and Clear of Obstruction:
Area Free of Ponding or Surface
Curtain Drains, Ditches, Swales
Control Panel Communication
Treated pod for worms. Also discharge
is stuck and not pumping. Customer
will return to replace pump.
Yes
Effluent: Yes
Functioning Properly. Yes
Checked: Panel does not call in. No dial tone
Inspection Notes
pump is not working. Impeller on pump
contacted by main office. Technician
David Parker
Operator Operators Signature