SUBJECT: Compliance Inspection Report
Long Creek WWTP
NPDES WW Permit No. NC0024244
Stanly County
Mr. Ferris:
The North Carolina Division of Water Resources conducted a Compliance Evaluation Inspection
(CEI) of the Long Creek WWTP on August 16, 2022. This inspection was conducted to verify
that the facility is operating in compliance with the conditions and limitations specified in NPDES
WW Permit No. NC0024244 and SOC S19-007. The findings and comments noted during this
inspection are provided in the enclosed copy of the inspection report entitled "Compliance
Inspection Report".
If you should have any questions regarding this inspection, please do not hesitate to contact
Roberto Scheller with the Water Quality Regional Operations Section in the Mooresville Regional
Office at 704-663-1699 or via email at roberto.scheller@ncdenr.gov.
Sincerely,
DocuSigned by:
44+w H P;zpa,.
-F161 FB69A2D84A3...
Andrew Pitner, Acting Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Laserfiche
Bryan Hinson (Water/Wastewater Resource Manager): blhinson@albemarlenc.gov
Brandon Plyler (ORC) email: bplyler@albemarlenc.gov
D_E
NORTH CAROLINA
ow..m�.m or Environmental o�.i�
North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11611 Mail Service Center I Raleigh, North Carolina 27699-1611
919.707.9000
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2
21IIIIII
L
NPDES yr/mo/day Inspection
3 I NC0024244 111 121 22/08/16 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
191S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I2 I 711 1 72 I N I 731 1 74 71
I I J
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Long Creek WWTP
1040 Coble Ave Extension
Albemarle NC 28002
Entry Time/Date
09:41AM 22/08/16
Permit Effective Date
18/12/01
Exit Time/Date
12:26PM 22/08/16
Permit Expiration Date
22/02/28
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Michael J Ferris,PO Box 190 Albemarle NC 280020190/City
Manager/704-984-9410/7049849406 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling Dispo: Facility Site Review Compliance Schedules
Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Roberto Scheller
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
1-DocuSigned by: g�31�2�22
I�vk� �� DWR/MRO WQ/707-235-2204/
"-91 C2A007838943E...
Signature of Man
Andrew Pitn
®a►tsQn@r1F�viewer Agency/Office/Phone and Fax Numbers Date
rA44I4 4/ H P2 !JR/MRO WQ/704-663-1699 Ext.2180/ 9.2.22
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
N C 0024244 111 121 22/08/16
I17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current NPDES Permit #NC0024244 was issued on December 1, 2018 and expired on February
28, 2022. A Permit Renewal application was received by the Division dated September 7, 2021.
Permit is for continue operation and maintainace of a 12.0 MGD wastewater treatment system.
Discharge is via Outfall #001 into Long Creek which is classified as C waters in the Yadkin -Pee Dee
River Basin.
The subject facility is under Special Order by Consent (EMC SOC WQ S19-007) with modified permit
parameters for BOD (Summer/Winter), Ammonia Nitrogen (Summer/Winter), and TSS. Please note
that in accordance with SOC WQ S19-007, Item 2. (d), No later than fifteen (15) calendar days after
any date identified for accomplishment of any activity listed in 2(a), Table of Scheduled Activity, the
City shall submit to the Water Quality Regional Operations Section, Regional Supervisor, written
notice of compliance or noncompliance therewith. Please also note that quarterly progress reports
detailing the work and activities undertaken and completed on the upgrades to the collection system
and WWTP are to be submitted.
Flows for the calendar year 2021 were caculated with a yearly average monthly flow of 4.89 MGD or
40.79% of the 12 MGD permitted flow. Flows for calendar year 2020 were caculated with a yearly
monthly average flow of 6.247 MGD or 52.05% of the 12 MGD permitted flow. The noted reduction of
percent flow may be attritubed to reduced yearly average rainfall during 2021. The average rainfall
for the Albemarle area is reported at 48.3 to 47 inches per year. Total rainfall for 2021 was reported
at 35.67 inches.
Enclosed with this report are copies of 12-month calculated averages for permit parameters. Also
attached are graphs of the 12-month averages for BOD (Inf), BOD (Eff), TSS, NH3 as N, Flow, and
Fecal Coliform. It was noted that effluent BOD and NH3 as N reflect affect of high flows. The influent
BOD graph shows reverse affect of high Flows indicating a reduction in influent BOD by dilution.
Compliance history for the 12-month period, July 2021 through June 2022, was reviewed with the
following reported violations:
08-2021
09-2021
10-2021
11-2021
12-2021
01-2022
SP-2021-00
SP-2021-0011
SP-2021-0015
SP-2022-0001
SP-2022-0004
SP-2022-0005
Exceeded Monthly Average - TSS
Exceeded Weekly/Monthly Average - TSS
Exceeded Weekly/Monthly Average - TSS
Exceeded Weekly/Monthly Average - TSS
Exceeded Weekly Average - TSS
Exceeded Monthly Average - TSS
At time of inspection records and required information appeared to be well kept and readily available
for review.
Page# 2
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new MODE
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The current permmit became effective on December 1, 2018 and expired on February
28. 2022.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Annual Report on line.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
El El El El
• ❑ ❑ ❑
▪ El El El
❑ ❑ • ❑
Operations & Maintenance Yes No NA NE
Page# 3
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ▪ ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Compliance Schedules
Is there a compliance schedule for this facility?
Is the facility compliant with the permit and conditions for the review period?
Comment: Facility under SOC S19-007.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Contract lab. Environment 1 Inc. and Field Lab Certification #5648.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
•
Page# 4
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Grit Removal Yes No NA NE
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: At time of inspection influent sampler was recorded at 2 degrees C.
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? • ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? ❑ ❑ El •
Is SCADA telemetry available and operational? ❑ ❑ • ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ •
Comment: Influent pump station consist of 4 screw lift pumps.
Standby Power Yes No NA NE
Page# 5
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Are all pumps present? • ❑ El El
Are all pumps operable? • El El El
Are float controls operable? • El ❑ ❑
Is SCADA telemetry available and operational? El El • El
Is audible and visual alarm available and operational? El El El •
Comment: Second lift station consist of 4 screw lift pumps located at secondary treatment.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? • El ❑ ❑
Are surface aerators and mixers operational? • El El El
Are the diffusers operational? El El • El
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ El •
Is the DO level acceptable?(1.0 to 3.0 mg/I) El ❑ ❑ •
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
•
Yes No NA NE
❑ ❑ ❑
Page# 6
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Cross flow
Is the filter media present? • ❑ ❑ ❑
Is the filter surface free of clogging? • ❑ ❑ ❑
Is the filter free of growth? • ❑ ❑ ❑
Is the air scour operational? El El ❑ ❑
Is the scouring acceptable? • El El El
Is the clear well free of excessive solids and filter media? • El ❑ ❑
Comment: Effluent trubid.
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 7
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Disinfection -Gas
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- -
If yes, then when was the RMP last updated?
Comment:
Yes No NA NE
• ❑ ❑ ❑
1000-0012-3092
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ •
Is storage appropriate for cylinders? ❑ ❑ ■ ❑
# Is de -chlorination substance stored away from chlorine containers? • ❑ ❑ ❑
Are the tablets the proper size and type? ❑ ❑ • ❑
Comment: Sodium Bisulfite used for dechlorination.
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
El El El El
Page# 8
Permit: NC0024244
Inspection Date: 08/16/2022
Owner - Facility: Long Creek WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: At time of inspection effluent sampler was recorded @ 5 degrees C.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Comment:
Yes No NA NE
❑ ❑ ❑ ❑
El El El El
El El El El
El El El El
❑ ❑ ❑ ❑
El El El El
El El El El
Page# 9