Loading...
HomeMy WebLinkAboutWQCS00328_Compliance Evaluation Inspection_20220825ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director Mr. Robert Dunham, Town Manager Town of Harrisburg PO Box 100 Harrisburg, NC 28075 NORTH CAROLINA Environmental Quality August 25, 2022 Subject: Compliance Evaluation Inspection Permittee: Town of Harrisburg Wastewater Collection System Permit No. WQCS00328 Cabarrus County Dear Mr. Dunham, Tony Parker and Maria Shutte of the Mooresville Regional Office of the NC Division of Water Resources (DWR or the Division) conducted a compliance evaluation inspection (CEI) of the subject wastewater collection system (WWCS) on August 23, 2022. The assistance provided by Andrew Ulrich and other staff during this inspection is greatly appreciated. A copy of the inspection report is attached for your records and inspection findings are summarized below. Site/System Review The following system components were inspected: a. Four pump station were inspected. No issues noted. b. Numerous man holes were inspected. No issues noted. c. One outfall and 1 aerial were inspected. No issues noted. As you are aware, owners of permitted collection systems must comply with their permit and all rules listed under NC Administrative Code 15A NCAC 02T .0400, et seq. The system's compliance status with each of these rules is summarized below: a. 15A NCAC 02T .0403(a)(1): Requires that the system be effectively maintained and operated at all times to prevent discharge to land or surface waters and any contravention of ground or surface water standards. Observations: The system had SSO's for the review period. These have been addressed previously under separate cover. Compliance Status: Compliant �D_EQ�NORTH CAROLINA o�mm�M mro����l o�.i� North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1601 East Center Avenue, Suite 301 I Mooresville, NC 28115 704.663.1699 b. 15A NCAC 02T .0403(a)(2): Requires that a map of the wastewater collection system be developed and actively maintained. Observations: The Town uses GIS and paper maps. Compliance Status: Compliant c. 15A NCAC 02T .0403(a)(3): Requires that an operation and maintenance (O&M) plan be developed and implemented, which includes inspection frequency, preventative maintenance schedule, and overflow response. Observations Records were available for all activities. Compliance Status: Compliant d. 15A NCAC 02T .0403(a)(4): Requires that the permittee or its representative inspect pump stations that are not connected to a telemetry system (i.e., remote alarm system) every day (i.e., 365 days per year) and pump stations that are connected to a telemetry system at least once per week. Observations: Pump station logs indicate that the pump stations are being inspected as required. Compliance Status: Compliant e. 15A NCAC 02T .0403(a)(5): Requires that the permittee or its representative inspect high -priority sewers (HPS - as defined in 15A NCAC 02T .0402(2)) at least once every six months and document the inspections. Observations: All high priority lines were inspected and documented as required. Compliance Status: Compliant f. 15A NCAC 02T .0403(a)(6): Requires that the permittee or its representative conduct a general observation of the entire wastewater collection system at least once per year and document same. g- Compliance Status: Compliant. 15A NCAC 02T .0403(a)(7): Requires that overflows and bypasses from the system be reported to the Division's Mooresville Regional Office in accordance with 15A NCAC 02B .0506(a), and that public notice must be provided as required by G.S. 143-215.1C. 1:)..E Q?) NORTH CAROLINA nepnrhrerrt of Environmental Ouolny North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1601 East Center Avenue, Suite 301 I Mooresville, NC 28115 704.663.1699 Observations: SSO's have been reported with this system for this review period and have been previously addressed. The NC regulations and statutes, which cover the reporting requirements for SSOs, are found in NC Administrative Code 15A NCAC 02B .0506(a) and NC General Statute 143-215.1C, respectively. You may access the NC regulations online at the NC Office of Administrative Hearings (OAH) website at: http://www.oah.state.nc.us/rules/ and the NC General Statutes online at the NC General Assembly's website at: http://www.ncga.state.nc.us/gascripts/Statutes/StatutesTOC.pl. You may wish to review them to ensure you are fully familiar with all requirements. When reporting SSOs to DWQ, you must call the Mooresville Regional Office (MRO) at 704-663-1699 during normal business hours. If outside normal business hours, you must report the spill to the NC Division of Emergency Management at 1-800-858-0368. Please note that all reportable SSOs must be reported within 24 hours of the occurrence, or first knowledge, of the SSO. Please also note that voice mail or faxed messages are not considered as the initial verbal report. You must talk to and report the spill to a live person. Compliance Status: Compliant h. 15A NCAC 02T .0403(a)(8): Requires that a grease control program be developed and implemented as follows: J. 1. For publicly owned collection systems, the Grease Control Program shall include at least bi-annual distribution of grease education materials to users. 2. Grease education materials shall be distributed more often than required above if necessary to prevent grease -related sanitary sewer overflows. Observations: Educational info is provided as required. Compliance Status: Compliant. 15A NCAC 02T .0403(a)(9): Requires that right-of-ways (ROW) and easements be maintained to allow for personnel and equipment accessibility. Observations: Lines and R/W's were well maintained. Compliance Status: Compliant. 15A NCAC 02T .0403(a)(10): Requires that documentation be kept for all activities you undertake to comply with the requirements of 15A NCAC 02T .0403, subparagraphs (a)(1) through (a)(9), for a minimum of three years, with the exception of the map, which shall be maintained for the life of the system. Observations: Records were reviewed for all activities. D_E Q?) NORTH CAROLINA nepnrhrerrt of Environmental Ouolny North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1601 East Center Avenue, Suite 301 I Mooresville, NC 28115 704.663.1699 Compliance Status: Compliant The attached inspection report should be self-explanatory; however, if you have any questions regarding the inspection report or this letter please contact Tony Parker at 704-663-1699 or tony.parker@ncdenr.gov. Attachments: BIMS Inspection Report CC: DWR files (Laserfiche) D_E Q?) NORTH CAROLINA o�mm�Mm .�����I o�.i� kswie/� Sincerely, DocuSigned by: 14,41.1-44/ H P;xs,1.4 F161 FB69A2D84A3... for W. Corey Basinger, Regional Supervisor Mooresville Regional Office Water Quality Regional Operations Section Division of Water Resources, NCDEQ North Carolina Department of Environmental Quality I Division of Water Resources Mooresville Regional Office 1601 East Center Avenue, Suite 301 I Mooresville, NC 28115 704.663.1699 Compliance Inspection Report Permit: WQCS00328 SOC: County: Cabarrus Region: Mooresville Effective: 06/01/18 Effective: Contact Person: Gregory Peifer Directions to Facility: System Classifications: CS2, Primary ORC: Andrew J Ulrich Secondary ORC(s): On -Site Representative(s): Related Permits: Expiration: 05/31/26 Expiration: Title: ORC Owner : Town of Harrisburg Facility: Harrisburg Collection System PO Box 100 Harrisburg NC 280750100 Phone: 704-239-9762 Certification: 1005841 Phone: 704-455-4669 NC0036269 Water and Sewer Authority of Cabarrus County - Rocky River WWTP Inspection Date: 08/23/2022 Primary Inspector: Tony Parker Secondary Inspector(s): Reason for Inspection: Routine Permit Inspection Type: Collection Facility Status: Compliant Question Areas: ▪ Miscellaneous Questions ▪ Capital Improvement Plan ▪ Inspections ▪ Lines Entry Time 09:30AM Exit Time: 01:OOPM Phone: 704-663-1699 Inspection Type: Collection System Inspect Non Sampling system management and operation ❑ Not Compliant (See attachment summary) ▪ General ▪ Map ▪ Spill Response Plan ▪ Manholes ▪ Sewer & FOG Ordinances ▪ Reporting Requirements ▪ Spills ▪ Pump Stations Page 1 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Inspection Summary: Page 2 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine General Is there a properly designated primary ORC and at least one back-up of proper grade? Are logs being reviewed by the system management or owner on a regular basis? # What is that frequency? # Are there any issues being addressed currently or any in the planning stages? Is there a specific pump failure plan available for all pump stations? Does plan indicate if pump parts/new pumps are in spare parts/equipment inventory? Are new/significantly upgraded pump stations equipped with anti -corrosion materials? Does the permittee have a copy of their permit? # Is permit expiring within the next 6 months? If Yes, has the Permittee applied for renewal? Comment: The current permit expires 5/31/2026. Sewer and FOG Ordinances Is Sewer Use Ordinance (SUO) or other Legal Authority available? Does it appear that the Sewer Use Ordinance is enforced? Is there a Grease Control Program that legally requires grease control devices? What is the standard grease trap cleaning requirement in the FOG ordinance? Is Grease Control Program enforced via periodic inspections/records review? Is action taken against violators? # Have satellite systems adopted an equivalent or more stringent ordinance? Is grease/sewer education program documented with req'd customer distribution? # Are other types of education tools used like websites, booths, special meetings, etc? If Yes, what are they? (This can reduce mailing to annual.) The Town conducts mail outs 2/year, do fair booth set ups and provide info on website. Comment: Capital Improvement Plan Has a Capital (CIP) or System Improvement Plan been developed and adopted? Is it designated for wastewater only or does it have a dedicated section? Does CIP cover three to five year period of earmarked improvements? Does CIP include description of project area? Does CIP include description of existing facilities? Does CIP include known deficiencies? Does CIP include forecasted future needs? Comment: The Towns CIP appears to be adequate to meet future needs. Map Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ daily • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ •❑ ❑ ❑ ❑•❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ quarterly • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑•❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE Page 3 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Is there a overall sewer system map? Does the map include: Pipe Type (GS/FM) Pipe sizes Pipe materials (PVC, DIP, etc) Pipe location Flow direction Approximate pipe age Pump station ID, location and capacity # Force main air release valve location & type # Location of satellite connections Is the map being updated for changes/additions within 1 year of activation? Comment: The Town uses GIS and paper maps. Reporting Requirements # Have there been any sewer spills in the past 3 years? If Yes, were they reported to the Division if meeting the reportable criteria? If applicable, is there documentation of press releases and public notices issued? Is an Annual Wastewater Performance Report being filed with the Division, if required? Is the report being made available to all its sewer customers? # How is it being made available? Comment: The Town is not free of spills but are reporting as required. Inspections Are adequate maintenance records maintained? Are pump stations being inspected at the required frequency? # Is at least one complete functionality test conducted weekly per pump station? Is there a system or plan in place to observe the entire system annually? Is the annual inspection documented? # Does the system have any high -priority lines/locations? Are inspections of HPL documented at least every 6 months? Are new lines being added to the HPL list when found or created? Comment: Documentation reveals HPL's are inspected as required. Spill Response Action Plan Is a Spill Response Action Plan available? Is a Spill Response Action Plan available for all personnel? Does the plan include: • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Website Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Page 4 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine 24-hour contact numbers Response time Equipment list and spare parts inventory Access to cleaning equipment Access to construction crews, contractors, and/or engineers Source of emergency funds Site sanitation and cleanup materials Post-overflow/spill assessment Does the Permittee appear to respond within 2 hours of first knowledge of a spill? • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: A spill response plan was available. Spare parts, pumps and equipment are maintained at the public works shop. Spills Is system free of known points of bypass? If No, describe type of bypass and location Are all spills or sewer related issues/complaints documented? # Are there repeated overflows/problems (2 or more in 12 months) at same location? # If Yes, is there a corrective action plan? Comment: Lines/Right-of-Ways/Aerial Lines Please list the Lines/Right of Ways/Aerial Lines Inspected: Leatherwood outfall R/W and aerial. Outfalls were mowed and maintained and documentation was provided for all activities. Are right-of-ways/easements maintained for full width for access by staff/equipment? If No, give details on temporary access: Is maintenance documented? Are gravity sewer cleaning records available? Has at least 10% of lines older than 5 yrs been cleaned annually? Were all areas/lines inspected free of issues? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: Documentation was provided for all activities and the Town had cleaned 10% of their system for the review period. Manholes Please list the Manholes Inspected: Various M/H's inspected with no major issues noted. Are manholes accessible? # Are manhole covers/vents above grade? Are manholes free of visible signs of overflow? Are manholes free of sinkholes and depressions? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page 5 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Are manhole covers present? # Are manholes properly seated? # Are manholes in good condition? # Are inverts in good condition? Is flow unrestricted in manholes? Are manholes free of excessive amounts of grease? Are manholes free of excessive roots? Are manholes free of excessive sand? Are manhole vents screened? Are vents free of submergence? Are manholes free of bypass structures or pipes? Comment: M/H vent pipes were properly screened. Pump Stations Please list the Pump Stations Inspected: Bentley Hill P/S, Leatherwood P/S, Town Center P/S and Kensington P/S. No issues noted. # Number of duplex or larger pump stations in system # Number of vacuum stations in system # Number of simplex pump stations in system # Number of simplex pump stations in system serving more than one building How many pump/vacuum stations have: # Atwo-way "auto polling" communication system (SCADA) installed? # A simple one-way telemetry/communication system (auto -dialer) installed? For pump stations inspected: Are they secure with restricted access? Were they free of by-pass structures/pipes? Were wet wells free of excessive grease/debris? # Do they all have telemetry installed? Is the communication system functional? Is a 24-hour notification sign posted ? Does the sign include: Owner Name? Pump station identifier? # Address? Instructions for notification? 24-hour emergency contact numbers? Are audio and visual alarms present? • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE 14 0 0 0 1 13 • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ •❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page 6 of 7 Permit: WQCS00328 Owner - Facility: Town of Harrisburg Inspection Date: 08/23/2022 Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine Are audio and visual alarms operable? # Is there a backup generator or bypass pump connected? If tested during inspection, did it function properly? Is the back-up system tested at least bi-annually under normal operating conditions? # Does it have a dedicated connection for a portable generator? # Is the owner relying on portable units in the event of a power outage? # If Yes, is there a distribution plan? If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan? The Town relies on dedicated and portable generators for back-up power when necessary. For the 14 P/S's the Town has 7 dedicated and 2 portable generators. Four of the P/S's inspected during this visit had dedicated on -site generators and 3 were fueled by natural gas and 1 by diesel. These units functioned with out issue when tested. # Does Permittee have the approved percentage of replacement simplex pumps? Is recordkeeping of pump station inspection and maintenance program adequate? Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ •❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: Pump stations were well maintained and operated and documentaion was provided for all activities. Page 7 of 7