HomeMy WebLinkAboutNC0089095_Draft Permit_20220823 ROY COOPER1)
Governor
ELIZABETH S.BISER
Secretary
RICHARD E.ROGERS,JR. NORTH CAROLINA
Director Environmental Quality
August 23,2022
Mr.Aubrey Deaver
A&D Water Service, Inc.
P.O. Box 1407
Pisgah Forest,NC 28768-1407
Subject: Draft NPDES Permit NC0089095
High Vista Falls WWTP
Grade II Biological WPCS
Henderson County
Dear Permittee:
The Division has reviewed your request to renew the subject permit.Enclosed with this letter is a copy of the draft
permit for your facility.Please review this draft carefully to ensure your thorough understanding of the
information,conditions,and requirements it contains.
The draft permit includes the following significant changes from the existing permit:
> The text describing electronic data submission requirements has been updated.
The NPDES standard conditions(Parts II,III,and IV)that are a part of the permit are not included in this draft
document(cover,map, and Part I). The conditions are the same as in your current permit except that agency and
division names have been updated. The latest version is available at https://bit.Iy/3k5NFaL and can be viewed
online or downloaded as a PDF file.
With this notification,the Division will solicit public comment on this draft permit by publishing a notice in
newspapers having circulation in the general Henderson County area,per EPA requirements.Please provide
your comments,if any,to me at the address below no later than 30 days after receiving this draft permit.
Following the 30-day public comment period,the Division will review all pertinent comments and take
appropriate action prior to issuing a final permit. If you have questions concerning the draft, please se contact me at
via e-mail at charles.weaver@ncdenr.gov.
S ncerel y,
71/441°- ' / )7'
Environmental Specialist I I
NPDES Compliance and Expedited Permitting
ec: NPDES File[Laserf"iche]
�-y�� North512Nort CarolinahSalisb Depaury Strertmentet o1 f Environmental1611MailService QualiTyCenter i Division
Raleigh of WaterNorthCarolina 27 Resources
, 699-1 61 1
o 1..1; ___ �/ 919.707.9000
Permit NC0089095
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENTAL QUALITY
DIVISION OF WATER RESOURCES
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
(NPDES)
In compliance with the provision of North Carolina General Statute 143-215.1,other lawful standards and
regulations promulgated and adopted by the North Carolina Environmental Management Commission,and the
Federal Water Pollution Control Act, as amended,
A & D Water Service, Inc.
is hereby authorized to discharge wastewater from an outfall located at the
High Vista Falls WWTP
Creasman Hill Road
Mills River
Henderson County
to receiving waters designated as Line Creek within the French Broad River Basin in accordance with effluent
limitations,monitoring requirements,and other conditions set forth in Parts I,II,III,and IV hereof.
This permit shall become effective
This permit and authorization to discharge shall expire at midnight on October 31,2027.
If the permittee intends to continue to discharge at the facility beyond the term of this permit, a renewal
application must be submitted no later than May 4, 2027(180 days before the expiration of this permit).
Signed this day.
g /-7-2
Richardp
ers,Jr.,Director
Division of Water Resources
By Authority of the Environmental Management Commission
Page 1 of 6
Permit NC0089095
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES permits issued to this facility,whether for operation or discharge are hereby revoked. As of
this permit issuance, any previously issued permit bearing this number is no longer effective. Therefore, the
exclusive authority to operate and discharge from this facility arises under the permit conditions, requirements,
terms,and provisions included herein.
A & D Water Service, Inc. is hereby authorized to:
1. Continue to operate the High Vista Falls WWTP, which discharges treated domestic wastewater to
Line Creek. Treatment includes the following components:
> One(1) influent bar screen
> Two (2) influent equalization basins, one 9,000 gallons, one 6,500 gallons, transfer pumps,
blowers
> Five (5) 9,000 gallon aeration basin with blowers
> Flow splitter box
> Two (2) 6,200 gallon rectangular clarifiers with sludge transfer systems
> Two (2)48 ft3 multi-media tertiary filters
> Filter backwash clearwell with pumps
> Two (2) 1,200 gallon chlorine contact chambers with liquid bleach chlorination
> Effluent flow splitter box
> One(1) 500,000 gallon effluent off-spec holding pond
> Dechlorination
> Post aeration
> Effluent flow meter with recorder
> Effluent composite sampler
> Two (2) sludge holding tanks, one 2,300 gallons, one 9,000 gallons
> 100 KW standby generator
> Effluent lift station for conjunctive distribution(option).
This facility is located off Creasman Hill Road in Mills River, in Henderson County.
2. Discharge through Outfall 001 at a specified location (see attached map) into Line Creek, a
waterbody currently classified as C waters within the French Broad River Basin.
3. This facility anticipates continuing to provide treated wastewater for conjunctive use. Conjunctive
use and subsequent non-discharge permitting is administered by the Non-Discharge Permitting
Section.
Page 2 of 6
Permit NC0089095
Part I
Grade II Biological Water Pollution Control System [15A NCAC 08G.0302]
A. (1) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
[15A NCAC 02B .0400 et seq., 02B .0500 et seq.]
Beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge
treated domestic wastewater from Outfall 001. Such discharges shall be limited and monitored 1 by the Permittee
as specified below:
LIMITS MONITORING REQUIREMENTS
EFFLUENT CHARACTERISTICS Monthly Daily Measurement Sample Sample Location
[Parameter Codes] Average Maximum Frequency Type
Flow 0.045 MGD Continuous Recorder Effluent
[50050]
Total Residual Chlorine 2 28 pg/L 2/Week Grab Effluent
[50060]
BOD,5-Day(20 Deg.C) 10.0 mg/L 15.0 mg/L Weekly Composite Effluent
[C0310]
Total Suspended Solids 5.0 mg/L 10.0 mg/L Weekly Composite Effluent
[C0530]
Nitrogen,Ammonia Total(as N) 1.0 mg/L 5.0 mg/L Weekly Composite Effluent
[C0610]
Fecal coliform(geometric mean) 14/100 ml 25/100 ml Weekly Grab Effluent
[31616]
pH >6.0 and<9.0 standard units Weekly Grab Effluent
[00400] — —
Dissolved Oxygen(mg/L) Daily average>5.0 mg/L Weekly Grab Effluent
[00300]
Temperature, °C Weekly Grab Effluent
[00010]
Turbidity, NTU Quarterly Grab Effluent
[00070]
Footnotes:
1. The permittee shall submit discharge monitoring data electronically using the Division's eDMR system [see
A. (2)].
2. The Division shall consider all effluent TRC values reported below 50 µg/L to be in compliance with the
permit. However,the Permittee shall continue to record and submit all values reported by a North Carolina-
certified laboratory(including field certified), even if these values fall below 50 µg/L.
THERE SHALL BE NO DISCHARGE OF FLOATING SOLIDS OR FOAM VISIBLE IN OTHER
THAN TRACE AMOUNTS.
Page 3 of 6
Permit NC0089095
A. (2) ELECTRONIC REPORTING OF DISCHARGE MONITORING REPORTS
[G.S. 143-215.1(b)]
Federal regulations require electronic submittal of all discharge monitoring reports (DMRs) and program
reports. The final NPDES Electronic Reporting Rule was adopted and became effective on December
21, 2015.
NOTE: This special condition supplements or supersedes the following sections within Part II of this
permit(Standard Conditions for NPDES Permits):
• Section B. (11.) Signatory Requirements
• Section D. (2.) Reporting
• Section D. (6.) Records Retention
• Section E. (5.) Monitoring Reports
1. Reporting Requirements [Supersedes Section D. (2.) and Section E. (5.) (a)1
The permittee shall report discharge monitoring data electronically using the NC DWR's Electronic
Discharge Monitoring Report(eDMR) internet application.
Monitoring results obtained during the previous month(s) shall be summarized for each month and
submitted electronically using eDMR. The eDMR system allows permitted facilities to enter
monitoring data and submit DMRs electronically using the internet. The eDMR system may be
accessed at: https://deq.nc.gov/about/divisions/water-resources/edmr.
If a permittee is unable to use the eDMR system due to a demonstrated hardship or due to the facility
being physically located in an area where less than 10 percent of the households have broadband
access,then a temporary waiver from the NPDES electronic reporting requirements may be granted
and discharge monitoring data may be submitted on paper DMR forms (MR 1, 1.1, 2, 3) or
alternative forms approved by the Director. Duplicate signed copies shall be submitted to the
following address:
NC DEQ/Division of Water Resources/Water Quality Permitting Section
ATTENTION: Central Files
1617 Mail Service Center
Raleigh,North Carolina 27699-1617
See "How to Request a Waiver from Electronic Reporting" section below.
Regardless of the submission method, the first DMR is due on the last day of the month following
the issuance of the permit or in the case of a new facility, on the last day of the month following the
commencement of discharge.
Starting on December 21,2025, the permittee must electronically report the following compliance
monitoring data and reports,when applicable:
• Sewer Overflow/Bypass Event Reports;
• Pretreatment Program Annual Reports; and
• Clean Water Act(CWA) Section 316 (b)Annual Reports.
Page 4 of 6
Permit NC0089095
The permittee may seek an electronic reporting waiver from the Division(see"How to Request a
Waiver from Electronic Reporting" section below).
2. Electronic Submissions
In accordance with 40 CFR 122.41(1)(9),the permittee must identify the initial recipient at the time
of each electronic submission. The permittee should use the EPA's website resources to identify the
initial recipient for the electronic submission.
Initial recipient of electronic NPDES information from NPDES-regulated facilities means the entity
(EPA or the state authorized by EPA to implement the NPDES program)that is the designated entity
for receiving electronic NPDES data [see 40 CFR 127.2 (b)].
EPA plans to establish a website that will also link to the appropriate electronic reporting tool for
each type of electronic submission and for each state. Instructions on how to access and use the
appropriate electronic reporting tool will be available as well. Information on EPA's NPDES
Electronic Reporting Rule is found at: https://www.federalregister.gov/documents/2015/10/22/2015-
24954/national-pollutant-discharge-elimination-system-npdes-electronic-reporting-rule
Electronic submissions must start by the dates listed in the "Reporting Requirements" section above.
3. How to Request a Waiver from Electronic Reporting
The permittee may seek a temporary electronic reporting waiver from the Division. To obtain an
electronic reporting waiver, a permittee must first submit an electronic reporting waiver request to
the Division. Requests for temporary electronic reporting waivers must be submitted in writing to
the Division for written approval at least sixty (60) days prior to the date the facility would be
required under this permit to begin submitting monitoring data and reports. The duration of a
temporary waiver shall not exceed 5 years and shall thereupon expire. At such time, monitoring data
and reports shall be submitted electronically to the Division unless the permittee re-applies for and is
granted a new temporary electronic reporting waiver by the Division. Approved electronic reporting
waivers are not transferrable. Only permittees with an approved reporting waiver request may
submit monitoring data and reports on paper to the Division for the period that the approved
reporting waiver request is effective.
Information on eDMR and the application for a temporary electronic reporting waiver are found on
the following web page:
http://deq.nc.gov/about/divisions/water-resources/edmr
4. Signatory Requirements [Supplements Section B. (11.) (b) and Supersedes Section B. (11.) (d)1
All eDMRs submitted to the permit issuing authority shall be signed by a person described in Part II,
Section B. (11.) (a)or by a duly authorized representative of that person as described in Part II,
Section B. (11.) (b). A person, and not a position, must be delegated signatory authority for eDMR
reporting purposes.
For eDMR submissions,the person signing and submitting the DMR must obtain an eDMR user
account and login credentials to access the eDMR system. For more information on North
Page 5 of 6
Permit NC0089095
Carolina's eDMR system, registering for eDMR and obtaining an eDMR user account,please visit
the following web page:
http://deq.nc.gov/about/divisions/water-resources/edmr
Certification. Any person submitting an electronic DMR using the state's eDMR system shall make
the following certification [40 CFR 122.22]. NO OTHER STATEMENTS OF CERTIFICATION
WILL BE ACCEPTED:
"I certify, under penalty of law, that this document and all attachments were prepared under my
direction or supervision in accordance with a system designed to assure that qualified personnel
properly gather and evaluate the information submitted. Based on my inquiry of the person or
persons who manage the system, or those persons directly responsible
sPonsible for gathering the information,
the information submitted is, to the best of my knowledge and belief true, accurate, and complete. I
am aware that there are significant penalties for submitting false information, including the
possibility of fines and imprisonment for knowing violations."
5. Records Retention [Supplements Section D. (6.11
The permittee shall retain records of all Discharge Monitoring Reports, including eDMR
submissions. These records or copies shall be maintained for a period of at least 3 years from the
date of the report. This period may be extended by request of the Director at any time [40 CFR
122.41].
Page 6 of 6
a
r/'
rI : '.� k
f
i
MV
NCH Y 191 w A'
1,t-Wtr,ui Top } t 1
441'4
", x ,( 'T " Sue.; Shojis i
Discharge
yw� T NC0089095
i, .•- �-...
•
' High Vista ~- .1
• Falls WWTP '�,
-, • - / /
•
•
/
iMltitkt htru.iti t .
{
USGS Quad: Skyland, N.C.
Outfall Facility
Latitude: 35° 25' 52.6"N 35° 25' 51.8" N
Longitude: 82° 34' 18.5" W 82° 34' 20.1" W 7
Stream Class: C North Facility Location
Subbasin: 04-03-02 HUC: 06010105 High Vista Falls WWTP NC0089095
Receiving Stream: Line Creek Henderson County