Loading...
HomeMy WebLinkAboutNC0023736_Sewer ExtensionsT TOWN OF SAWMILLS HELENA STREET AREA CDBG SANITARY SEWER PROJECT AMMENDMENT - IDLEWOOD DRIVE AREA PUMP STATION DESIGN CALCULATIONS April 11, 2002 BENJAMIN B. THOMAS, P.E. WEST CONSULTANTS, PLLC MORGANTON, NORTH CAROLINA WEST CONSULTANTS PLLC I. DESIGN FLOW: A. PRESENT FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) B. FUTURE FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) NO. UNIT FLOW (GAUDAY/UNIT) r, 42.E 120 7'0 240 w5 360 0 25 3 a, `o 40 F� 0� 12 120 Y�g0 TOTAL: PEAK: NO. UNIT FLOW (GAUDAY/UNIT) 120 r: 0 240 °300; 360 u r Oj 25 4 Q 3 0 40 py 12 120 TOTAL: PEAK: TOTAL FLOW (GAUDAY) 5,040 16,800 1,800 0 0 23,640 GAUDAY 16.42 GPM 41.04 GPM TOTAL FLOW (GAUDAY) 0 0 108,000 0 0 108,000 GAUDAY 75.00 GPM 187.50 GPM II. SYSTEM CURVES: FORCEMAIN SIZE: 6" SDR21 I.D. = 5.955 INCHES EQUIVALENT LENGTH ='a020 LF LOW WATER ELEVATION=114, MSL HIGH POINT=9 MSL STATIC HEAD= 115 FEET C = 120 1 C = 150 Q f Hf Hs TDH f Hf Hs H VELOCITY GPM FT/100FT FEET FEET FEET IFT1100FT FEET FEET 7FEET FPS 50 0.035 1.75 115.00 116.75 0.023 1.16 115.00 .16 0.58 100 0.125 6.30 115.00 121.30 0.083 4.17 115.00 119.17 1.15 150 0.266 13.34 115.00 128.34 0.176 8.83 115.00 123.83 1.73 200 0.452 22.71 115.00 137.71 0.299 15.03 115.00 130.03 2.30 250 0.683 34.31 115.00 149.31 0.452 22.71 115.00 137.71 2.88 300 0.958 48.07 115.00 163.07 0.634 31.81 115.00 146.81 3.46 MIN. PRESENT PUMPING RATE: 41.04 GPM MIN. FUTURE PUMPING RATE: 187.50 GPM PUMP SELECTIONAIFBANKIVCORSh'543 U '[,5 +C,MPEL DER,$'flpttR"f?11f OPERATING CONDITIONS BASED ON C=120 (SEE ATTACHED CURVES): ONE PUMP ON 200� GPM @�„�37 FT. TDH TWO PUMPS ON 23Q GPM @ �.�1�3 FT. TDH May.14. 2003 i 1 1AM 828-324-4365 iughes Euppy, inc. 3awmule, NC PUMP DATA SHEET Fairbanks Morse Pump, 80 Hz :iarve: 33M404A )esign Point~ Flow: 200 US gpm Mead: 138 It 3uenp: 5430-NONCLOO -1 dbb Size: 4"5433MV (A) Speed: 1770 rpm Dla:11,3125 in Jrnits: Temperature: 104'F Sphere sl?e: 3 In Pressure: 85 psi Power: --- bhp 3pealf►o Speed: Ns: 1505 Nos: 7538 Mmensions: Suction. 4 in Discharge: 4 in Actor; so hP Speed:1900 Frame: 320 SUBMRQR St:andwXPLPROF Enclosure sized tar Max Power on Design Curve — Data Point — Flow: 200 US gpm Head,139 It Eff. 44% Power: 15.8 bhp NPSHr: 1 Oft Design Curve — Shutoff Head: 154 ft Shutoff` dP: 86.8 psi Min Flow. 140 US gpm SEP: 72% OF a 900 US gpm NOL Pwr: 41.7 bhp 1431 US gpm — Max. Curve — Max Pwl': 48.0 bhp a I Soo u3 gpm No.8i84 P H!wput, ,,,�.�� 05/13/03 Seisatiad file: (unfiled) Catalog: FMSUBBO.MPC v2.0 Fluid: Water Temperature. 60 T SO, 1 Viscosity: 1.122 cP Vapor pressure: 0.2668 psis Atm pressure.,14.7 psis NPSHa: --it Piping: System: -- Suction; --- in Discharge: -- in US gpm 200 400 B00 B00 1000 12M 1400 1600 1aco --- PERFORMANCE EVALUATION -- Flow Speed Mead Pump Power NPSHr Motor Motor Hmfyr Cost US GPM rpm ft OAefi bhp It %off kW )kWh 240 1770 138 50 18.6 10 200 1770 13R 44 15.9 .10 i 60 1770 142 37 15.6 10 120 Flow Rats is Out of Range for this. Pump 80 Flow Rate is Out of Range for this Pump --C3 Hu sa ca Se D5430 M&W Submersible Solids -Handling r INS Basic Pump Dimensions 203 TOP VIEW OF PUMP UNIT TOP GUIDE BRACKET DETAIL 29s� if AA DIA. r 1 i t 2 HOLES 6'% t AB GUIDE RAIL 2' SCHEDULE 40 PIPE BY OTHERS I I+ 2 DISCHARGE (8) D F1 - - - OP HG C B 1'A' WIDE 4 SLOTS FOR MOUNTING OF BASE ELBOW CL SUCTION - BOTTOM VIEW OF ELBOW BOTTOM OF SUMP • e • i a CP WL (4) PUMP MOTOR FRAME DISCH A B C D E F1 F2 L W X Y AA AB CP HG, MW OP WL 4' D5432MV 210T 4 10 11% 2% 63/a 4 1 7 31 93/a 9 51/a 3 31A 54s/e 7A 113/a 15 32 4' D5432MV 250T 4 10 113A 23A 63/a 4 1 7 31 93/ 9 51/a 3 31A 58% 7A 113/a 15 7 4' D5433MV 210T 4 10 11% 2% 63A 4 1 7 323/a 10% 93/a 51/a 3 31A 54T/a 7A 12 15 32 4' D5433MV 250T 4 10 113A 2% 63/a 4 1 7 323/a 10% 93/a 51h 3 3% 581A 'A 12 15 37 4' D5433MV 320T 4 10 11% 2% 63/a 4 1 7 323/ 10% 93/a 51/a 3 3% 67% TA 12 15 43 6' D5433MV 210T 6 14 141/z 31/a 8 6 13/a 91/a 39% 123A 111/a 8'/z 3 3% 587A 1 16 20% 36 6' D5433MV 250T 6 14 141/z 31/a 8 6 13/a 91/a 39% 123A 111/a 811 3 31A 62% 1 16 20Ys 41 6' D5433MV 320T 6 14 14'/z 31/a 8 6 1M 9A 39% 12 111/a 8'/z 3 3% 71% 1 16 205A 1 47 NOTES: (1) DISCHARGE FLANGE IS 125# ANSI DRILLING UNLESS NOTED. (2) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. (3) 5400'S AND 540OK-S ARE DIMENSIONALLY IDENTICAL (4) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN OPERATE CONTINUOUSLY AT 'MW' WATER LEVEL (5) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. f (6) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH GROUT OR A SOLE PLATE GROUTED IN PLACE (n NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION PURPOSES UNLESS CERTIFIED. DIMENSIONS SHOWN MAY VARY DUE TO NORMAL MANUFACTURING TOLERANCES. (8) IF RISER PIPE IS NOT SAME SIZE AS THE DISCHARGE ELBOW, AN ECCENTRIC INCREASER MUST BE USED LIMITED TO TWO SIZES LARGER MAXIMUM. Mi UL LISTED CUSTOMER P.O. NO. ® Farbanks Morse Pump JOB NAME TAG NAME BASIC PUMP D5432MV AND D5433MV PULL-UP SUBMERSIBLE FAIRBANKS MORSE MTR PUMP SIZE AND MODEL GPM TDH RPM ROTATION MOTOR HP FRAME PHASE HERTZ VOLTS ENCLOSURE CERRFlED FOR CERNFlED BY DATE oG 543MS009 NO 5 8/1/97 Fairbanks Morse Pump D5430 M&W Submersible Solids -Handling Pumps 230 Setting Plans F2 PLAN VIEW ACCESS COVER SUMP VENT GUIDE RAILS / i 2' SCHEDULE 40 ' / (3" FOR 400 & 440 FRAMES AND 10' PUMPS) PIPE BY OTHERS EFFLUENT PIPE LIFTING CABLE c, a 4 WL(5) i l SUMP I.D. HINGE SIDE ACCESS OPENING POWER CABLE FLOAT CONTROL PUMP SUMP I.D. A B C D E F1 F2 4'D5432MV 60 30 42 11 21 15 10 10 4"D5433MV 60 30 48 .11 24 15 11 11 6'D5433MV 72 36 60 113/4 30 17 13 13 4'D5434MV 66 42 54 13 27 18 13 13 6'D5434MV 96 42 1 76 21 38 1 261/4 18 18 8'D5434SMV(2) 84 40 68 20 34 26'/2 131/2 131/2 8'D5434LMV 3 96 48 72 24 36 30'/2 18 18 4"D5435MV 72 36 60 18 30 22 12 12 B"D5435MV 96 58 86 201/2 43 27 20 20 10'D5435MV 108 68 88 22 44 3035 "" 221/2 5"D5436MV R.T.F. 8"D5436SMV R.T.F. 400 & 440 FRAME PUMPS REQUIRING HEAVY DUTY ELBOWS PUMP SUMP I.D. A B I C I D I E F1 F2 8"D5435MV 108 66 90 122%1 43 1 21 1 21 5'D5436MV R.T.F. 8"D5436LMV R.T.F. l- LIFTING BAIL 0 MW(6) NOTES: (1) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. (n BASES ARE DESIGNED TO HAVE FULL CONTACT WITH (2) FOR USE WITH IMPELLER DESIGN T8131A. GROUT OR A SOLE PLATE GROUTED IN PLACE. (3) FOR USE WITH IMPELLER DESIGNS T8131 D OR TAKC5W. (8) NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION (4) 5400'S AND 5400K'S ARE DIMENSIONALLY IDENTICAL PURPOSES UNLESS CERTIFIED. DIMENSIONS SHOWN MAY (5) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. VARY DUE TO NORMAL MANUFACTURING TOLERANCES. 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN (9) REFER TO BASIC PUMP DIMENSION DRAWING FOR WL AND OPERATE CONTINUOUSLYAT'MW' WATER LEVEL MW DIMENSIONS. (6) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. DUPLEX IN -LINE, D5430MV, SUBMERSIBLE PULL-UP ®FWrban*s Mom P p SINGLE DOOR ACCESS COVER 543Kc-: No 3 °o° Fairbanks Morse Pump 8/1/97 III. WETWELL DESIGN: A. DETERMINE OPERATING VOLUME: T 30n MINUTES (7.5 TO 30) Qddf = 16.42 GPM Q = 200 GPM V = 452.07 GAL. B. SELECT WETWELL DIMENSIONS: DIAMETERT6 FEET WETWELL DEPTH = PRESENT CONDITIONS: OPERATING DEPTH: 2.14 FEET TOP E L E V 1121 00 GROUND1120 50 LOWEST SEWER IN 1115 10 LAG PUMP ON = 1114.52 ALARM = 1114.02 LEAD PUMP ON = 1113.52 PUMPS OFF = 1111.38 BOTTOM = 1107.88 FUTURE: T v 1 MINUTES (7.5 TO 30) Qddf = 75.00 GPM Q = 200 GPM V = 468.75 GAL. 13.12 FEET FUTURE CONDITIONS: OPERATING DEPTH: 2.22 FEET TOP ELEV = 1121.00 GROUND = 1120.50 LOWEST SEWER IN = 1115.10 LAG PUMP ON = 1114.60 ALARM = 1114.10 LEAD PUMP ON = 1113.60 PUMPS OFF = 1111.38 BOTTOM = 1107.88 DEPTH REQUIRED FOR PUMP PROTECTION 35t3 FEET PRESENT CONDITIONS CYCLES PER HOUR: 2.0 FUTURE CONDITIONS CYCLES PER HOUR: 6.0 C. CHECK FLOTATION: 1. BUOYANCY = SUBMERGED VOLUME X 62.4 PCF: WETWELL I.D , FEET WETWELL O.D. 7.00 FEET SUBMERGED DEPTH: 13.28 FEET BUOYANCY: 31,898 LBS. 2. WEIGHT OF WETWELL: TOP = 9.00 INCHES AND 3,876 LBS. RISER = 11.87 FEET @ 1910.00 LBSNF = 22,665 LBS. BOTTOM = 8.00 INCHES AND 3,850 LBS. TOTAL = 30,391 LBS. FACTOR OF SAFETY = 0.95 NO GOOD EXTENDED BASE SLAB IS REQUIRED BASE SLAB EXTENSION = 8.0 INCHES HEIGHT OF SOIL = 12.62 FEET WET SOIL WT.(50PCF) = 10,102 LBS. THEN TOTAL RESISTANCE TO UPLIFT = 40,492 LBS. FACTOR OF SAFETY = 1.27 OK V = T Qddf 1 — Qnddf L V = active volume within the pump station (gallons) T = allowable cycle time between starts (minutes) Qddf = design daily flow to pump station (gallons per minute) Q = pumping rate of a single pump (gallons per minute) WETWELL DATA PER TINDALL CONCRETE G-SERIES DIA.E(FT) O.D. WEIGHTS HEIGHT (INCHES EXTENDED BASE FT) I RISER LBNF) BASE (LB)' TOP (LB) BASE TOP O.D. (FT) 4.0 4.83 915 1375 1242 6 8 5.83 5.0 5.83 1370 2600 2773 8 9 7.17 6.0 7.00 1910 3850 3876 8 9 8.33 7.0 8.17 2207 5240 7625 8 16 9.33 8.0 9.33 2879 6840 8689 8 16 11.00 10.0 11.67 4481 12030 14312 9 16 14.00 * BASED ON BASE AREA X HT X 150 PCF t- c.�, : c` � (N t' ' (L ► 7�raz� 2 C AC-- A-0 �r�J ' - L-0 fi(/- ei L t: 1C- --rc, Y'Vf-'f S (A ffol,) Hle�W SrWcv(_. - ' 77 -7t SCE, -4s c I>o s�f��(� �� �-r (►cal f L� wvz � � ass s� &P6) tN0�.s -TF(C por owo,,p ff 1 V 1 V J 1 \ ` c Q F BEGIN RESURFA' lNG , STANDARDABeSC D;7ex o�. DETAIL D _ J TDETAIL F �. . -Y4- rBAw seo. STASpwMb D:TC" STANDARD sY pITCN l -Y4- POT StQ-/0 -2�0t 3..,., Da z -cS " ,figc ° POTSta. IO+OJAO 2 zo D S /9 18 55J E " h' ` is • �� ri. j `uia° . 7 2rr. sn.. r.e k- ue..a =� QF., PCS1Q. 10+39.74 - n \Rk.; sTA.2<+]5 4- LT. SrA.24+65 -L- LT. Typ: o+ urwr • CLFS£ R' Rir_r_a _ Pl Sto 11+44b9 Mpr"RN7e p6 , ''Ft - - . _ D.6li, DDE- 90 CY+y (+-1.�A, DDE- 7 CY+y S p < 7" 03' S72' (LTl 5 i .tip STA. 2�+as RT. - r _ .' N-71:, DDE- 17 CY+y < .�' 22' 1J2 ea ; "^ ' - DETAL G RIP aAF - 1570N6 L 209b5' j 9 •S: DETAL [ PILTEE FABFJC 25 E ;'. i ` Lei�P.eL� WTCN STANDARD •v' DTCN T 104�• \_ - e .^ R PKSY& 12+49..39 -NtnD .1AFr. - / Sf / + 5.08 - 1 „�y,b S7,C ,•`1 ; \ ^ p•);^ F' p� 6� 1 I b . Y Fr. Nil D • �c� Fr. L-, POTSrQ. -r5- /O+OOAO STA r+ao io STA 2<+aa 1r rr• . STA '& to+ss x Jr. j �?OTSto. -L- 25+52.74^ -2_DDE- . CY+/J 5E b EXISTING 17 " f A \c;.Ass EXIS fil it M - &ruo4 DESIGNED BY: Vh DRAWN BY: CHECKED BY: I UL%-3 'P4q� I,,• -Y6- APPROVED BY: RBVr i({���A'Ia..t�.` i�"101a7 ) I POTSto.10+0OAO = 4 P0TS1o.-L- 30+6'5.75 P1 Sto 29+0 20 !8 53 O5 3' (RTJ REVISED: i NORTH CAROLINA J t F �:t FilD•NF^f'' 1. $ 2'30' 37T R' I DEPARTART T OF . �'• 1;�•••• PCSfQ.10+2856 0 = T 09" 43r \'� TRANSPORTATION , /�/ & 111 Pl Sto 10+99J8 L = 264.85' T = 133.65, DESIGN SERVICES U141T I% PHONE: ( 9.9 )250-4126 U IL TY DNSTRUCTI L- 5925'26.5(RT) , R = 800A�y FAX:I el9)250-4119 PLANS ONLY 0 = 38'Ir499' L =' 132A1 SE < SEE PLAITS �UTiLITI' NC GRID RUNOFF COt�ISTUCTIOf T = 70L WqD 83 =SEE PLA4'$ i,J4 = 150.00' fMo.11*6057 -L- 01 52 56' 04.5- w POTSta. 13+99.34 P/ Stc 33+58.41 CONNECT USING SE - EXISTING c < 10.0'Y 25S' tRTI I 1 D = 13 0 43r NECESSARY FITTINGS �\ D. T G 6 WATER AND SE ER LINES ARE �' o . ��I OTE: T < 70A4 sc PROP. VA--Cl" (4 DIA.) 1v n �, Ic,rtr', N (OWNED BY THE 1TOWN OF S,AWWILLS' S(/a.�g+00 + a� oGNO FILL R < BOOCk7 T f B•- �• / - -LINE91 - �.. �l ` i�tif,LL BE PLACED OR SE a SEE PLAITS SEE OFFSET +g3 +/- 37 FT LT. Z CD `09-CONSTRUCTION,ACTIIITIES ALLOWED �` XISTING 8" A)�D 1i2" WATER1IINEZIS Ol4'I� Q• j0" c' OVER EXISTING `AC WATERLINES RUNOF Y CALDWELL CQUNTY Zit %je > a 1 w \\ LOCATED OR. LEFT OF) PROP. 834 r= 12' PVC WATER PIPE P r� 1 g I - I % °j EXISTING KISSION ROAD�U{�TIL (C900, DR14) g ( i ;� \1 I -/ �-` n n , ( 5 % NEW WATEALINE S IS INST L ED PROP. 20:"-44" COPPER WATER PIPE S o _ _1 + PROP. MH B1 ,(A 'DIA.) r v ( ) +' , AND OPERATIbNAL. STA. 3+18 +-/-!:LINE01 TYPE K / s� x �^ �- �s 5.•r sit uw.FT' r - POP, 11) - 11 1/4° DI BENDS OFFSET38 +/. 30 FT LT. PROP. 76 - 8 PVC WATER 5 /(3) - 22 1/2 DI BENDS 1 J PROP. a56'c ���iP•VC WATER PIPE ��<4 ' � � � R e 0900, DR14) ,v ea �;-�'s� R14) PRDP. 1-) 45° DI BENDS 4.PIPE (C900, D PROP. S2: � `45P.�'"D BENDS J� r � PROP. 2 RDP. _ -it " RAN ' ?� ' c S ;>3 / / , e ) . 45 DI \BENDS , P..e ION COUL`NTG PROP - 1 - -S LIFT STATION EBB FURNITURE, UrL - ' '' •VILLE FURNITURE IND. INC. 113 pG Er X mll PRRppP.TRA,S3�ON NG (PVC TO C)'j 3 PR'F 1040' 6" PVC IAr EP IPE PROP. (1) " E VALVE�AN6 / {C900, DR14)s cS.; cu 6'� c• \VALVE BOX, 200# WP PROP. 50'1544 E{i,Wfl•ER PIPE /•c \ \\ 1 TYPE K �:rt /t \1 PROP. Tv2f_>�Y RANSITION COUPLING BEGIN COA'STf4UCTION .-1 r \ \ -Y4.- T Sio.15,+45A0 PAOR ` �'6" Y. 6" DI TEE 1 f�RO�) - 6" GATE VALVE s-oG y26 i `S °a+ ° �� BOXf200i WP 5a L- D0 �)- _a T1St 5 Z' AOP. (4) - A XIS WATER !2 0 \ �• dB pm x+ •13 _� p E;' FIE WITH BAf FLOK PREVENT s.W ;, PROP. rt CORPO TION STGP �• +20no r,- . r PROP. BN X 11 c SIP', Jom �f / 14 \ PROP, CZ) - RELOC / ;XE,ci - F _"•'.' gyp, ;f11'p 40 \ R'*66-55 \ e �• x HOg7 ` .. / . +1 m `�- y \!.� 2fir •A7m \. 4j, ,S\ v000 4_' :�,, / b 5m. q7 \IOm.53m /0 ' !b Nor OSTURB EU. M T 5725 \ 1 OX =/JJ TRACKS ToO R=- REMOVED i+ J � � EASEMENT R REMO'IAL 60m/ OF SPUR*25m L- _r- PROP. 425' - FILL OR R NOVE { ABANDONED 6" Av PIPE, {if,TER f c� PROP. (1) - 12" X 6r DI TEE PROP. (1) 6" TRARtITION 16 'COUPLING (PVC TO AC)t PROP. (1) - B" GATE tPA4E & VALVE, BOX, 200# WP oLE NOTE: TIE PROP. �V3�TERLINE sH1�r 20 TO EXISTING 6" �b FIREt. d oPOEMFiTION LINE' AT\R/W`% cNE 45 - s _ rt1 -S� � � _ sly RE(M7XLi\ ,.. J 1 Ya V - r- / •((�' t p E; +2500_-YE- -.- I°' PROP /82'F ' PVC �E P za71 ,s t 4� J B',-Py_16 DDRCH -Y6- 1 ADB pjs E�SPADE 1�1 2 PCs3� 19 Imo% �.zeJu �- I�1 DI -L- p uAi✓ � 18 +SQm �_ •t/.lf l/ Y R1G"r OF *um +:m A:' 4RCONA LEA 7h,E +28Jo -L- EXIST. MH "Ai' *ter -L- STA. 0+00 +/- INEPT° OFFSET +54 +/-- 26 FT LT 1d7L 8US RELOCATE iwr ra Sow PROP. 1 ABANDON ' SDR 35: ' VIER' srA s6+oa sr. k-15:, D -s cY+y, E EAD CONSTI UC,TlON sTJ, as+so R . k-2x, E-6 ccy, r f Or' r'- ~� i �A. )'6- P07 �. FIRE PROTECTION _ i SYSTEA G_ PROP. ABANDONED ✓�l�-F),t: ; . \ L Ell QXI-ST.. -i1'f.TERI_Nlid PROP 312' - 6" PVC WATER PIPE r (C900, \ PROP (2) 45° DI BENDS PROP1) -. 6" >; 6" DI TEE _:T -'.RECONNECT E} ITT 'V(AT-R '�' kETER 1"iT�:�4CKFL0'I' PREVENTER PROP. ,(2) - 4/4" CORPORA.TIOA`=STOP PROF. ,(E) - 6" Xk 1, TAY.PING SADDLE 1,V,TCH161NE 1..9 SEE SKEET UC-5 ' FILL OR AC PIPE, LONN)•- 1& _�-A— R. fi•GREENE Po 20 SHED 1S '6lA' D \ 0 w V DRCH " `�' 50 DEruL A f v� 6 c�A'I I I rl _ DATE 1� CONC CGN• TR4�F'M-04LA_ US 321A I JJ 9600 IIJ 13wo CA1Alf. NT.ROAD. i6x 22X � SR 1133 l603 / �2B,7C• 3c07 - � (RELQ:'ATED) •/ 5402 11 3200 26Q7 /�2800 AffSSION ROAD 1�_ q p 32� / - SR 110E - '0 (RELO-ATED) r nea? � 200,' AOT 27°—'J5h? US 321A f-- - 05/07/02 Permit Number WQ0021309 Permit Tracking S3 Program Category Status Project Type Non -discharge Iri review New Project Permit Type Fast Track C /�T/ 6 Version Permit Classification GravitySewer Extension, Pump Statiocnr�, & Individual A 4��-� Pressure Sewer Extensions �J Primary Reviewer Permit Contact Affiliation forrest . westall Permitted Flow Facility Facility Name Helena Street Area CDBG Sanitary fi&lion Address Owner IP MAY - 8 2002 Major/Minor Minor County Caldwell Facility Contact Affiliation Owner Name Owner Type Town of Sawmills Government - Municipal Owner Affiliation Robert Frye 4076 US Hwy 321-A Granite Falls NC 28630 Dates/Events Draft Scheduled Public Orig Issue App Received Initiated Issuance Notice 05/03/02 Regulated Activities I\1" Outf all 'INTULL Issue Effective Expiration Requested/Received Events RO staff report received RO staff report requested Additional information requested Additional information received Waterbody Name Stream Index Number Current Class Subbasin State`of North Carolina (-------- ..... RECEIVED Department of Environment and Natural ResourCW ? R QUALITY SECTION Division of Water Quality FAST -TRACK APPLICATION MAY 3 2002. for GRAVITY SEWERS, PUMP STATIONS, AND FORC (Pressure sewers systems are not to be included as part of this application L�adklQWDISCHARGE PERMITTING THIS FORM MAY BE PHOTOCOPIED FOR USE AS AN ORIGINAL INSTRUCTIONS: Indicate that you have included the following list of required application package items by signing your initials in the space provided next to each item. Failure to submit all required items will lead to additional processing and review time for the permit application. t= Application Form - Submit one original and one copy of the completed and appropriately executed application form. Any changes to this form will result in the application being returned. The Division of Wafer Quality-sDi•vision) will -- only accept application packages that have been fully completed with all applicable items addressed�•c You do-notineed to submit detailed plans and specifications unless you respond NO to item IV.6. and/or item IV! -I !=' iZR Attachment - Submit the completed and properly executed Form WSCA 10/99 for each watershed ] n th1r jbg2 location. o,,4 r O.Application Fee - Submit a check in the amount of $400 made payable to: North Carolina and Natural Resources (NCDENR). rt/a D. Certificates of Public Convenience and Necessity — If the application is being submitted in the name of a privately - owned public utility, submit two copies of the Certificate of Public Convenience and Necessity, which demonstrates that the public utility is authorized to hold the utility franchise for the area to be served by the sewer extension. If a Certificate of Public Convenience and Necessity has not been issued, provide two copies of a letter from the NC Utilities Commission's Public Staff that states that an application for a franchise has been received, that the service area is contiguous to an existing franchised area, and/or that franchise approval is expected. n/a E: Operational Agreements — Submit one original and two copies of a properly executed operational agreement if the sewer extension will be serving residential or commercial lots (e.g., houses, condominiums, townhomes, outparcels, etc.) that will be owned by a homeowners' association or developer. If the applicant is a homeowners' association, use Form HOA 10/99. If the applicant is a developer, use Form DEV 10/99. �g Flow Acceptance Letters — If the owner of the downstream sewers and/or WWTF is different from the applicant, submit two copies of a flow acceptance letter from the owner of the downstream sewers and WWTF. Flow acceptance letters must contain the following minimum information: applicant and project name, amount of flow accepted, and name and permit number of the receiving sewers/WWTF. The flow acceptance must not expire prior to permit issuance and must be dated less than a year prior to the application date. Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific flow acceptance letter. THE COMPLETED APPLICATION PACKAGE, INCLUDING ALL SUPPORTING INFORMATION AND MATERIALS, SHOULD BE SENT.TO THE FOLLOWING ADDRESS: NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF WATER QUALITY NON -DISCHARGE PERMITTING UNIT By U.S. Postal Service: By Courier/Special Delivery: 1617 MAIL SERVICE CENTER - 512 NORTH SALISBURY STREET, SUITE 1219 ' RALEIGH, NORTH CAROLINA 27699-1617 RALEIGH, NORTH CAROLINA 27604 TELEPHONE NUMBER: (919) 733-5083 FACSIMILE NUMBER: (919) 715-6048 For more information, visit our web site at: h2o.ennstate.nc.usIndpu/ FORM: FTA 06/06' Page 1 of 5 „! t Application Number: (to be completed by DWQ) I. GENERAL INFORMATION: -1. Applicant's name (name of the municipality, corporation, individual, etc.): Town of Sawmills 2. Owner's or signing official's name and title (15A NCAC 2H .0206(b)): Robert Frye, Town Manager 3. Name and complete address of applicant: Town of Sawmills 4076 US Highwav 321—A City: Granite Falls State: NC Zip: 28630 Telephone number: ( 828 ) 396-7903 Facsimile number:( 828) 396-8955 4. Project name (name of the subdivision, facility or establishment, etc.): Town of -Sawmills Helena Street Area CDBG Sanitary Sewer Project 5. County where project is located: Caldwell 6. Fee submitted: $ 400.00 (See Instruction C.) 7. Name and complete address of engineering firm: West and Associates, P.A. 405 S. Sterling Street City: Morganton State: NC Zip: 28655 Telephone number: ( 828 ) 433-5661 Facsimile number:( 828) 433-5662 8. Name and affiliation of contact person who can answer questions about --Benjamin-.-B. Thomas,. P.E. MAY - 8 2002 II. PERMIT INFORMATION: 1. Project is: X new; modification bHYAAtsEH UAiITY SEl i I:-; { ASHEVl.I L REGtO>`IA� 2. If this application is being submitted as a result of a .modification to an existing permit, provide: existing permit number n/a and the issuance date 3. Applicant is: X public private If private, units (lots, townhomes, etc.) are: leased (Skip to item III.); sold 0 Z.— z 0 F= w N o III M: 0 W N LU L:J } 4 1 m W W t c� ¢ m L7� G! Q U it COW' <L- = z - — 4. If sold; facilities owned by a: public utility (See Instruction D.); homeowners' association/developer (See'Instruction E.) RMATION ON WASTEWATER: Please provide a one- or two -word description specifying the origin of the wastewater (school, subdivision, hospital, commercial facility, industry, apartments, condominiums, etc:): residences Volume of wastewater generated by this project: - 29,570 gallons per day Explanation of how wastewater flow was determined (15A NCAC 2H .0219(1)): 82 — 3 BR houses @ 120 GPD/BR and a garage w/2 employees @ 25 GPD/employee Nature of wastewater: 100 % Domestic/Commercial; % Industrial; % Other waste - specify: FORM: FTA 06/00 Page 2 of 5 5. If wastewater is industrial in nature: ` a. Level of pretreatment that has been provided to ensure protection of the receiving collection system and wastewater treatment facility: n/a b. If a pretreatment permit is required, has one been issued? n/a, Yes; No. If yes, please attach a copy of the pretreatment permit. If no, provide date application was submitted: IV. DESIGN INFORMATION: 1. Brief project description: 8,167 LF of 8" gravity sewer, 804 LF 4" forcemain, a pump station with standby generator and autodial'er 2. Owner and name of wastewater treatment facility (WWTF) receiving wastewater (See Instruction F.): _ City of Lenoir — Gunpowder Creek 3. WWTF permit number (NC00***** or WQ00*****): NC 0023736 4. List the owner(s) of any intermediate sewers if different from applicant or owner of WWTF (See Instruction F.): n/a 5. Summary of GRAVITY SEWER to be permitted: Diameter (inches) Length (linear feet) 811 8,167:: 6. Does the subject gravity sewer collection system comply with the most recent version of the Gravity Sewer Minimum Design Criteria and 15A NCAC 2H .0200? X Yes; No. If no, please identify criteria and explain: 7. Summary of PUMP STATIONS to be permitted: No. or Name Design. Flow (MGD). Pump Operational Points GPM @_ feet TDH Reliability Option Selected 1 , t, 0.230-, -126 48 standby generator f, FORM: FTA 06/00 Page 3 of 5 8. Summary of FORCE MAIN to be permitted: Diameter (inches) Length (linear feet) 4" 804 9. List any equipment being utilized that is not specifically mentioned elsewhere in the application or as part of the Minimum Design Criteria (e.g., telemetry, hoist, odor control equipment, mechanical bar screens, etc.): the pump station will have an autodial telemetry system, a standby generator, and a concrete pad for the-Town's portable hoist. 10. Do the subject pump stations and force mains comply with the Minimum Design Criteria for the Fast - Track Permitting of Pump Stations and Force Mains document adopted June 1, 20QO and 15A NCAC 2H .0200? X Yes; No. If no, please identify criteria and explain: NOTE: If you responded NO to item IVA and/or item IV.10. above, two (2) copies of detailed plans, specifications, supporting information, and any other materials pertaining to the identified criteria should be submitted with the completed and appropriately executed application form. FORM: FTA 06/00 Page 4 of 5 V. CERTIFICATIONS Professional Engineer's Certification: I, Benjamin B. Thomas attest that this application for Helena Street Area CDBG Sanitary Sewer Project has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000. Although certain portions of this submittal package may have been developed by other professionals, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC General Statutes 143-215.6A and,143-215.613, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. North Carolina Professional Engineer's seal, signature, and date: Ap.pIIicantps Certification; I Robert Frye , attest that this application for Sanitary Sewer Project has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. Note: In accordance with NC General Statutes 143-215.6A and 143-215.613, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signature: —�� �� Date: I RECEIVED i WATER QUALIT`! SECTIC;N MAY - 3 2002 NON -DISCHARGE PERMITTING FORM: FTA 06/00 Page 5 of 5 04/09/2002 16:05 4 Tuesdsy, Apd ft 2002 4.44 PM Chester Wout (828) 43M862 PAGE 02 p.02 State d North Car®lina Department of Enviro ent and Natural Resources Div on Of Water Quality WATERSHED CLASSMdATION ATTACHMENT Any changes made to thb forma will In tho application being retut med.. (THIS FORK mA Y BE PROTOC'OFILD FOR USE AS AN ORIGINAL) 1Pia'TRUCTIONS: 7 To drtermint th® clasetftoation of the wtaUmhW(!) in vbWh the sutdoot p%yeet will ba located, you am roquirod to submit Lhis form. with IWIN I through i voMp1*Wi tt} the opplaprisAA Division of Water Quality Regional Office W atcr Quality Supervisor (see Page: 2 of 2) prlar ia, ii9 vtittiil ofto application for review. At a t ninimwn. you rrui%t include 2n 8,5" by 1 P copy of to ponion ara 7. i"uto USGS Topographic Map that atltows the•surfum waters immediately downslape of tho project You i dfy the IneWon of the project and this closest down$[ope yutfacr waters {waters for w hieh yoan tv reailttlWng ft a ) on the subWttad tars copy. If the facility it loe.nted in the Neuse River Bash also i�tt ude a r of the soil survey rea' f®t p je- on. Ile corresponding non-disehasge oppR aden may atot be inbaAfW WWI tlttis f � as b 6100ro a rcaional ofriec rind inclutiaeal vAtb the ttvbzditdL f1 l7 1. Applirant's name (nano of lid maiaipality, at tiott, hwivlgltial, eto.)t as Town u£ Sawmills ��. _ 2002 �I 2. Narnc and complete add:ery of appiimrmt: Town of SawmiTLa n-- --, _ . _ _ VV 4076 US Highway 32a—A I� 'L ASILLG1t 0f�=' REf�lJA� City: Granite Fells amm NC zip: 28630 Telephone number: (.02L) 396—Z903 pt>ile attl,aber: () 396-8965 3, Project name (nano of the subalvUlm fie d1w of maddb6numt, otm): Town Of 8aWMi J1 Helena Street: Area CDDG Sanitary Setter; Project A. County whorl p7ajwt is Ia mb& C® AkW 1 � � ��- 5. Nmne(s) of Closest surfee wars: Frets=oa_rZ1c 6. River basin(%) in which the pmjmct is It _.. 9AtJ3dM 7. Topoga *e map nuat ad tit Granite FaZ�ig. 6..Nxe. 1970 8.. Narth Carolina Profesaional EngLowla xuL Id tnd dow�aa�aet•t�ns•�, SM. "�. 207n Neese plovidt we with the a e) of to Mks erW , (s), ando�f A `a` rives ba dn(s) where these activities will occur, as idandw an 92 mmkoked =P Noma(s) of surfut: wata> s and fie): Y • SO r Cla niftcadon(s) (as, cstallsW by the ZWC): N12 r'6 # Proposed claulficadon(s} if ttppHuble: /�„V—d River basin buffer rube, if applicable: A)I.# 9lg1tatwre of rnglor.nl--jae t cti pactattmal: / a %'~ RECEIVED FORM: WSCA 10199 hp 1 U2 q WATER QUALITY SECTION • MAY - 3 2002 a NON -DISCHARGE PERMITTING r -. . r 04/16/2002 14:07 8283968955 TOWN OF SAWMILLS ..4 L Y PAGE 02 C" MAt1AciEF JAMES H. HIPP CITY OF LENOIR NORTH CAROLINA Department of Public Works, Wider I1e80ura8e, and Engineering office of Administration: Public VVorks, Watgr Resources, and Engineering Lan: 0. Hagarnan, Jr-, Dlractor Post Office BOX 958 6i8-8 Greer Circle Lenoir, NC 29048 828-767-2100 022-757 2112 (Fax) Lenoir ave net MKiM DAVID W. BARLOW arr GOtN= G. L BERNHARDT T W BROACH S. L BUSS j. E, GEORGE F. H. M00AE H. L. PRICE M. 0. STRAWN April 11, 2002 � ..... Mr. Bob Frye, Town Administrator MAY — 8 Z00 Town of Sawn -ills 2 ' �f% , '�i 4076 >.rs Highway 321-A 1/.. �� 1-i Sawm&, Nortb Carolina 286SO ASHE��Lc�'AurYs�cr- t) -/0�1 J Re: Jaste�rrater Flaw Allocation — CD1:_ G Sanitary Sewer Project o Heleaa Stxee� �FFiC Dear Administrator Frye: l am writing to confLrm that there is adequate capacity at the Gunpowder Wastewater Treatment Plant to accept additional flaw from the Town of Sawrxlalls per the enlisting contractual agreement. We will allocate 29,570 GPD (gallons per day) of wastewater from the project referenced as CDBG Sanhary Sewer Project — Helena Street .Area. if there are additional questions, please contact any office. Sincerely, CTT OF LENOIR s H. Hip City Manager xc: Len D. Hagaman, Jr., Director of Public Works, Water Resources, and Engineering Jl H/1dh POSrOFF= ROX Q58 ° LWCIA. NORTH CAROLINA 25eMS-0958 a (saai �" -FINED to a. rF.R DUALITY SEC -- _ L,( J 1 MAY - 3 2002 00 NON -DISCHARGE PERMITTING WEST,, AND,ASSOCIA ES, P A. ' " 3 Consulting Engineers .. 405 South Sterling "Street°' z . " \ MORGANTON, NORTH CAROLINIX28655 ` � • • j. 'i 4>, . (828) 433=566`1 ,k `4 NCDENR Div. Of Water Quality JOB NUMBER/PHONE o+y30/02 £ Non -Discharge Permitting Unit.o. i. ATrENt*N ' 1617 �Mai1. Seivee :Cuter .. w ' - Raleigh", NE 27,699-1617(. , t• FE6Relena Street Area "CDBG' Sewer. Proj`octg E F Town ° of Sawmills, NC � WE ARE SENDING YOU Attached —Under separate cover via the following items. Shop drawings — Prints — Plans Specifications — Samples Copy of letter — Change order — Other: 2 Fast-1'racx Hppiication r"or uravizy 2 Pump Station Calculations 1 Plan Review Fee $400.00 CAAY - 8 2002 THESE ARE TRANSMITTED as checked below: x For your approval — Approved as submitted — Resubmit For your use — As requested For review and comment FOR BIDS DUE/DATE: REMARKS —Approved as noted Submit Returned for corrections Return Other copies for approval copiesfor distribution corrected prints PRINTS RETURNED AFTER LOAN TO US COPY TO If enclosures are not as noted, please notify us at once. PRODUCT 13127T - SIGNED :3, ! O,,--6IF FOLD AT (>) TO FIT COMPANION 771 DU-O-VUE ENVELOPE. PRINTED IN U.S.A. B • '.,,,,> w �a N a ZD D m� N uD .I TOWN OF SAWMILLS HELENA STREET AREA CDBG SANITARY SEWER PROJECT PUMP STATION CALCULATIONS APRIL, 2002 BENJAMIN B. THOMAS, P.E. WEST AND ASSOCIATES, P.A. MORGANTON, NORTH CAROLINA RECEIVED WATER QUALITY SECTION l M AY - 3 2002 NON -DISCHARGE PERMITTING l Z G? G` L Flo-f = -' 12✓ Z d _ . .." , 1%�, _720. CZ% _,7 G l�.lrl� f oJ.i7 IPZ1 H OF Fos:, c� �,v U wi Q. rtf-ru2 yam - RECEIVED WATER QUALITY SECTION M AY. - 3 2002 j k NON -DISCHARGE PERMITTING i (f) �u i v"I LC-, 6)4- L-F .4 LEI- LL- G:_ '41L Zo N t,95 G, I ; �! i -A , D, —4 e, " 61 p Fe- 2 ,+ l tk � ID,is�oo r r �-�t©q� 7,A8 im r l�� _ �- .� ►� Imo-.. -t-1 L -,E_ F k�R-l5bq:-)KS RECEIVED WATFR QUALITY SECTION M AY - 3 2002 r I NON -DISCHARGE PERMITTING t Pump performance Models 4V/4VX Speed:• .. Discharge: 4* Max- Solids: 3- ■w■■I1nIn,■nz■N!!H or, l•FE Operation is recommended within heavy dashed boundary. ■►ilk■\`■�li�l�■■1\I�to�■■i��\`�■,■■■■■■■■■■■■■■ �211■■CI■■IlliQR 1■a ■■■■■ ■■■■■■■���\\■il\�\■■■�►1�■■■��,■■�■■■■■■■ '■■■■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■ ■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■■ Pump performance is based on clear water (1.0 specific gravity @ 68"F) and pump fluid end (hydraulic) efficiency. Motor data based on 401C ambient temperature. Available Models Motor Electrical Data Service Service NEC Explosion Start Run Factor Run Factor Start Run Code Service Standard Proof HP Volta Phase Amps Amps Amos KW KW KVA KVA Letter Factor 4V30M4-21 4VX30M4-21 3 230 1 101 17.5 21 2.1 2.5 23.2 4.0 J 1.2 4V30M4-03 4VX30M4-03 3 200 3 66.7 15 18 3.5 4.3 23.0 5.0 G 1.2 4V3OM4-23 4VX30M4-23 3 230 3 58 12 14.4 3.5 4.3 23.0 5.0 G 1.2 4V30M4-43 4VX30M4-43 3 460 3 29 6 7.2 3.5 4.3 23.0 5.0 G 1.2 4V30M4-53 4VX30M4-53 3 575 3 21.3 5 6 3.5 4.3 23.0 5.0 G 1.2 4V50M4-21 4VX50M4-21 5 230 1 141 34 41 6.3 7.7 32.4 ' 7.8 H 1.2 4VSOM4-03 4VX50M4-03 5 200. 3 111 21.6 26 5.6 6.9 38.4 7.2 H 1.2 4V50M4-23 4VX50M4-23 5 230 3 96 18 21.6 5.6 6.9 38.4 7.2 H 1.2 4V50M4-43 4VX50M4-43 5 460 3 48 9 10.8 5.6 6.9 38.4 7.2 H 1.2 4V50M4-53 4VX50M4-53 5 575 3 39 7.2 8.6 5.6 6.9 38.4 7.2 H 1.2 4V75M4.03 4VX75M4-03 7.5 200 3 172 32.2 37 8.0 9.9 59.5 11.1 J 1.2 4V75M4-23 4VX75M4-23 7.5 230 3 150 28 32 8.0 9.9 59.7 11.1 J 1.2 4V75M4-43 4VX75M4-43 7.5 460 3 74.8 14 16 8.0 9.9 59.7 11.1 J 1.2 4V75M4-53 4VX75M4-53 7.5 575 3 67.2 11.2 13. 8.0 9.9 66.8 11.1 K 1.2 0M4-03 10 200 3 172 37 37 10.1 10.1 59.5 12.8 G 1.0 0M4-23 10 230 3 150 32 32 59.7 12.8 G 1.0 0M4-43 L 10 460 3 74.8 16 16 10.1 10.1 51.7 12.8 G 1.0 0M4-53 10 575 3 67.2 13 13 10.1 10.1 66.8 12.8 H 1.0 Motor Efficiencies and Power Factor Motor Efficienc % Power Factor % Service Service Factor 100% 75% 50% Factor 100%. 75% 50% HP Phase Load Load Load Load Load Load Load Load 3 1 71 70 67 59 52 51 49 45 3 3 74 73.5 69.5 61.5 73 70.5 62.5 52 5 1 67.5 68 65 56 83 81 73 62.5 5 3 77 77 77 70.5 80 77.5 71 59.5 7.5 3 75 75 72.5 65 77 72 62 49.5 10 3 75 75 75 71 79 79 72 58 AIL-® F. E. Myers, 1101 Myers Parkway, Ashland, Ohio 44805-1969 K3616 3/95 AWALVWD 419/289-1144 • FAX: 419/289-6658 • TLX: 98-7443 Printed in U.S.A. 5) l� 2f rQAM' � K�C U.c= T:) )k L4- L AJ E old C—, F-;, (SOLD U:oJ T,,) ib tzL, ,, fJ �2osUC►<-� 1� �c�J6 � i<�= lzozbao RIM? 0�,j 4—..5D O 2 i zDfJ.A— L— �/� C,LAM t,— S (&,,—L✓ _ D _ ! rD �— t C) � I m x iL Cl� - (� b ? S �' . (4!,4 F-) -71 (e, ca:z-� 16 -"q i a_DZ_ 7Z). x 1-7 MAY - 33 20Q) NON -DISCHARGE PERIM ITTIN'S 17- t I D lam& i,- L t LUA f K. iouJbJ O 47 ``( A5430 M&W Submersible Solids -Handling Pumps Setting -Plans Iz 269 17- J— F2 T-- PLAN VIEW ACCESS COVER SUMP VENT SUMP I.D. HINGE SIDE ACCESS OPENING GUIDE RAIL2" I a SCHEDULE 40 PIPE BY OTHERS - POWER --- N I1� -11t-' CABLE EFFLUENT---'*�- I — +' FLOAT PIPE---� CONTROL LIFTING CABLE LIFTING LUGS (5) (6) F_�M PUMP SUMP I.D. A B C 4'A5432MV 60 30 42 11 4'A5433MV 60 30 148 1 11 6"A5433MV 72 36 60 113/4 PUMP D E F1 F2 4'A5432MV 21 15 10 10 4"A5433MV 24 15 11 11 WA5433MV 30 17 13 13 I• 4 � � e I ELEVATION NOTES: (1) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. (7) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH (2) FOR USE WITH IMPELLER DESIGN T8D1A. GROUT OR A SOLE PLATE GROUTED IN PLACE. (3) FOR USE WITH IMPELLER DESIGNS T8D1 D OR TAKC5W. (8) NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION (4) 5400'S AND 5400K'S ARE DIMENSIONALLY IDENTICAL. PURPOSES UNLESS CERTIFIED. DIMENSIONS SHOWN MAY (5) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. VARY DUE TO NORMAL MANUFACTURING TOLERANCES. OPTIONAL CONTINUOUS IN AIR MODIFICATION AVAILABLE. (9) REFER TO BASIC PUMP DIMENSION DRAWING FOR WL AND (6) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR MW DIMENSIONS. SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. RECEIVED WATER QUALITY SECTION DUPLEX IN -LINE, A5430MV, SUBMERSIBLE PULL-UP Pump ®IVI P2 9 SINGLE DOOR ACCESS COVER Ro° 543MS087 No! 3 8/1/97 NON-DISCFIPa tP l9 fTING 3-._-4gV--ate Pa u-( ? ` i,Ll ttt • . �k t S� � N � -t=1—e �.�1 i t� izz� c�G�.—� t �u`�S� �- i � � �— 14 +D a 1 l� i l L U,__�--- ME -z' z Q 711 C'I oo F D Sz -t t —.4 1 4 .4 z-1-4 ij e- Ef, Pow? h�- ni iu 1,4 -2 -1 --1 .44 1 �Te n 6 , . ('r�\ `.L�� ' � ~ ' | ^ ��| -------' '- ''! ---- `! 00 ! |�' FLA • State of North Carolina Department of Environment and Natural Resources Asheville Regional Office Michael F. Easley, Governor William G. Ross, Jr., Secretary Gregory J. Thorpe, Ph.D., Acting Director Division of Water Quality �f NCDENR NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES WATER QUALITY SECTION Mr. Robert Frye, Town Manager Town of Sawmills 4076 US Highway 321-A Granite Falls, North Carolina 28630 May 14, 2002 SUBJECT: Permit No. WQ0021309 Helena Street CDBG Area Town of Sawmills Wastewater Collection System Extension Caldwell County Dear Mr. Frye: In accordance with your application received May 3, 2002, please find attached Permit No. WQ0021309 for the construction and operation of the subject wastewater collection system extension. This Permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by reference. Please pay particular attention to condition three (3) of the permit which requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any individual system -wide collection system permit issued to the Town of Sawmills. Permitting of this project does not constitute acceptance of any part of the project that does not meet 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12,1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. It shall be the Permittee's responsibility to ensure that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute 143-215.6A through 143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -Licensed Professional Engineer to the licensing board. k"Robert Frye May 14, 2002 Page Two In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the Town of Sawmills for the construction and operation of approximately 8167 linear feet of eight -inch gravity sewer; a 126 gallon per minute pump station with duplex pumps, on -site audible and visual high water alarms, telemetry, and standby generator; as well as approximately 804 linear feet of four -inch force main to serve 82 residences and a commercial garage as part of the Helena Street Area CDB Project and the discharge of 29,570 gallons per day of collected domestic wastewater into the Town of Sawmills's existing sewerage system, pursuant to the application received May 3, 2002, and in conformity with 15A NCAC 2H .0200; the Division's Gravity Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data subsequently -filed and approved by the Department of Environment and, Natural Resources and considered a part of this permit. The sewage and wastewater collected by this system shall be treated in the City of Lenoir's Gunpowder Wastewater Treatment facility (NPDES Permit No. NC0023736) prior to being discharged into the receiving stream. If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This. request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Mr. Jim Reid at 828/251-6208. Sincerely, Enclosure xc: Caldwell County Health Department Non -Discharge Permitting Unit City of Lenoir, L.D. Hagaman, Jr. Bengie Thomas, West and Associate Jim Reid, . 2 R' NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES RALEIGH WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT TOWN OF SAWMILLS HELENA STREET AREA CDBG PROJECT PERMIT NUMBER WQ0021309 This permit shall be effective from the date of issuance *until rescinded and shall be subject to the following specified conditions and limitations: 1. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit: 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. 2. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. 3. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2H .0227: a. The sewer system shall be effectively maintained and operated .at all times to prevent discharge to surface waters, and any contravention of the groundwater standards in 15A NCAC 2L .0200 or the surface water standards in 15A NCAC 213.0200. b. A map of the sewer system shall be developed prior to January 1, 2004 and shall be actively maintained. C. An operation and maintenance plan shall be developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day, as defined in 15A NCAC 213 .0503(5). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. High -priority sewer lines shall be inspected at least once per every six-month period of time. 3 �-VQ0021309 ` f. A general observation of the entire sewer system shall be conducted at least once per year. g. Inspection and maintenance records shall be maintained for a period of at least three years. h. Overflows and bypasses shall be reported to the appropriate Division Regional Office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute 143-215.1C. 4. This permit shall not be transferable. In the event there is a desire for the wastewater facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, .and other supporting materials as may be appropriate. -The approval of this request shall be considered on its merits and may or may not be approved. 5. Construction of the gravity sewers shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. 6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a copy of the construction record drawings, as well as supporting design calculations for any pump stations permitted as part of this project shall be received from a North Carolina -licensed Professional Engineer certifying that the facilities have been installed in accordance with this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design • Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Main adopted June 1, 2000 as applicable; and other supporting materials. If this project is to be completed in phases and partially certified, you shall retain the responsibility to track further construction approved under the same permit, and shall provide a final certificate of completion once the entire project has been completed. A copy of the construction record drawings, indicating the facilities constructed in the phase being certified, shall be submitted with each partial. certification. Mail the Engineer's Certification, one copy of the "Construction Record Drawings", and one copy of the supporting design calculations to the Non -Discharge Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617. 7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. 8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes 143-215.6A through 143-215.6C. 4 WQ0021309 9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of'additional or replacement facilities., 10. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General Permit NCG0100000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A NCAC 2H .0500. 11: Non-cormpl!iance NPtification:. The Permittee shall report by telephone to the Asheville Regional Office, telephone number 828/251-6208 as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. • Persons reporting such occurrences by telephone shall also file a written report in letter form within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. Per ..it issued this the Fourteenth day of May, 2002., NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION AGregoryJ. Thorpe, Ph.D., Acting Director Division of Water Quality By Authority of the Environmental Management Commission Permit Number WQ0021309 5 ,Permit No. WQ0021309 May 14, 2002 ENGINEERS CERTIFICATION D b 5 � MAR 3 1 2Q04 Partial 1 'Final WATER QUALITY SECTION ASHEVILLE REGIONAL OFFICE I, Beniamin B. Thomas—, as a duly registered Professional Engineer in the State of North Carolina, having been authorized to obsery periodically, eekly, full time) the construction of the project, _Sawmills's Helena Street area CDBG Prolec_t, Town of Sawmills, Caldwell County for Project Name Location and County the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. O'111111111.,,,0 NO, Mot,, North Carolina Professional Engineer's seal, signature, and date: `•,•`0,�EESSI�•��q���'•,, ,® '�• a SE AL Js��3 20757 ie ,t• The above Engineer's Certification shall be completed and submitted to the address below with one copy of the "Construction Record Drawings" of the wastewater collection system extension as well as supporting design calculations for any pump stations permitted as part of this project. This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been received by the Division. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Enginneer's Certification shall be considered a violation of the permit. and shall subject the Permittee. to appropriate enforcement actions. NORTH CAROLINA DIVISION OF WATER QUALITY WATER QUALITY SECTION NON -DISCHARGE PERMITTING UNIT 1617 MAIL SERVICE CENTER RALEIGH, NORTH CAROLINA 27699-1617 C1 N%WNN �OF G Michael F. Easley, Governor \Q William G. Ross, Jr., Secretary Cq North Carolina Department of Environment and Natural Resources �I Alan W. Klimek, P.E., Director O 'C Division of Water Quality Asheville Regional office WATER QUALITY SECTION May 13, 2003 Mr. Robert Frye Town of Sawmills 4076 Highway 321-A Granite Falls, North Carolina 28630 Subject: Permit No. WQ0022566 Helena Street CDBG Sewer Town of Sawmills City of Lenoir, Gunpowder Plant Sewers Caldwell County Dear Mr. Frye: In accordance with the application received May 6, 2003, please find enclosed Permit No. WQ0022566, dated May 13, 2003, for -construction and. operation of the subject wastewater collection system ,extension. The permit will be effective until rescinded; it implements the conditions and limitations specified therein. This cover letter shall be considered a part of the permit and is incorporated by reference. Please pay particular attention to Permit Condition 3 which requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any individual system -wide collection system permit issued to the Town of Sawmills. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2H :0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. The Town of Sawmills is responsible for ensuring that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina - licensed Professional Engineer to the licensing board. In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the Town of Sawmills for construction and operation of approximately 12,892 linear Robert Frye May 13, 2003 Page Two feet of eight -inch gravity sewer; a 200—gallon per minute pump station with -duplex pumps, on -site audible and visual high water alarms, and on -site generator with automatic transfer switch; as well as approximately 4197 linear feet of six-inch force main to serve the Helena Street CDBG Sanitary Sewer Project, and the discharge of 49,610 gallons per day of collected domestic wastewater into the City of Lenoir's existing sewerage system, pursuant to the application received May 6, 2003 and in conformity with 15A NCAC 2H .0200; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data. subsequently filed and approved by the Department of Environment and Natural Resources and considered a part of this permit. The sewage and wastewater collected by this system shall be treated in the City of Lenoir's Gunpowder Creek Wastewater Treatment Facility (NPDES Permit No. NC0023736) prior to being discharged into the receiving stream. This permit shall become voidable unless the agreement between Town of Sawmills and City of Lenoir for the collection and final treatment of wastewater is in full force and effect. If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within ,30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Mr. James Reid at 828/251-6208. Sincerely, Alan W. limek, P.E. Enclosure xc: Caldwell County Health Department'.. / Benjie Thomas, West &Associates Water Quality Central Files NDPU Files James Reid NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES TOWN OF SAWMILLS, HELENA STREET CDBG SEWER WASTEWATER`COLLECTION SYSTEM EXTENSION PERMIT This permit shall be effective from the date of issuance until rescinded and shall be subject to the following specified conditions and. limitations: 1. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. 2. This -permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. 3. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2H .0227: a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and any contravention of the groundwater standards in 15A NCAC 2L :0200 or the surface water standards in 15A NCAC 2B .0200. b. .A map of the sewer system shall be developed prior to January 1, 2004 and shall be actively maintained. c. An operation and maintenance plan shall be developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. High -priority sewer lines shall be inspected at least once per every six-month period of time. f. A general observation of the entire sewer system shall be conducted at least once per year. g. Inspection and maintenance records shall be maintained for a period of at least three years. 3 WQ0022566 h. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and .public notice shall be provided as required by North Carolina General Statute §143-215.1 C. 4. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. 5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. 6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a copy of the construction record drawings, as well as supporting design calculations for any pump stations permitted as part of this project shall be received from a North Carolina -licensed Professional Engineer certifying that the facilities have been installed' in accordance with this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Main adopted June 1, 2000 as applicable; and other supporting materials. If this project is to be completed in phases and partially certified, you shall retain the responsibility to track further construction approved under the same permit, and shall provide a final certificate of completion once the entire project has been completed. A copy of the- construction record drawings, indicating the facilities constructed in the phase being certified, shall be submitted with each partial certification. Mail the Engineer's Certification, one copy of the "Construction Record Drawings," and one copy of the supporting design calculations to the Non -Discharge Permitting Unit, 1617 -Mail Service Center, Raleigh, NC 27699-1617. 7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. 8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C. 8. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. 0 4 ,r WQ0022566 9. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules,' regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 213 .0200, erosion and sedimentation control requirements in 15A NCAC Chapter 4 and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A NCAC 2H .0500. 11. Non-compliance Notification: The Permittee shall report by telephone to the Asheville Regional Office, telephone number (828) 251-6208, as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or. b. Any failure of a pumping station -or sewer line resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. 12. Persons reporting such occurrences by telephone shall also file a written report in letterform within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. Permit issued this the Thirteenth day of May, 2003. NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION�`y' 3;, t' an W. Kli ek, .E., Director Division of Water Quality = By Authority of the Environmental Management Commission Permit Number WQ0022566 Permit No. WQ0022566 May 13, 2003 Town of Sawmills, Helena St. CDBG Sanitary Sewer Complete and submit this form to the permit issuing Asheville Regional office with the following: • One copy of the project record drawings (plan . & profile views of sewer lines) of the wastewater collection system extension • supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to the project should be clearly identified on the record drawings or in written summary form. Permit modifications are required for any changes resulting in non-compliance with this permit, regulations or minimum design criteria. This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been received by the Division. Therefore, it is highly recommended that this certification be sent in a manner that provides proof of receipt by the Division. ENGINEER'S CERTIFICATION 0 Partial Final as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe ([periodically, ❑ weekly, ❑ full time) the construction of the Helena St. CDBG Sanitary Sewer, County project for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance. of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track .Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS: ASHEVILLE REGIONAL OFFICE 59 WOODFIN PLACE ASHEVILLE, NC 28801 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. 6 W ATF ud r r- MAY _ C 2003 State of North Carolina Department of Environment and Natural Resources Division of Water Quality FAST -TRACK APPLICATION EWERS, PUMP STATIONS, AND FORCE MAINS (Pressure sewers systems are not to be included as part of this application package) INSTRUCTIONS: Indicate that you have included the following list of required application package -items by checking the space provided next to each item. Failure to submit all required items will lead to your application, being returned as incomplete or additional processing and review time. This form may be photocopied for use as an original. ® I. Application Form - Submit one original and one copy of the completed and appropriately executed application form. Any changes to this form will result in the application being returned. The Division of Water Quality (Division) will only accept application packages that have been fully completed with all applicable items addressed. You do not need to submit detailed plans and specifications unless you respond NO to Item 13(12) ® 11. Application Fee - Submit a check in the amount of $400 made payable to: North Carolina Department of Environment and Natural Resources (NCDENR). ❑ III. Certificates of Public Convenience and Necessity — If the application is being submitted in the name of a privately -owned public utility, submit two copies of the Certificate of Public Convenience and Necessity (CPCN) which demonstrates that the public utility is authorized to hold the utility franchise for the area to be served by the sewer extension. If a CPCN has not been issued, provide two copies of a letter from the North Carolina Utilities Commission's Public Staff that states that an application for a franchise has been received, that the service area is contiguous to an existing franchised area, and/or that franchise approval is expected. The project name in the CPCN or letter must match that provided in Item A(2a) of this application. ❑ IV. Operational Agreements — Submit one original and two copies of a properly executed operational agreement if the sewer extension will be serving residential or commercial lots (e.g., houses, condominiums, townhomes, outparcels, etc.) that will be owned by a homeowners' association or developer (Item B(2b)). If the applicant is a homeowners' association, use Form HOA 02/03. If the applicant is a developer, use Form. DEV 02/03. EVEN IF THE PROJECT WILL BE TURNED OVER TO A MUNICIPALITY, FORM DEV 02/03 IS REQUIRED. V. Flow Acceptance Letters — If the owner of the downstream sewers and/or WWTF is different from the applicant, submit two copies of a flow acceptance letter from the owner of the downstream sewers and WWTF, if different. Flow acceptance letters must contain the following minimum information: applicant and project name, amount of flow accepted, and name and permit number of the receiving sewers/WWTF. The flow acceptance must not expire prior to permit issuance and must be dated less than a year prior to the application date. Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific flow acceptance letter. ® VI. Map — Submit an 8.5-inch by 11-inch copy of the portion of a 7.5-minute USGS Topographic Map along with this form. The map should identify the entire project area location as well as the closest downslope surface waters as clearly as possible. Each map portion must be labeled with the map name and number, the identified location, and be of clear and reproducible quality. For instance, if the project involves 4 miles of interceptor sewer that traverses over or near several different waterbodies (or counties, basins, etc.), the map should have location ID's for each different waterbody (where the sewer line is within 100 feet of such waterbody - see Instruction VII). ® VII. Watershed Classifications — Section C • If any portion of the project is within 100 feet of any down slope surface water, Section C must be completed for the pertinent sections. • If the. entire project area is a minimum of 100 feet away from any down slope surface waters BUT there is a pump station involved where a history of power outage is to be used to provide adequate design storage instead of dual feed or permanent or portable generator, Section C must be completed to demonstrate that the closest down slope surface water is Class C (see 15A NCAC 2H .0219(h)(3)(D)). • Use the guidance document entitled, "Determining Watershed Classifications for Form FTA 02/03 (Fast -Track Sewer Systems)" available from http://h2o.enr.state.nc.us/ndpu or by contacting the appropriate regional office. INSTRUCTIONS FOR FORM FTA 02/03 ❑ VIII. Environmental Assessments — If this project is subject to an Environmental Assessment (EA) ]15A NCAC 01C .0500], this application can not be used. Send the project application on Form PSFMGSA 10/99 to the Non -Discharge Permitting Unit, 1617 Mail Service C enter, Raleigh, NC 2 7699-1617. Applications c an not b e processed until a Finding of No Significant Impact (FONSI) or Environmental Impact Statement (EIS) has been issued. A copy is to be submitted with that permit application. ® IX. Certifications — Section D The application must be certified by both the applicant and a North Carolina Registered Professional Engineer (PE). The applicant, signature must match the signing official listed in Item A(1 b). The PE should NOT certify the application if he/she is unfamiliar with 15A NCAC 2H .0200, the Gravity Sewer Minimum Design Criteria (most recent version) and the Minimum Design Criteria for the cast -Track Permitting of Pump Stations and Force Mains (most recent version), as applicable to the project. Certification by a PE who is unfamiliar with these documents is subject to NC Board referral. THE COMPLETED FTA 02/03 APPLICATION PACKAGE, INCLUDING ALL SUPPORTING DOCUMENTS AND $400 FEE, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFWIF REGIONAL OFFICE ADDRESS COUNTIES SERVED Asheville Regional Office 59 Woodfin Place Avery, Buncombe, Burke, Caldwell, Asheville, Asheville, North Carolina 28801 ille, N Cherokee, Clay, Graham, Haywood, 08 Henderson, Jackson, Macon, Madison, (828) 251-6208 Fax McDowell; Mitchell, Polk, Rutherford, Swain, Transylvania, Yancey Fayetteville Regional Office 225 Green Street Suite 714 Anson, Bladen, Cumberland, Harnett, Hoke, Fay Fayetteville, North Carolina 28301 Montgomery, Moore, Robeson, Richmond, Sampson, Scotland (910) 486-1541 (910) 486-0707 Fax Mooresville Regional Office 919 N Main Street Alexander, Cabarrus, Catawba, Cleveland, Mooresville, North Carolina 28115 Gaston, Iredell, Lincoln, Mecklenburg, Rowan, (704) 663-1699 Stanly, Union (704) 663-6040 Fax Raleigh. Regional Office 1628 Mail.. Service Center Chatham, Durham, Edgecombe, Franklin, Raleigh, North Carolina 27699-1628 Granville, Halifax, Johnston, Lee, Nash, Northampton, Orange, Person, Vance, Wake, (919) 571-4700 Warren, Wilson (919) 571-4718 Fax Washington Regional Office 943 Washington Square Mall Beaufort, Bertie, Camden, Chowan, Craven, Washington, North Carolina 27889 Currituck, Dare, Gates, Greene, Hertford, Hyde, Jones, Lenoir, Martin, Pamlico, (252) 946-6481 (252) 975-3716 Fax Pasquotank, Perquimans, Pitt, Tyrrell, Washington, Wayne Wilmington Regional Office 127 Cardinal Drive Extension Brunswick, Carteret, Columbus, Duplin, New Wilmington, North Carolina 28405 Hanover, Onslow, Pender (910) 395-3900 (901) 350-2004 Fax Winston-Salem Regional 585 Waughtown Street Alamance, Alleghany, Ashe, Caswell, Office Winston-Salem, North Carolina Davidson, David, Forsyth, Guilford, 27107 Rockingham, Randolph, Stokes, Surry, (336) 771-4600 Watauga, Wilkes, Yadkin (336) 771-4631 Fax For more information, visit our web site at: http://h2o.enr.state.nc.us/ndpu/ INSTRUCTIONS FOR FORM FTA 02/03 FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 1 ---- ---. _—._.._ ..---------._...__...... .... ----- - - -- ....._..--..._........ - ._. _.................... ................... USE THE TAB KEY TO MOVE FROM FIELD TO FIELD! Application Number: (to be completed by DWQ)� J. Owner.• I a. Town of Sawmills Full Legal Name (company, municipality, HOA, utility, etc.) Z 1 b. Robert Frye, Town Manager 0 ...---._.._. Signing Official Name and Title (Please review 15A NCAC 2H .0206(b) for authorized signing officials!) ........ ..... _...--........------.._.._............-..... __.._...... --..._.._..._:._....._.......... -.............. _ H Q ,1 c. _..... ..... .... ..__-.____..._-..... _..... __........ _.._.._........... .... .... .... _..-..........._.........._--- ................. ..__.._.-._.._............ _....... ......:...._...._..._.._...... The legal entity who will own this system is: ❑ Individual ❑ Federal ®.Municipality ❑ State/County ❑ Private Partnership ❑ Corporation_❑ Other, (specify): .. _. ® 11d. 4076 US Highway 321-A 1e. Granite Falls ItL__..... _. Street Address City __._.._......... ..... - ...... -- ---.._......._......--- - _ -----...........-- -- _.._.._...... _..-- ....._..........--- - ._.._....__..._._._._._..- Z 'If. -...._._._..---.._.._.._....._... _ ...._._..... ....__...._...... NC 1 g. 28630 State Zip Code I h. 828-396-7903 1 i. 828-396-8955 1 j. _._.. Telephone Facsimile E-mail --._.._....._..-... ........_._-....._....._....____....._...._......_....__._._...__.._..._._....-.._.._...__._.....---...__......_...___......._..-___ () 12. _._.._.....__....... _...__.._.._.......... _ ---- ....__.._........., Project (Facility) Information: ..... __ .............. _ ......... IL 2a. .......... .......... .............. ........... _............... ......._......... .. _...... _.. __...... _...- -.............. _... ... _..................... ....._............. Helena Street Area CDBG Sanitary Sewer Project 2b. Caldwell a Brief Project Name (permit will refer to this name) County Where Project is Located Q J. _._..._......__..._...__............---- ....._.......-- -----..........__..__......__.._.._......_._._.._........._._..__._........_._..._._..__......... ._..._..._... ....... ..... _.... ......._........ -..._..-_. _..._._...._..__........... _.... ............. _.......... ...... ... _.... Contact Person: a 3a. Benjamin B. Thomas, PE, West Consultants, PLLC Name and Affiliation of Someone Who Can Answer Questions About this Application 3b. 828433-5661 3c. benjiethomas@bellsouth.net Phone Number E-mail 1. Project is ❑ New ® Modification (of an existing permit) If Modification, Permit No.: WQ0021309 - 2. Owner is ® Public (skip to Item B(3)) ❑ Private (go to Item 2(a)) 2a.- If private, applicant will be: 2b. If sold, facilities owned by a (must choose one) ❑ Retaining Ownership (i.e. store, church, single office, etc.) ❑ Public Utility (Instruction III) ❑ Leasing units (lots, townhomes, etc. - skip to Item B(3)) El Homeowner Assoc./Developer (Instruction IV) ❑ Selling units (lots, townhomes, etc. - go to Item B(2b)) 3. City of Lenoir Owner of Wastewater Treatment Facility (WWTF) Treating Wastewater From This Project i 4a. Gunpowder Creek 4b. NC0023736 Name of WWTF WWTF Permit No. 0 LL 5a. City of Lenoir 5b. 8" 5c. unknown Z �- Owner of Downstream Sewer Receiving Sewer Size Permit Number of Downstream Sewer 6. The origin of this wastewater is (check all that apply): ® Residential Subdivision ❑ Car Wash ® Apartments/Condominiums ❑ InstitutionLU a 100 /o Domestic/Commercial ❑ Mobile Home Park ❑ Hospital CL ❑ School ❑ Church % Industrial ❑ Restaurant ❑ Nursing Home o ❑ Office El Other (specify): /o Other (specify): 7. Volume of wastewater to be permitted in this project: 49,610 gallons per day 8. If the permitted flow is zero, indicate why: " ❑ Interceptor Line - Flow will be permitted is subsequent permits that connect to th' i ❑ Flow has already been allocated in Permit No. MAY ❑ Rehabilitation Ai 2003 l or replacement of existing sewer with no new flow expected 6 M12 FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 2 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2H .0219(I) for Item 13(7) or the design flow for line or pump station sizing if zero flow in the space below. Values other than that in 15A NCAC 2H .0219(1)(1-2) must be approved prior to submittal of this application. Submit a separate request to the Division of Water Quality, Non -Discharge Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617 in accordance with 15A NCAC 2H .0219(I)(3). (87) 3-bedroom houses @360 + (2) 2-bedroom houses @240 + (42) 1 -bedroom apartments @120 + (58) 2-bedroom apartments @ 240 + garage with 2 employees @ 25 -49,610 GPD 10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary) Size (inches) Length (feet) Gravity or Force Main en (pull down menu) 8 12,892 ............:..:............ .... ...._..:..._..:................. ........_..._........................ ..... ..._................._.,_.._......................_............_............ _._. _.. , Gravity .............._..............._..._._...................._.................................................... .;.........._.................__. 6...... ..... ...__...._._....... ....... _..... ......._...... .... ...... ........ 4,197 Force Main W L ..._..._.._..... _......... _.... ..................... .. s . Grav ity _.._.Gravity H t_......... ................_._._.. _............. Gravity _.._.._......._...._..._............- ......-.._...._._............ _ Gravity VGravity --- -----'----.._.. _...... _ _...... ..:. _ Z ENTER TOTAL LINE LENGTH IN MILES 3.24 h- 111. Summary of Pump Stations to be Permitted (attach additional sheets as necessary) Power Reliability Option Location ID Design Flow Operational Point (dual line feed, permanent generator WATS, --.........__ ._....-own o.._.._P.........ns) -'- (MGD) GPM @ TDH (as shown on plans) — !portable generator w/autodialer, wet well storm ATS _ ... .... ..._ .............. Does the sewer system comply with the Minimum Design Criteria for the Fast Track Permitting of Pump Stations and Force m Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC 2H .0200 as applicable? ® Yes ❑ No If no, please reference the pertinent minimum design criteria or regulation and indicate why a variance is requested: F SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS PERTINENT TO THE VARIANCE WITH YOUR APPLICATION I 3. Have the following submitted for approval? Wetland/Stream Crossings - General. Permit or 401 Certification? ® Yes ❑ No ❑ N/A Sedimentation and Erosion Control Plan? Stormwater? ® Yes ❑ No ❑ N/A ❑ Yes ❑ No ® N/A F'rA r»inz FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 3 1. Use the Division's guidance document entitled, "DETERMINING STREAM CLASSIFICATIONS FOR FORM FTA 02/03 (FAST -TRACK SEWER SYSTEMS)" to collect and record the stream classification data below (attach additional sheets as necessary). This document is available from our web site or by contacting the appropriate Division of Water Quality regional office (see instructions for addresses) OR indicate the following: - ....—...---..._..... - -- _ ..__...._......_._...--...:....._..._..:...--...----.........._......._._._..._.—_._._........... _.._......... ._....._._....... _........ ._.... __......... _........ __..__._......_..._......._.._.__.......... .......... ❑ A Watershed Classification is not needed because all parts of the project are at least 100 feet away from any down slope waterbody; AND, .................._................-....._.................................._................._..............................._................_........................_..........................._..........................___...... _......................... ......._.................. _.................... __.......... _... .... _........... __..... ............. ........-......_... ................ ..... .........:..._...... El ...A . ._...-...__.-........ Watershed Classification is not needed because the design does not depend on wet well storage as a power reliability option for any pump station near a Class C down slope waterbody. Location ID Name of on Man Waterbed Freemason Creek Freemason Creek River Basin Caldwell Catawba ... ....... ..............,.........._.................... Waterbody Waterbody Stream Waterbody Index Classification _....._ _._....__........ __..._......._ _. 11-47-(1) WS-IV Submit the 8.5" x 11" topographic map as required in Instruction VI regardless of whether a classification is provided! Applicant's Certification: I attest that this application for Helena Street Area CDBG Sanitary Sewer Project has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143-215.6A and 143-215.6B, any person -who knowingly makes any false statement representation, c penalties y up to $25,000 per violation. lass 2 misame iv, reh=may inclu�de a fine not to exceed $10,000 as well as civiln, [j certificationellas in an application up $25,shalbe a of a C..... � � la. Signing Official Signat re 2. Professional Engineer's Certification: W-2q--e T Date 1 attest that this application for Helena Street Area CDBG Sanita' .18„� ewe��IPLojeet? - has been reviewed by me and is accurate, complete and consistent with the informatibn-in=the.engineering plans, calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance. Although certain portions of this submittal package may have been developed by other professionals, inclusion of these materials under my signature and seal signifies that 1 have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. 2a. Benjamin B. Thomas, P.E. Professional Engineer Name .. ... _............ _..... ............ ....__.._..._..................... 2b. West Consultants, PLLC Engineering Firm 2c. 405 S. Sterling Street Address --- ----------- --------- _...... .---............ _...--- .. ,2d. Moraanton City ........----...... .... ......._ _...... ....... ......__.. :2g. 828-433-5661 Telephone 828-433-5662 Facsimile ,,Oj91.1f/1/1�` �.•�''�H CAR01 .1 056, 010 ... _........... . __..._._......... ... _........................................ f . E AL CO_ •• '• NC 2f. 28655 •i� - �,' •,� ++++, State Zip •��ee' �• ben jiethomas bel[south.net E-mail Seal, Signature & Date Vm n nn in?. v \ N 8 / 1 3966 ti xr z 3965 :. P •4a 1 \ �''" ' � "; a pro tax.. + i2 r ; -vim - �r ,�• „o.E : o � r X : •� II. '``.11•. 11 .".-r:• tj �- • Y� •_z_-// :c.'t �+ L.' _ //3r � II .•� r VI,/ �i 'IY1IrIA _ Ir _ _ �' i 12 • 11 /i 1200 3962 r �. • }- > •o s � 3961 c :yt I `i 11 47'30" 1 " I /' ^ \ '.. v ,5,,.:='., .\'.\ - • ••. f ♦tkD 1 I..\ 1 `s1� K n •'..a.°�r.�" n I' a 0 APR-30-20W 13:07 . AWOMMPID Apd129,20033 T OF L.,ENOIR Post-:, Fax Myc�e 767 _AJWg OPY MMA DAVID M RAFLOW C"CUUML M L REFROVADT I W. BROACH L L U93; J. 12- 2604GE F. K ACM)FA. N. L MM RL 0. STRAWN' Mr.. Bob Frye, Town Adminiq'Irator Town of Sawmills 4076 US Highway 321-A SaWmills, North Carolina 28 0 Re: Wastewater Flow AIIJcation — CDBG Sanitary Sewer Project — Helena Street Area Dear Mr. Frye, I am writing to confirm that #Here is adequate capacity at the Crmpowder wastewater Treatment Plant to accept ad4tional flow from the Town of Sa'wnu*lls per the existing contractual agreement: Wew�ill allocate 49,610 GPD (&Ion$` per day) of wastewater ' from the project referenced a CDBG Sanitary Sewer Project — ,Helena Street Area. If there are additional quesfio� , please contact my office. Sincerely, CITY OF LENOIR City Manager POST OMCE Box age LENOIR, NORM CAROUNA 98648-0958! • (820) 757-P-2cx3 TOTAL P.01 TOWN OF SAWMILLS HELENA STREET AREA CDBG SANITARY SEWER PROJECT AMMENDMENT - IDLEWOOD DRIVE AREA PUMP STATION DESIGN CALCULATIONS April 11, 2002 BENJAMIN B. THOMAS, P.E. WEST CONSULTANTS, PLLC MORGANTON, NORTH CAROLINA �• i a MAY F 2003 __j 4�JATER QUALITI' SECTION � ASHEVILLII REGIONAL OFFICE WEST CONSULTANTS PLLC I. DESIGN FLOW: A. PRESENT FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) B. FUTURE FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) NO. UNIT FLOW TOTAL FLOW (GAUDAY/UNIT) (GAL/DAY) " 3 42 120 5,040 70 240 16,800 360 1,800 0 25 0 ,4Yz 3 0 40 0 12 0 120 p TOTAL: 23,640 GAL/DAY 16.42 GPM PEAK: 41.04 GPM NO. UNIT FLOW TOTAL FLOW (GAUDAY/UNIT) (GAL/DAY) s 0, 120 0 0 240 p 3Q0 360 108,000 0 25 0 3 0 PQ 40 0 12 0 120 0 TOTAL: 108,000 GAL/DAY 75.00 GPM PEAK: 187.50 GPM LOW WATER ELEVATION= HIGH POINT= STATIC HEAD= II. SYSTEM CURVES: FORCEMAIN SIZE: 1 6" SDR21 EQUIVALENT LENGTH = r 5024 LF RIM MSL 1.229 ` MSL 115 FEET I.D. = 5.955 INCHES C = 120 C = 150 Q f Hf Hs TDH f Hf Hs TDH VELOCITY GPM FT/100FT FEET FEET FEET FT/100FT FEET FEET FEET FPS 50 0.035 1.75 115.00 116.75 0.023 1.16 115. 00 116.16 0.58 100 0.125 6.30 115.00 121.30 0.083 4.17 115.00 119.17 1.15 150 0.266 13.34 115.00 128.34 0.176 8.83 115.00 123.83 1.73 200 0.452 22.71 115.00 137.71 0.299 15.03 115.00 130.03 2.30 250 0.683 34.31 115.00 149.31 1 0.452 22.71 115.00 137.71 2.88 MIN. PRESENT PUMPING RATE: 41.04 GPM MIN. FUTURE PUMPING RATE: 187.50 GPM PUMP SELECTION #FRBANI� M©RSE 45435MU1 [ 5'S +/�MPLLER1780 RPM` OPERATING CONDITIONS BASED ON C=120 (SEE ATTACHED CURVES): zl ONE PUMP ON 20dGPM @17FT. TDH TWO PUMPS ON �m323GPM @14 FT. TDH D5430 M&W Submersible Solids -Handling Pumps Basic Pump Dimensions 205 TOP VIEW OF PUMP UNIT L i �X 0 C 0 _ _ _T 0 0 _ W TOP GUIDE BRACKET DETAIL 51 , BRACKET FOR USE WITH 400 & 440 5 4 FRAME MOTORS - AND 10° PUMPS 1/s" DIA. I �FI — , , AB 4 HOLES GUIDE RAILS 2: SCHEDULE 40 (3 FOR 400 & 440 FRAMES AND 10° PUMPS) PIPE BY OTHERS 2Y/1s AA %"DIA. 2 HOLES 61/z I� +, —AB —►I F2 I+-- Fi —►I ram- I I Ct DISCHARGE p -�� A Cam— "G" WIDE 4 SLOTS B FOR MOUNTING OP OF BASE ELBOW �HG BOTTOM VIEW OF ELBOW CP WL (4) I Yr 1Lji MW(5) SUCTION H(8) BOTTOM OF SUMP PUMP MOTOR FRAME DISCHLA B C D E F1 F2 G H L W X Y AA AB CP HG MW OP WL 4'D5435MV 21OT 4(9 11% 2% 6'/a 4 1 7 VA 3 33�A 107A 9V18 77/s 3 31/a 553A �/s 151/4 15 331/44"D5435MV 250T 4(9)11-% 2% 6% 4 1 7 1'A 337A 107A 9�s 7�/1s 3 31/a 591/z 7/a 151/4 15 3BY2 4"D5435MV 320T 4(9)11% 2% 63/a 4 1 7 11A 3 33'/a 101/a 95/s 7'/1s 3 31/a 68% 7A 151A 15 z8°D5435MV 320T 811 17V1a 47/16 91/4 7 27/a 10% 11/a 93/a 61% 21 193/a 1211/a 3 31/a 70 11/4 241/z 19 453/4 8°D5435MV 360T 8(11) 16 171A6 47/is 9'/a 7 27A 10% 11/a 93/4 61% 21 19Y. 12"/1s 3 3'A 701/z 1'/4 241/2 19 473/a 8"D5435MV 365T 8(11 16 17'As %1s 9'/a 7 27/e 101/a 1'/a 934 61s/a 21 19�a 12"/1s 3 3'/s 721/z 11/4 24'/z 19 493/4 8°D5435MV 400T 8(9) 30Yz 341/4 6Ya 123a 14 4 -25 1'/a 3'/a 69 21 193A 1211/s 11 8 RTF 13/a 241/2 27'/2 RTF 8"D5435MV 440T 8(9) 30'/2 341/4 6% 123/a 14 4 25 1'/a 31/4 69 21 193/a 1211/is 112 13/a 241/z 27'/z 71 10"D5435MV 360T 10(9 301/2 341/4 61M6 135/e 14 4 25 1'/a 51/z 74'As 217/a 201As 133/a ;iill B 85% 13/a 27 33 62'/z 10°D5435MV 400T 10(9) 30Yz 34'/a 617/s 13s/a 14 4 25 1'/a SYz 741As 217/e 201As 133/a 8 115 13/a 27 33 74 NOTES: (1) DISCHARGE FLANGE IS 125# ANSI DRILLING UNLESS NOTED. (7) NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION PURPOSES UNLESS CERTIFIED. (2) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. DIMENSIONS SHOWN MAY VARY DUE TO NORMAL MANUFACTURING TOLERANCES. (3) 5400-S AND 5400K'S ARE DIMENSIONALLY IDENTICAL (6) DISTANCE REQUIRED FOR PROPER SUCTION CLEARANCE. (4) RECOMMENDED LOW WATER LEVEL FOR CONWNUOUS OPERATION. (9) IF RISER PIPE IS NOT SAME SIZE AS THE DISCHARGE ELBOW, AN ECCENTRIC INCREASER 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN MUST BE USED LIMITED TO TWO SIZES LARGER MAXIMUM. OPERATE CONTINUOUSLY AT "MW" WATER LEVEL (10) IF FUTURE CONSIDERATIONS REQUIRE CHANGING TO A 400 OR 440 FRAME MOTOR, (5) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR THE 400 OR 440 FRAME DIMENSIONS SHOULD BE USED. SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. (11) IF RISER PIPE IS NOT SAME SIZE AS THE DISCHARGE ELBOW, AN ECCENTRIC INCREASER MUST BE USED LIMITED TO ONE SIZE LARGER MAXIMUM. (6) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH UL LISTED GROUT OR A SOLE PLATE GROUTED IN PLACE. ISO-9001 CERTIFIED CSA CERTIFIED (THRU 365 FRAME) CUSTOMER P.O. NO. ®Fairbanks Morse Pump JOB NAME TAG NAME BASIC PUMP PUMP SIZE AND MODEL GPM TDH RPM ROTATION D5435MV PULL-UP SUBMERSIBLE MOTOR HP FRAME PHASE HERTZ VOLTS ENCLOSURE FAIRBANKS MORSE MTR CERTIFIED FOR CERTIFIED BY DATE NOG 543MS013 No 5 8/1 /97 Fairbanks Morse Pump 230 F2 T--- ACCESS COVER SUMP VENT PLAN VIEW GUIDE RAILS�j//V 2" SCHEDULE 40 (3" FOR 400 & 440 FRAMES AND 10' PUMPS) , PIPE BY OTHERS EFFLUENT PIPE LIFTING CABLE 4 WL (5) y{I IF D5430 M&W Submersible Solids -Handling Pumps Setting Plans SUMP I.D. HINGE SIDE ACCESS OPENING POWER CABLE FLOAT CONTROL PUMP SUMP I.D. A B C D E F1 F2 4'D5432MV 60 30 42 11 21 15 10 10 4'D5433MV 60 30 48 11 24 15 11 11 6'D5433MV 72 36 60 113/a 30 17 13 13 4'D5434MV 66 42 54 13 27 18 13 13 6'D5434MV 96 42 76 21 38 261/a 1 18 1 18 8'D5434SMV(2) 84 40 6B 20 34 261/z 131/z 131/z 8'D5434LMV 3 96 48 72 24 36 301/z 18r221/2 4"D5435MV 72 36 60 18 30 22 12 8"D5435MV 96 58 86 201/z 43 27 20 10"D5435MV 108 68 88 22 44 30% 221/z 5"D5436MV R.T.F. 8"D5436SMV R.T.F. 400 & 440 FRAME PUMPS REQUIRING HEAVY DUTY ELBOWS PUMP SUMP I.D. A B C I D I E F1 F2 8"D5435MV 108 1 66 1 90 22SA 43 1 21 21 5"D5436MV R.T.F. 8"D5436LMV R.T.F. LIFTING BAIL MW(6) I •, � I T ELEVATION r NOTES: (1) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. (7) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH (2) FOR USE WITH IMPELLER DESIGN T8131A. GROUT OR A SOLE PLATE GROUTED IN PLACE. (3) FOR USE WITH IMPELLER DESIGNS T8131D OR TAKC5W. (8) NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION (4) 5400'S AND 5400K'S ARE DIMENSIONALLY IDENTICAL PURPOSES UNLESS CERTIFIED. DIMENSIONS SHOWN MAY (5) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. VARY DUE TO NORMAL MANUFACTURING TOLERANCES. 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN (9) REFER TO BASIC PUMP DIMENSION DRAWING FOR WL AND OPERATE CONTINUOUSLY AT'MW" WATER LEVEL MW DIMENSIONS. (6) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. DUPLEX IN -LINE, D5430MV, SUBMERSIBLE PULL-UP ®FakbanksMorsePump SINGLE DOOR ACCESS COVER NO 543MS037 Na 3 Fairbanks Morse Pump 8/1/97 III. WETWELL DESIGN: A. DETERMINE OPERATING VOLUME: T =- " 30'MINUTES (7.5 TO 30) Qddf = 16.42 GPM Q = 200 GPM V = 452.07 GAL. B. SELECT WETWELL DIMENSIONS: DIAMETER: FEET WETWELL DEPTH = PRESENT CONDITIONS: OPERATING DEPTH: 2.14 FEET TOP ELEV =1121 t1y0 GROUND =1120 5Qo LOWEST SEWER IN111v 1Q LAG PUMP ON = 1114.52 ALARM = 1114.02 LEAD PUMP ON = 1113.52 PUMPS OFF = 1111.38 BOTTOM = 1107.88 FUTURE: Tr 10 MINUTES (7.5 TO 30) Qddf = 75.00 GPM Q = 200 GPM V = 468.75 GAL. 13.12 FEET FUTURE CONDITIONS: OPERATING DEPTH: 2.22 FEET TOP ELEV = 1121.00 GROUND = 1120.50 LOWEST SEWER IN = 111.5.10 LAG PUMP ON = 1114.60 ALARM = 1114.10 LEAD PUMP ON = 1113.60 PUMPS OFF = 111.1.38 BOTTOM = 1107.88 DEPTH REQUIRED FOR PUMP PROTECTION �a 3 50= FEET PRESENT CONDITIONS CYCLES PER HOUR: 2.0 FUTURE CONDITIONS CYCLES PER HOUR: 6.0 C. CHECK FLOTATION: 1. BUOYANCY = SUBMERGED VOLUME X 62.4 PCF: WETWELL I D fflEgMFEET WETWELL O.D. 7.00 FEET SUBMERGED DEPTH: 13.28 FEET BUOYANCY: 31,898 LBS. 2. WEIGHT OF WETWELL: TOP = 9.00 INCHES AND 3,876 LBS. RISER = 11.87 FEET @ 1910.00 LBSNF = 22,665 LBS. BOTTOM = 8.00 INCHES AND 3,850 LBS. TOTAL = 30,391 LBS. FACTOR OF SAFETY = 0.95 NO GOOD EXTENDED BASE SLAB IS REQUIRED BASE SLAB EXTENSION = 8.0 'INCHES HEIGHT OF SOIL = 12.62 FEET WET SOIL WT.(50PCF) = 10,102 LBS. THEN TOTAL RESISTANCE TO UPLIFT = 40,492 LBS. FACTOR OF SAFETY = 1.27 OK V = TQddf 1 - Qddf Q V = active volume within the pump station (gallons) T = allowable cycle time between starts (minutes) Qddf = design daily flow to pump station (gallons per minute) Q = pumping rate of a single pump (gallons per minute) WETWELL DATA PER TINDALL CONCRETE G-SERIES DIA. O.D. WEIGHTS HEIGHT (INCHES) EXTENDED BASE (FT) (FT) RISER (LBNF) BASE LB)* TOP (LB) I BASE TOP O.D. (FT) 4.0 4.83 915 1375 1242 6 8 5.83 5.0 5.83 1370 2600 2773 8 9 7.17 6.0 7.00 1910 3850 3876 8 9 8.33 7.0 8.17 2207 5240 7625 8 16 9.33 8.0 9.33 2879 6840 8689 8 16 11.00 10.0 11.67 4481 12030 14312 9 16 14.00 * BASED ON BASE AREA X HT X 150 PCF A. sA-wm l Lt_S _.-_ -_- _-.—.�_---_'" ' .... �� � � I r l/�y��_. __ _[ _` , _ � V -" "rJ �'_� �{•F^�`��.��,p_ _ WLd A V �� _ _ -! `V(...t�. � • ' I ' {...-•�.� i _ _ // 062, C � for . 51P,-(L .. � s -t r�cu J7ss s) - U c7� SvIJ �- I Nt -Tycz r oil ooD /�r�o'`P S �r4�cotJ y 1 c WATF F O�� 94G Michael F. Easley, Governor William G. Ross, Jr., Secretary r7 North Carolina Department of Environment and Natural Resources > Alan W. Klimek, P.E., Director Division of Water Quality Asheville Regional Office WATER QUALITY SECTION Mr. Robert Frye Town of Sawmills 4076 Highway 321-A Granite Falls, North Carolina 28630 Dear Mr. Frye: May 13, 2003 Subject: Permit No. WQ0022566 Helena Street CDBG Sewer Town of Sawmills City of Lenoir, Gunpowder Plant Sewers NN�Caldwell County . In accordance with th&application received May 6, 2003, please find enclosed Permit No. WQ0022566, dated May 13, 2003, for construction and operation of the subject wastewater collection system extension. The permit will be effective until rescinded; it implements the conditions and limitations specified therein. This cover letter shall be considered a part of the permit and is incorporated by reference. Please pay particular attention to Permit Condition 3 which requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any individual system -wide collection system permit issued to the Town of Sawmills. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. The Town of Sawmills is responsible for ensuring that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina - licensed Professional Engineer to the licensing board. In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the Town of Sawmills for construction and operation of approximately 12,892 linear WQ0022566 h. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1 C. 4. ' This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. 5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. 6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a copy of the construction record drawings, as well as supporting design calculations for any pump stations permitted as part of this project shall be received from a North Carolina -licensed Professional Engineer certifying that the facilities have been installed in accordance with this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the. Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Main adopted June 1, 2000 as applicable; and other supporting materials. If this project is to be completed in phases and partially certified, you shall retain the responsibility to track further construction approved under the same permit, and shall provide a final, certificate of completion once the entire project has been completed. A copy of the construction record drawings, indicating the facilities constructed in the phase being certified, shall be submitted with each partial certification. Mail the Engineer's Certification, one copy of the "Construction Record Drawings," and one copy of the supporting design calculations to the Non -Discharge - Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617. 7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. 8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C. 8. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. WQ0022566 9. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200, erosion and sedimentation control. requirements in 15A NCAC Chapter 4 and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A NCAC 2H .0500. 11. Non-compliance Notification: The Permittee shall report by telephone to the Asheville Regional Office, telephone number (828) 251-6208, as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or - b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. 12. Persons reporting such_ occurrences by telephone shall also file a written report in letterform within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not.recur. Permit issued this the Thirteenth day of May, 2003. NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION Alan W. KliFhek,F.E., Director Division of Water Quality By Authority of the Environmental Management Commission Permit Number WQ0022566 5 Permit No. WQ0022566 May 13, 2003 Town of Sawmills, Helena St. CDBG Sanitary Sewer Complete and submit this form to the permit issuing Asheville Regional office with the following: • One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection system extension • supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to the project should be clearly identified on the record drawings or in written summary form. Permit modifications are required for any changes resulting in non-compliance with this permit, regulations or minimum design criteria. This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been received by the Division. Therefore, it is highly recommended that this certification be sent in a manner that provides proof of receipt by the Division. ENGINEER'S CERTIFICATION ❑ Partial ❑ Final I, , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (❑ periodically, ❑ weekly, ❑ full time) the construction of the Helena St. CDBG Sanitary Sewer, County project for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS: ASHEVILLE REGIONAL OFFICE 59 WOODFIN PLACE ASHEVILLE, NC 28801 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. 6 State of North Carolina Department of Environment and Natural Resources Division of Water Quality FAST -TRACK APPLICATION SEWERS, PUMP STATIONS, AND FORCE MAINS (Pressure sewers systems are not to be included as part of this application package) INSTRUCTIONS: Indicate that you have included the following -list of required application package.items by checking the space provided next to each item. Failure -to submit all required items will lead to your application being returned as incomplete or additional processing and review. time. This form may be photocopied for use as an original. 01. Application Form - Submit one original and one copy of the completed and appropriately executed application form. Any changes to this form will result in the application being returned. The Division of Water Quality (Division) will only accept application packages that have been fully completed with all applicable items addressed. You do not need to submit detailed plans and specifications unless you respond NO to Item B(12) ® If. Application Fee - Submit a check in the amount of $400 made payable to: North Carolina Department of Environment and Natural .Resources (NCDENR). ❑ III. Certificates of Public Convenience and Necessity — If the application is being submitted in the name of a privately -owned public utility, submit two copies of the Certificate of Public Convenience and Necessity (CPCN) which demonstrates that the public utility is authorized to hold the utility franchise for the area to be served by the sewer extension. If a CPCN has not been issued, provide two copies of a letter from the North Carolina Utilities Commission's Public Staff that states that an application for a franchise has been received, that the service area is contiguous to an existing franchised area, and/or that franchise approval is expected. The project name in the CPCN or letter must match that provided in Item A(2a) of this application. ❑ IV. Operational Agreements — Submit one original and two copies of a properly executed operational agreement if the sewer extension will be serving residential or commercial lots (e.g., houses, condominiums, townhomes, outparcels, etc.) that will be owned by a homeowners' association or developer (Item B(2b)). If the applicant is a homeowners' association, use Form HOA 02/03. If the applicant is a developer, use Form DEV 02/03. EVEN IF THE PROJECT WILL BE TURNED OVER TO A MUNICIPALITY, FORM DEV 02/03 IS REQUIRED. ® V. Flow Acceptance Letters — If the owner of the downstream sewers and/or WWTF is different from the applicant, submit two copies of a flow acceptance letter from the owner of the downstream sewers and WWTF, if different. Flow acceptance letters must contain the following minimum information: applicant and project name, amount of flow accepted, and name and permit number of the receiving sewers/WWTF. The flow acceptance must not expire prior to permit issuance and must be dated less than a year prior to the application date. Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific flow acceptance letter. ® VI. Map — Submit an 8.5-inch by 11-inch copy of the portion of a 7.5-minute USGS Topographic Map along with this form. The map should identify the entire project area location as well as the closest downslope surface waters as clearly as possible. Each map portion must be labeled with the map name and number, the identified location, and be of clear and reproducible quality. For instance, if the project involves 4 miles of interceptor sewer that traverses over or near several different waterbodies (or counties, basins, etc.), the map should have location ID's for each different waterbody (where the sewer line is within 100 feet of such waterbody - see Instruction VII). ® VII. Watershed Classifications — Section C • If any portion of the project is within 100 feet of any down slope surface water, Section C must be completed for the pertinent sections. • If the entire project area is a minimum of 100 feet away from any down slope surface waters BUT there is a pump station involved where a history of power outage is to be used to provide adequate design storage instead of dual feed or permanent or portable generator, Section C must be completed to demonstrate that the closest down slope surface water is Class C (see 15A NCAC 2H .0219(h)(3)(D)). • Use the guidance document entitled, "Determining Watershed Classifications for Form FTA 02/03 (Fast -Track Sewer Systems)" available from http://h2c.enr.state.ric.us/ndpu or by contacting the appropriate regional office. 1��\1_J INSTRUCTIONS FOR FORM FTA 02/03 ❑ VIII. Environmental Assessments — If this project is subject to an Environmental Assessment (EA) ]15A NCAC 01C .0500], this application can not be used. Send the project application on Form PSFMGSA 10/99 to the Non -Discharge Permitting Unit, 1617 Mail Service C enter, Raleigh, NC 2 7699-1617. Applications c an not b e processed until a Finding of No Significant Impact (FONSI) or Environmental Impact Statement (EIS) has been issued. A copy is to be submitted with that permit application. ® IX. Certifications — Section D The application must be certified by both the applicant and a North Carolina Registered Professional Engineer (PE). The applicant signature must match the signing official listed in Item A(1 b). The PE should NOT certify the application if he/she is unfamiliar with 15A NCAC 2H .0200, the Gravity Sewer Minimum Design Criteria (most recent version) and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (most recent version), as applicable to the project. Certification by a PE who is unfamiliar with these documents is subject to NC Board referral. THE COMPLETED FTA 02/03 APPLICATION PACKAGE, INCLUDING ALL SUPPORTING DOCUMENTS AND $400 FEE, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE REGIONAL OFFICE ADDRESS COUNTIES SERVED Asheville Regional Office 59 Woodfin Place Avery, Buncombe, Burke, Caldwell, Asheville, North Carolina 28801 Cherokee, Clay, Graham, Haywood, (828) 251-6208 Henderson, Jackson, Macon, Madison, (828) 251-6152 Fax McDowell, Mitchell, Polk, Rutherford, Swain, Transylvania, Yancey Fayetteville Regional Office 225 Green Street Suite 714 Anson, Bladen, Cumberland, Harnett, Hoke, Fay Fayetteville, North Carolina 28301 Montgomery, Moore, Robeson, Richmond, Sampson, Scotland (910) 486-1541 (910) 486-0707 Fax Mooresville Regional Office 919 N Main Street Alexander, Cabarrus, Catawba, Cleveland, Mooresville, North Carolina 28115 Gaston, Iredell, Lincoln, Mecklenburg, Rowan, (704) 663-1699 Stanly, Union (704) 663-6040 Fax Raleigh Regional Office 1628 Mail Service Center Chatham, Durham, Edgecombe, Franklin, Raleigh, North Carolina 27699-1628 Granville, Halifax, Johnston, Lee, Nash, Northampton, Orange, Person, Vance, Wake, (919) 571-4700 Warren, Wilson (919) 571-4718 Fax Washington Regional Office Beaufort, Bertie, Camden, Chowan, Craven, 943 Washington Square Mall Currituck, Dare, Gates, Greene, Hertford, Washington, North Carolina 27889 Hyde, Jones, Lenoir, Martin, Pamlico, (252) 946-6481 Pasquotank, Perquimans, Pitt, Tyrrell, (252) 975-3716 Fax Washington, Wayne Wilmington Regional Office Brunswick, Carteret, Columbus, Duplin, New 127 Cardinal Drive Extension Hanover, Onslow, Pender Wilmington, North Carolina 28405 (910) 395-3900 (901) 350-2004 Fax Winston-Salem Regional 585 Waughtown Street Alamance, Alleghany, Ashe, Caswell, Office Winston-Salem, North Carolina Davidson, David, Forsyth, Guilford, 27107 Rockingham, Randolph, Stokes, Surry, (336) 771-4600 Watauga, Wilkes, Yadkin (336) 771-4631 Fax For more information, visit our web site at. http://h2o.enr.state.nc.us/ndpu/ INSTRUCTIONS FOR FORM FTA 02/03 FAST -TRACT{ APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 1 .... _.............. __..... —.__.....__.._._.—__ ... _..... ......... _... _............ _..... _.............._..._......_..._.....................__......................... _......... _.... .......... __................ __............... ..._.._..................... .................... ...................._.................................. ................. .-......................... .................. _....... USE THE TAB KEY TO MOVE FROM FIELD TO FIELD! Application Number: (to be completed by DWQ) �c i1. Owner.• 1 a. Town of Sawmills Full Legal Name (company, municipality, HOA, utility, etc.) Z i '1 b. Robert Frye, Town Manager 0 Signing Official Name and Title (Please review 15A NCAC 2H .0206(b) for authorized signing officials!) 11 c. The legal entity who will own this system is: ❑ Individual ❑ Federal ® Municipality ❑ State/County ❑ Private Partnership ❑ Corporation ❑ Other (speci _. fY) ....._..._-.. 0 11d. 4076 US Highway 321-A 1e. Granite Falls 6L, Street Address City _._...._.._..................._.._........................_._.... _..-._.._...................._..._.... . ..................... ..................... ..... --......... _................_.... _......._..... _...... ......... ............... Z_ ilf. ....__._. NC 11g. 28630 Z ! State Zip Code ............... 1 h. ....... ...._._...._..... ................... _..._...__..._.... _........... ........... ;._................................_.._.__......._.............._............__........__._._...._...._.._.............._.........._........_.............._.._..._._......................._.._....__......................................................._..........._.:............................................._........._.. 828-396-7903 11i. 828-396-8955 '1j. Telephone ........._ Facsimile ._...... ___................................ .......................... ..... ....-------E-mail.............__- ........ ..... _... .... _....... . _. (� 2. ...... Project (Facility) Information: _ _.__..................._._.................................................................... ....... _..................... ........................ a2a. ._....... ....................... ---... _.............................. ......... ......__..................... _......... .......................... ......... .. ... ............. _......... ..... .... .._ ............... Helena Street Area CDBG Sanitary Sewer Project 2b. Caldwell IL Brief Project Name (permit will refer to this name) County Where Project is Located Q 3 ... ... ...... .... ..... .- ............................. ....... . Contact Person: Q 3a. Benjamin B. Thomas, PE, West Consultants, PLLC - - - - i Name and Affiliation of Someone Who Can Answer Questir - ^ ,l) ;30. 828-433-5661 Phone Number (V '1. ?...._.............._ Project is ❑ New ® Modification of an existing 1 ( 9I W 2. .......... _.._....---- i2a. i Owner is 0 Public (skip to Item B(3)) Cj ... _... _...... If private, applicant will be: loose one) ❑ Retaining Ownership (i.e. store, church, single off, ❑ Leasing units (lots, townhomes, etc. - skip to Item) Aruction IV) ❑ Selling units (lots, townhomes, etc. - go to Item Bi 0 i3. City of Lenoir ® Owner of Wastewater Treatment Facility (WWTF) Tres' 4a. Gunpowder Creek Name of WWTF 0. Pa. i Cityof Lenoir 5b. 8" Z Owner of Downstream Sewer Receiving Sewi �.-��,rnrNumber of Downstream Sewer -- a6. The origin of this wastewater is (check all that apply): ® Residential Subdivision ❑ Car Wash W ® Apartments/Condominiums El Institution o ®Mobile Home Park 100 /o Domestic/Commercial ❑ Hospital a ❑ School ❑ Church % Industrial m i ❑Restaurant ❑ Nursing Home o Other (specify): El Office ❑/o Other (specify): (p ty) 7. Volume of wastewater to be permitted in this project: 49,610 gallons per day 8. If the permitted flow is zero, indicate why: ❑ Interceptor Line - Flow will be permitted is subsequent permits that connect to this line ! ❑ Flow has already been allocated in Permit No. ❑ Rehabilitation or replacement of existing sewer with no new flow expected 'PTA 01/01 FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 2 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2H .0219(I) for Item 13(7) or the design flow for line or pump station sizing if zero flow in the space below. Values other than that in 15A NCAC 2H .0219(1)(1-2) must be approved prior to submittal of this application. Submit a separate request to the Division of Water Quality, Non -Discharge Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617 in accordance with 15A NCAC 2H .0219(I)(3). (87) 3-bedroom houses @360 + (2) 2-bedroom houses @240 + (42) 1-bedroom apartments @120 + (58) 2-bedroom apartments @ 240 + garage with 2 employees @ 25 = 49,610 GPD I 3 10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary) Size (inches) 0 6 Length (feet) Gravity or Force Main _(pull down menu) 12,892 ............ Gravity ..........................._... _... _......................... 4,197 --....__.................__.......... __.._........... ..._ ... . Force Main ............ ................... ......................... ...................................... ........... Gravity ;............. _..... .:......_.......... _........... ....:..................... _............................ _... _..... _............. ........... Gravity ....... ............. .............. ........... :....................................... ..... ......... Gravity ...................... _._..... ................._... _... _._.................................... _...... ....:...................... ........... Gravity ....................................................... Gravity :............:................................... .......................... 3.24 ........_............ .......................... .............................. ...................., r 111. Summary of Pump Stations to be Permitted (attach additional sheets as necessary) ' Power Reliability Option Location ID Design Flow Operational Point (dual line feed, permanent generator WATS, Q ! (as shown on plans)] (MGD) i GPM @ TDH portable generator w/autodialer, wet well storage Z i H Pu....m .sation 0.288 20. .1,..3.....7... .. _........ .... _........... _......:.......................pranent generator w/ ATSm..__.........._...................... .......... _.._ W i i a 112. Does the sewer system comply with the Minimum Design Criteria for the Fast Track Permitting of Pump Stations and Force m. Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC 2H .0200 as applicable? ® Yes ❑ No If no, please reference the pertinent minimum design criteria or regulation and indicate why a variance is requested: :SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS PERTINENT TO THE VARIANCE WITH YOUR APPLICATION 13. Have the following s been submitted for approval? Wetland/Stream Crossings - General Permit or 401 Certification? ® Yes ❑ No ❑ N/A Sedimentation and Erosion Control Plan? ® Yes ❑ No ❑ N/A Stormwater? [:]Yes [--]No ® N/A PTA mini FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 3 1. Use the Division's guidance document entitled, "DETERMINING STREAM CLASSIFICATIONS FOR FORM FTA 02/03 Z (FAST -TRACK SEWER SYSTEMS)" to collect and record the stream classification data below (attach additional sheets as 0 necessary). This document is available from our web site or by contacting the appropriate Division of Water Quality regional office (see instructions for addresses) OR indicate the following: ❑ A Watershed Classification is not needed because all parts of the project are at least 100 feet away from any down slope waterbody; AND, L_L;._..._.........................................._....................._..................._..._.........................._......................................__.........................._........................................_........_............__._..................__.................................................__......:_....._.........._.............._..__.._............__.............__................._................__............... El Watershed Classification is not needed because the design does not depend on wet well storage as a power reliability option for any pump station near a Class C down slope waterbody. �n.......... _..... ............... _._---- ........ ......................_ ........................ ........................... _. Submit the 8.5" x 11" topographic map as required in Instruction VI regardless of whether a classification is provided! 11. Applicant's Certification: I attest that this application for Helena Street Area CDBG Sanitary Sewer Project has been reviewed by me and is accurate and complete to the best of my knowledge. I understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. ................... ... _.... ....... ..._. ... .. ... ......... ...... .... .1 a. Signing Official Signat re Date 2. Professional Engineer's Certification: 1 attest that this application for H elena Street Area CDBG Sanitary Sewer Project has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and F- all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the i proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria V_ for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump !L Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance. i Although certain portions of this submittal package may have been developed by other professionals, inclusion of these materials under my signature and seal signifies that I have reviewed this material and have judged it to be consistent with W the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who () knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 ................................................................................_............................_y......................................................................................._......_........................................................................... as civil penalties up to $25,000 per violation. misdemeanor which may include a fine not to exceed $10,000 as well 2a. Benjamin B. Thomas, P.E. Professional Engineer Name 2b. West Consultants Engineering Firm PLLC 2c. 405 S. Sterlina Street Address ....................__..........__..._.._.._............_- ..... _........... ._--. ,2d. Morganton City ._- ........... _....... - ............ =2g. 828-433-5661 Telephone 2e. NC '2f. 28655 State Zip --............_...._......._............... _.._... ..................... ... ._............ __..._................. _......... _.:.......... _....__............... __.. 828-433-5662 2i. benjiethomas@bellso Facsimile E-mail re & Date 3966 00 .12 50' 3965 II. IVfyTjponu II I I L I OeS S't ul:Q -64 RM =r U) La tc) �o 3962 ?00 '15 I uu 3961 47'3011 1 e— �k(s ITY OF L.EN01F% Post-itFax Note 7671 1Dat0,d/?P—t Mr. Bob Frye Town Arlmini Cnyca."M 0. L BEF94MARDT T W. EMOA CH 1. 1- 003; J. r OMME F. K. N=Af-' W.F. PME X 0. srMVIN, Town of Sawmills 4076 US Highway 321 -A Sawmills, North Carolina 28 0 Re: Wastewater Flow Alidcafion — CDBG Sanitary Sewer �roiect — Helena Street Area Dear Mr. Frye: I am writing to confirm that there is adequate capacity at the Chm powder Wastewater Treatment Plant to accept additional flow frain the Town of Sawmills per the existing contractual agreement. We will allocate 49,610 GPD (gallon�'per day) of wastewater fro Mi the project referenced as CDBG Sanitaxy Sewer eject Helena Street Area. If there are additional questiots, please contact my office. Sincerely, CITY OF LENOIR James H. Hipp City Manager JMKSM0 POST OFFICE a()X 0G8 LNO1R, NORM CAPtouNA 98848-0958i (age) 757-2200 TOTAL P.01 TOWN OF SAWMILLS GRANITE FALLS, NC 28630 10827 04/29/2003 SEWERPERM SEWER PERMIT 40000 0.00 400.00 CHECK: 010827 . 04/29/2003 NCDENR 400.00 �����`.0iw .. Y:5 Nt__. gel 3�9:.C.{ : (3»�® P L 8' b - b .6 ... C ... .'4.. �1 : •. •"-• � �- o��oF A�,���� 10827 N TOWN OF SAWMILLS FUM CA S GRANITE FALLS, 4076 US HWY 321A 396-7903 BANK NC 28630 NUMBER ' - GRANITE FALLS, NC 28630 010827 66-30/531 *FOUR. HUNDRED AND XX / 100 DATE AMOUNT 04/29/2003 * * * * * * *400.00* NCDENR (828) 433-5661 JOBNUMBER/PHONE To 4, Dzv. Of Water Quality (Asheville) �ATTENTION NCDENR 59 Woodfin Place RE Aslieviile NC 28801� Sawmills,�NC -Helena Street GDBG Sens t Change Order #'1 WE ARE SENDING YOU Attached — Under separate cover via the following items. Shop drawings — Prints Plans Specifications — Samples — Copy of letter Change order — Other: 2 2 1 THESE ARE TRANSMITTED as checked below: _x For your approval For your use As requested For review and comment Fast -Track Application For Gravity Sewers, Pump St Pump Station Calculations Plan Review Fee Approved as submitted Approved as noted Returned for corrections — Other MAY-62�1 Resubmit copies for approval Submit copies for distribution — Return corrected prints FOR BIDS DUE/DATE: 4/30/03 PRINTS RETURNED AFTER LOAN TO US REMARKS COPY TO SIGNED PRODUCT 13127T If enclosures are not as noted, please notify us at once. • FOLD AT (>) TO FIT COMPANION 777 DU-O-VUE ENVELOPE. PRINTED IN U.S.A. B TOWN OF SAWMILLS HELENA STREET AREA CDBG SANITARY SEWER PROJECT AMMENDMENT - IDLEWOOD DRIVE AREA PUMP STATION DESIGN CALCULATIONS April 11, 2002 BENJAMIN B. THOMAS, P.E. WEST CONSULTANTS, PLLC MORGANTON, NORTH CAROLINA WEST CONSULTANTS P«< I. DESIGN FLOW: A. PRESENT FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) B. FUTURE FLOW: TYPE OF UNIT 1-BDRM RES. UNIT 2-BDRM RES. UNIT 3-BDRM RES. UNIT BUSINESS (EMPLOYEES) CHURCHES(SEATS) RESTAURANTS(SEATS) SCHOOL WITH NO SHOWERS (STUDENTS) RETAIL (1,000 SQ. FT.) NO. UNIT FLOW TOTAL FLOW (GAUDAY/UNIT) (GAL/DAY) 42 120 5,040 �70 240 16,800 5 360 1,800 ,Q 25 0 p Og 3 0 0 40 0 12 0 120 0 TOTAL: 23,640 GAUDAY 16.42 GPM PEAK: 41.04 GPM NO. UNIT FLOW TOTAL FLOW (GAUDAY/UNIT) (GAL/DAY) 0 120 0 3 ` 4 240 0 300 360 108,000 z: 0 25 0 0 3 0 ..,0 40 0 12 0 120 0 TOTAL: 108,000 GAUDAY 75.00 GPM PEAK: 187.50 GPM II. SYSTEM CURVES: FORCEMAIN SIZE: 6" SDR21 I.D. = 5.955 INCHES EQUIVALENT LENGTH = G50MLF LOW WATER ELEVATION= MSL HIGH POINT= 1229 MSL STATIC HEAD= 115 FEET C = 120 C = 150 Q f Hf Hs TDH f Hf Hs TDH VELOCITY GPM FT/100FT FEET FEET FEET IFT/100FT FEET FEET FEET FPS 50 0.035 1.75 115.00 116.75 0.023 1.16 115.00 116.16 0.58 100 0.125 6.30 115.00 121.30 0.083 4.17 115.00 119.17 1.15 150 0.266 13.34 115.00 128.34 0.176 8.83 115.00 123.83 1.73 200 0.452 22.71 115.00 137.71 0.299 15.03 115.00 130.03 2.30 250 0.683 34.31 115.00 149.31 0.452 22.71 115.00 137.71 2.88 MIN. PRESENT PUMPING RATE: 41.04 GPM MIN. FUTURE PUMPING RATE: 187.50 GPM PUMP SELECTION: FAIRBANKS MORSE 4 435MU� 11 5'` +! IMPELLER, 1780 RPM S OPERATING CONDITIONS BASED ON C=120 (SEE ATTACHED CURVES): ONE PUMP ON 20p GPM @ 137 FT. TDH TWO PUMPS ON:!""'230'GPM @ nay_ 143 FT. TDH D5430 M&W Submersible Solids -Handling Pumps Basic Pump Dimensions 205 TOP VIEW OF PUMP UNIT L i 1_X 0 C O O _ T I I F2 F1 IF - - E C. - "G" WIDE 4 SLOTS FOR MOUNTING B OF BASE ELBOW BOTTOM VIEW OF ELBOW M TOP GUIDE BRACKET DETAIL 51 AA BRACKET FOR USE WITH 400 & 440 5 4 FRAME MOTORS I — AND 10" PUMPS T GUIDE RAILS 2° SCHEDULE 40 (3° FOR 400 & 440 FRAMES AND 10' PUMPS) PIPE BY OTHERS Ct DISCHARGE 1/a" DIA. !—AB 4 HOLES 213/is " �' y '—AA %' DIA. 2 HOLES 6Yz I ., —AB CID DI. WL (4) — - Y I — t + MW(5) SUCTION H(8) BOTTOM OF SUMP �e PUMP MOTOR DISCH A B C D E F1 F2 G H L W X Y AA AB CP HG MW OP WL 4°D5435MV 210T 4(9) 10 1155 23/s 63/a 4 1 7 1'/a 3 33�/a 10'/e 95/is 7�/s 3 3'/e 553/a gib 15'/a 15 33'/a 4°D5435MV 250T 4(9) 10 114a 23/a 63/a 4 1 7 1'/e 337% 107/e 96 7�/is 3 3'/s 59'/z '/s 15'/a 15 38'lz 4°D5435MV 320T 4(9) 10 115/a 2�a 63/a 4 1 7 11% 3 337/e 107/a 95/is 7�/is 3 3'/e 683/e �/e 15'/a 15 z 8°D5435MV 320T 8(11) 16 171A6 47/is 91/4 7 2% 10'A 1'/4 93/a 61% 21 19% 1211/16 3 31A 70 1'/4 241/z 19 453/4 8°D5435MV 360T 8(11) 16 171A6 47/is 91/4 7 27/a 101A 1'/a 93/4 61% 21 19Ys 1211/16 3 31/a 701/z 11/a 24'/z 19 473/4 8°D5435MV 365T 8(1 i 16 171A6 47/16 91/4 7 27A 10'/a 1'/4 93/a 615/a 21 193A 1211/,s 3 3'/s 72'/z 11/424Yz 19 493/4 8°D5435MV 400T 8(9) 301/2 341/4 65/e 123/a 14 4 25 11/a 3'/4 69 21 19% 1211/1s 11 8 RTF 13/4 24'/z 271/z RTF 8"D5435MV 440T 8(9) 301/2 341/4 6% 12% 14 4 25 11/4 3'/a 1 69 21 19% 1211A6 11 8 112 13/a 241/z 27'/2 71 10°D5435MV 360T 10(9) 301/z 341/4 611/1s 13% 14 4 25 11/a 5'/z 1741& 217A 201A6 133/a 11 8 855/a 13/4 27 33 621/z 10"D5435MV 400T .10(9) 301/z 341/a 6"/s 135/s 14 4 1 25 11/4 5'/z 1741A6 217A 20'As 133/4 11 8 115 13/4 27 33 74 NOTES: (1) DISCHARGE FLANGE IS 1259 ANSI DRILLING UNLESS NOTED. (n NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION PURPOSES UNLESS CERTIFIED. (2) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. DIMENSIONS SHOWN MAY VARY DUE TO NORMAL MANUFACTURING TOLERANCES. (3) 5400-S AND 5400K'S ARE DIMENSIONALLY IDENTICAL (8) DISTANCE REQUIRED FOR PROPER SUCTION CLEARANCE. (4) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. (9) IF RISER PIPE IS NOT SAME SIZE AS THE DISCHARGE ELBOW, AN ECCENTRIC INCREASER 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN MUST BE USED LIMITED TO TWO SIZES LARGER MAXIMUM. OPERATE CONTINUOUSLY AT'MW' WATER LEVEL (10) IF FUTURE CONSIDERATIONS REQUIRE CHANGING TO A 400 OR 440 FRAME MOTOR, (5) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR THE 400 OR 440 FRAME DIMENSIONS SHOULD BE USED. SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN (11) IF RISER PIPE IS NOT SAME SIZE AS THE DISCHARGE ELBOW, AN ECCENTRIC INCREASER CAN OCCUR OVER A PERIOD OF 15 MINUTES. MUST BE USED LIMITED TO ONE SIZE LARGER MAXIMUM. (6) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH UL LISTED GROUT OR A SOLE PLATE GROUTED IN PLACE. ISO-9001 CERTIFIED GSA CERTIFIED (rHRU 365 FRAME) CUSTOMER P.O. NO, ®Faiftnks Morse Pump JOB NAME TAG NAME BASIC PUMP PUMP SIZE AND MODEL GPM TDH RPM ROTATION D5435MV PULL-UP SUBMERSIBLE MOTOR HP FRAME PHASE HERTZ VOLTS ENCLOSURE FAIRBANKS MORSE MTR CERTIFIED FOR CERTIFIED BY DATE NOG 543MS013 No 5 8/1/97 Fairbanks Morse Pump D5430 M&W Submersible Solids -Handling Pumps 230 Setting Plans F2 T--- PLAN VIEW ACCESS COVER SUMP VENT GUIDE RAILS / 2' SCHEDULE 40 (3' FOR 400 & 440 FRAMES AND 10' PUMPS) PIPE BY OTHERS �. EFFLUENT PIPE LIFTING CABLE a, a a WL (5) rzl— POWER CABLE FLOAT CONTROL r IDE OPENING PUMP SUMP I.D. A B C D E F1 F2 4'D5432MV 60 30 42 11 21 15 10 10 4'D5433MV 60 30 48 11 24 15 11 11 6'D5433MV 72 36 60 113/4 30 17 13 13 4'D5434MV 66 42 54 13 27 18 13 13 6'D5434MV 96 42 76 21 38 261/4 18 18 8'D5434SMV 2 84 40 68 20 34 261/2 131/z 8'D5434LMV(3) 96 48 72 24 36 30�/z 18 18 4"D5435MV 6018 30 22 12 128"D5435MV �72; 86 201/z 43 27 20 20 10"D5435MV 88 22 44 3G% 221/z 22'/z 5'D5436MV R.T.F. 8'D5436SMV R.T.F. 400 & 440 FRAME PUMPS REQUIRING HEAVY DUTY ELBOWS PUMP SUMP I.D. A I B I C I D I E F1 F2 8'D5435MV 108 66 1 90 122%1 43 1 21 5'D5436MV R.T.F. 8'D5436LMV R.T.F. �- LIFTING BAIL MW(6) NOTES: (1) ALL DIMENSIONS ARE IN INCHES UNLESS NOTED. (7) BASES ARE DESIGNED TO HAVE FULL CONTACT WITH (2) FOR USE WITH IMPELLER DESIGN T8D1 A. GROUT OR A SOLE PLATE GROUTED IN PLACE. (3) FOR USE WITH IMPELLER DESIGNS T8D1 D OR TAKC5W. (8) NOT FOR CONSTRUCTION, INSTALLATION, OR APPLICATION (4) 5400'S AND 5400K'S ARE DIMENSIONALLY IDENTICAL PURPOSES UNLESS CERTIFIED. DIMENSIONS SHOWN MAY (5) RECOMMENDED LOW WATER LEVEL FOR CONTINUOUS OPERATION. VARY DUE TO NORMAL MANUFACTURING TOLERANCES. 210 FRAME AND WATER JACKETED 250 THRU 440 FRAME UNITS CAN (9) REFER TO BASIC PUMP DIMENSION DRAWING FOR WL AND OPERATE CONTINUOUSLY AT "MW" WATER LEVEL MW DIMENSIONS. (6) WATER LEVEL MAY BE DRAWN DOWN TO THIS LEVEL FOR SHORT TIME DUTY IN AIR MOTOR RATINGS. DRAW DOWN CAN OCCUR OVER A PERIOD OF 15 MINUTES. DUPLEX IN -LINE, D5430MV, SUBMERSIBLE PULL-UP Ol a banksMorsePump SINGLE DOOR ACCESS COVER 543M---- No 3 NOG Fairbanks Morse Pump 8/1/97 III. WETWELL DESIGN: A. DETERMINE OPERATING VOLUME: PRESENT: T =3Q MINUTES (7.5 TO 30) Qddf = 16.42 GPM Q = 200 GPM V = 452.07 GAL. B. SELECT WETWELL DIMENSIONS: DIAMETER: FEET WETWELL DEPTH = PRESENT CONDITIONS:. OPERATING DEPTH: 2.14 FEET TOP ELEV f4P1� 312�1 0£3 GROUNDt1205a LOWEST SEWER IN = LAG PUMP ON = 1114.52 ALARM = 1114.02 LEAD PUMP ON = 1113.52 PUMPS OFF = 1111.38 BOTTOM = 1107.88 FUTURE: T `;3 _ °90+MINUTES (7.5 TO 30) Qddf = 75.00 GPM Q = 200 GPM V = 468.75 GAL. 13.12 FEET FUTURE CONDITIONS: OPERATING DEPTH: 2.22 FEET TOP ELEV = 1121.00 GROUND = 1120.50 LOWEST SEWER IN = 1115.10 LAG PUMP ON = 1114.60 ALARM = 1114.10 LEAD PUMP ON = 1113.60 PUMPS OFF = 1111.38 BOTTOM = 1107.88 DEPTH REQUIRED FOR PUMP PROTECTION: FEET PRESENT CONDITIONS CYCLES PER HOUR: 2.0 FUTURE CONDITIONS CYCLES PER HOUR: 6.0 C. CHECK FLOTATION: 1. BUOYANCY = SUBMERGED VOLUME X 62.4 PCF: WETWELL I D. F �_ZI600 FEET WETWELL O.D. 7.00 FEET SUBMERGED DEPTH: 13.28 FEET BUOYANCY: 31,898 LBS. 2. WEIGHT OF WETWELL: TOP = 9.00 INCHES AND 3,876 LBS. RISER = 11.87 FEET @ 1910.00 LBSNF = 22,665 LBS. BOTTOM = 8.00 INCHES AND 3,850 LBS. TOTAL = 30,391 LBS. FACTOR OF SAFETY = 0.95 NO GOOD EXTENDED BASE SLAB IS REQUIRED BASE SLAB EXTENSION = 8.0 INCHES HEIGHT OF SOIL = 12.62 FEET WET SOIL WT.(50PCF) = 10,102 LBS. THEN TOTAL RESISTANCE TO UPLIFT = 40,492 LBS. FACTOR OF SAFETY = 1.27 OK V = T Qddf 1 - Q V = active volume within the pump station (gallons) T = allowable cycle time between starts (minutes) Qddf = design daily flow to pump station (gallons per minute) Q = pumping rate of a single pump (gallons per minute) WETWELL DATA PER TINDALL CONCRETE G-SERIES DIA. O.D. WEIGHTS HEIGHT (INCHES) EXTENDED BASE (FT) (FT) O.D. (FT) RISER (LBNF) BASE (LB)* TOP (LB) I BASE TOP 4.0 4.83 915 1375 1242 6 8 5.83 5.0 5.83 1370 2600 2773 8 9 7.17 6.0 7.00 1910 3850 3876 8 9 8.33 7.0 8.17 2207 5240 7625 8 16 9.33 8.0 9.33 2879 6840 8689 8 16 11.00 10.0 11.67 4481 12030 14312 9 16 14.00 * BASED ON BASE AREA X HT X 150 PCF - ' -------- ---- _----- .____' 2:7 � f- --`---��/-V-~ 7 -S-5-\� _ � � T} n Michael F. Easley, Governor William G. Ross Jr., Secretary �y North Carolina Department of Environment and Natural Resources Alan W. Klimek, P.E. Director Division of Water Quality December 1, 2003 Town of Sawmills Eric Davis 4076 US Hwy 321-A Granite Falls, NC 28630 Subject: Engineer Certification WQ0017555 Sawmills Town -City Of Lenoir Caldwell County Dear Mr. Davis The Division's Non -Discharge Permitting Unit has received the signed and sealed Engineering Certification required for compliance with the subject permit and 15A NCAC 2H .0220. Please note that any record drawings and other supporting documents submitted will be forwarded to the appropriate regional office along with a copy of the certification. Please keep this letter and Engineering Certification with your subject permit/record drawings file. If you have any questions regarding this letter, please contact Division of Water Quality Asheville Regional Office. Sincerely, 4" �) •.4..,) Glenda M. Rouse Enclosur cc: Asheville ReI", Ullater Quality Section Central Files West & Associates O N@N0WC DEC I ' 1203 1 J 6NAT 77R 01JALITY SECTION Non -Discharge Permitting Unit 1617 Mail Service Center Raleigh, NC 27699-1617 Customer Service Phone (919) 733-5083 Fax (919) 715-6048 Internet http://h2o.enr.state.nc.us/ndpu NCDENR 623-7748 Permit No. WQ0017555 DYcember 29, 1999 ENGINEER'S CERTIFICATION RECEIVED WATFR 011A1 ITY SFCTION ti 2 J hlorg)1scherge� Pemr�i ng Partial ��� Final I, h (� M ` /1 T601Q S , as a duly registered Professional Engineer in the State of North Cdrblina, laving been authorized to observe er lica`.l�veekly, full�ti e) the construction of the project, CLtiu �n.t (i s L�a'tvir T � r ;tiyi z LF ,��2� /D u-o G•P gum r/s Project Namel Location a d County for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance and intent of this permit, the approved plans and specifications, and other supporting materials. `J '�-757 Signature , Registration No. o�6oeeasestrp� Date %�'/GAL- �2,C�6 *,%,, Ce�6ItiH}� wdO knmsc'k SEAL 2075m , The Division of Water Quality hereby acknowledges receipt and acceptance of this Engineers Certification 4 WESvi TiANDASSOCIaTES,; P A'. Consultmg`Engineers „ z ?- a1til=Sfp..Wli'i ff �f'rPPt�,.�, �:'`<•�. -,. -... r.� �. <'r. Spa. a r ,t_`, .... NCDENR f Wate1 Quality Section J w Permits` & 4Engineeririg Unit { ter, ,t 617 -Maa l ,Service Center\ # Rale�.ghNG„ 5�27699 d 'd i JUMBEWP, HONE VTION £ �wmz?lls,',,NC� w Sawmills/Lenoir � � iterconn'ect Pro-ect ' i i 4 3 t Pt § 5 k j Si+. -3� �, i $•.,± vt } v i'j % � $'i f t'J ., <.�f" t �kiR .'$< r WE ARE SENDING YOU — Attached — Under separate cover via the following items. Shop drawings — Prints — Plans — Specifications Samples —Copy of letter Change order Other: COPIESD. DESCRIPTION 1 Engineer's Certification THESE ARE TRANSMITTED as checked below: X For your approval Approved as submitted — For your use Approved as noted — As requested — Returned for corrections For review and comment — Other FOR BIDS DUE/DATE: REMARKS RECEIVED' WATER DUALITY SECTION Jib 2 2Q` NorgNset arge Permitting Resubmit copies for approval Submit copies for distribution — Return corrected prints _ PRINTS RETURNED AFTER LOAN TO US COPY TO SIGNED H enclosures are not as noted, please notify us at once. • PRODUCT 13127T FOLD AT (>) TO FIT COMPANION 771 DU-O-VUE ENVELOPE. PRINTED IN U.SA B 1156 WEST CONSULTANTS, PLLC Consulting Engineers 405 South Sterling Street MORGANTON, NORTH CAROLINA 28655 Phone (828) 433-5661 Fax (828) 433-5662 TO Div. Of Water Quality (Asheville) NCDENR 2090 US Hwy 70 Swannanoa NC 2MM WE ARE SENDING YOU X Attached Under separate cover via Shop drawings Prints Plans Copy of letter Change order Other: JOB NUMBER/PHONE DATE 20032 3/29/2004 ATTENTION RE: Town of Sawmills / Caldwell County, NC Helena Street Area CDBG Sanitary Sewer Project the following items. Specifications Samples COPIES DATE NUMBER DESCRIPTION 1 As -Built Drawings 1 Engineer's Certification - WQ0021309 1 Engineer's Certification - WQ0022566 1 Pump Station Design Calculations (4/11/02) THESE ARE TRANSMITTED as checked below: For your approval Approved as submitted Resubmit copies for approval X For your use Approved as noted Submit copies for distribution As requested Returned for corrections Return corrected prints For review and comment Other FOR BIDS DUE/DATE: PRINTS RETURNED AFTER LOAN TO US REMARKS 1 MAR 3 1 WATER QUALITY SECTION ASHEVILLE REGIONAL OFFIC COPY TO File If enclosures are not as noted, please notify us at once. PRODUCT 13127M USE WITH 771 ENVELOPE NEBS To Reorder. 1-800-225-6380 or www.nebs.com SIGNED PRINTED IN U.S.A. A • n q-t l STATE OF NORTH CAROLINA DEPARTMENT OF TRANSPORTATION MICHAEL F. EASLEY LYNDo TIPPETT GOVERNOR SECRETARY April 2, 2004 Mr. Jim Reid Division of Water Quality Asheville Regional Office 2090 US Highway 70 Swannanoa, North Carolina 28778 REF: NCDOT Project 8.1731701 (R-4064) F.A. Project STP-321A(2) Sawmills — Intersection of US 321A and SR 1108 (Mission Rd) East of US 321A and SR 1130 (Cajah Mountain Rd) Caldwell County Dear Mr. Reid, Attached are one (1) original and one (1) copy of the completed application form for installation of the. proposed wastewater facility on the above highway project. This facility is owned by the Town of Sawmills and is to be constructed as part of the highway contract. We respectfully request your review and approval. Enclosed is a check in the amount of $400.00 for the permit application fee. If we can be any further assistance, please advise. RB W/vm Attachments MAILING ADDRESS: NC DEPARTMENT OF TRANSPORTATION DESIGN SERVICES UNIT 1591 MAIL SERVICE CENTER RALEIGH NC 27699-1591 S' erely, #B. Wilkins, PE Utilities Squad Leader TELEPHONE: 919-250-4128 FAX: 919-250-4119 WEBSITE. WWW.DOH.DOT.STATE.NC.US LOCATION: CENTURY CENTER COMPLEX ENTRANCE B-2 1020 BIRCH RIDGE DRIVE RALEIGH NC 27610 WEST CONSULTANTS, PLLC Consulting Engineers 405 South Sterling Street MORGANTON, NORTH CAROLINA 28655 Phone (828) 433-5661 Fax (828) 433-5662 TO NC Division Of Water Quality (Asheville) Asheville Regional Office 2090 US Highway 70 Swannanoa NC 28778 WE ARE SENDING YOU X Shop drawings Copy of letter Attached Under separate cover via Prints Plans Change order Other: 1305 JOB NUMBER/PHONE Kevin Barnett RE: Sawmills, NC - Cajah's Mountain/Mission Road Wasteawater Facility the following items. Specifications Samples COPIES DATE NUMBER DESCRIPTION 1 Letter from NCDOT 2 on -Discharge Permit Application 1 03/31/04 L590630 Check For $400.00 THESE ARE TRANSMITTED as checked below: X For your approval Approved as submitted For your use Approved as noted As requested Returned for corrections .For review and comment Other FOR BIDS DUE/DATE: REMARKS Revised applications as per your letter of April 13, 2004. Resubmit copies for approval Submit copies for distribution Return corrected prints PRINTS RETURNED AFTER LOAN TO US COPY TO If enclosures are not as noted, please notify us at once. PRODUCT 13127M USE WITH 771 ENVELOPE NEBS To Reorder: 1-800-225-6380 or www.nebs.com SIGNED PRINTED IN U.S.A. A .a FAST -TRACK APPLICATION REVIEW PROCEDURES Project Name: Review Date: _541D Project Number: AIC'o 1A fl&-d $'a l7317O I CR-W b-4) Reviewer:. , All fast -track projects should be submitted on the application entitled "Fast -Track Application for Gravity Sewers, Pump Stations, and Force Mains" (FORM: FTA 02/03 currently) unless otherwise directed by the NDPU. Any pump station/force main projects that require an Environmental Assessment (EA) are excluded from the Fast -Track review process, and should be submitted for full review to the Central Office (NDPU) on FORM: PSFMGSA 10/99. Additionally, any projects involving a flow reduction request must receive approval for the flow reduction from the central office. PRE -REVIEW a/REDoes the application package appear to be generally complete (i.e. all attachments, check, key questions answered)? If any portion of the application is not complete, or if any required instruction items have been omitted, RETURN the application package and supporting documents to the applicant using the Project Return Letter template. Send the package and letter via certified mail to the applicant, and a copy of the letter to the engineering consultant. Any projects that are to be returned shall be returned prior to accepting the application (i.e., before logging in the application and depositing the check). After a project has been accepted, any information that is found to be incorrect and/or lacking must be requested via an Additional Information. Request in accordance with 15A NCAC 2H .0208(e). _k/Ensure that a check for $400 is submitted and made out to NCDENR. All new projects and major modifications to existing projects require an application fee. A major modification includes any changes to permitted flow volumes, changes in pipe diameter, changes in pipe length greater that 10% of the originally permitted length, changes in the operating points of a pump station, etc. SECTION A — Application Information / If the applicant is private (Item B(2)) and listed as a corporation, check the NC Department of the Secretary of State's web site at http://www.secretary.state.nc.us/Corporations/ to ensure that the Applicant is registered with the Secretary of State to conduct business as a corporation in the / State of NC. Developer's and HOA's should be listed. Ensure that the signing official meets the requirements of 15A NCAC 2H .0206(b). If they do not, request a revised application that has been completed by an appropriate official or a letter from an appropriate official that indicates the person in question is delegated to sign the application on the applicant's behalf. A current list of Delegated Signing Officials can be obtained from the DWQ Intranet. If a new delegated signing official letter is presented with the application, forward a copy to the central office so that the person may be added to the Delegated Signing Official list. The central office will send E-mails to the appropriate region if a new signing official has been added so that the most current list can be used. The Non -Discharge Permitting Unit has an example delegated signing official letter from http://h2o.enr.state.nc.us/ndpu/spraypol.htmI#DELEG. SECTION B — Permit Information V" Project is new? Modification? If the project is a modification to an existing permit, be sure to enter the application into BIMS as a permit modification (i.e. "renew/modify application" and not "create new project") . Applicant a public entity (e.g. county, town, sanitary district)? 1 FAST -TRACK Application Review Procedures 2003 " Applicant a private entity? Own (i.e. lease) units, lots, parcels, etc? Sell units, lots, parcels, etc? Certificate of Public Convenience and Necessity? 2H .0205(d)(2) ♦ Required if the applicant is a public utility. In lieu of a Certificate of Public Convenience and. Necessity, they may submit written approval from the North Carolina Utilities Commission's Public Staff that states that the utility is allowed to provide utility service in the subject project area. Note that the project name on the application and on the CPCN must match. Contact the NCUC Public Staff if questions arise. Operational Agreement? 2H .0205(d)(2) ♦ Operational Agreements are only required if the applicant is not a public entity (i.e. Town, County, etc.) or public utility as designated by the North Carolina Utilities Commission AND the lots being served by the collection system are to be sold to individual owners. ♦ If the applicant is a developer, they must fill out the DEVELOPER Operational Agreement (FORM: DEV 02/03). A developer may be responsible for the system for an interim period until the homeowners association is formed, at which time a Permit Name/Ownership Change request (FORM: PNOCF 06/00) will be needed to transfer the permit to the HOA. ♦ If the applicant is a homeowners' association (HOA), they must fill out the ASSOCIATION Operational Agreement (FORM: HOA 02/03 The HOA must be registered with the Secretary of State's office and must provide a copy of the Associations' Bylaws and Articles of Incorporation. These documents. should be reviewed to ensure that all applicable language regarding the collection system is included as is required by the Operational. Agreement. ♦ The Operational Agreement should be attached to the permit and incorporated into the language of the permit. Please note that Operational Agreement language should not be altered without approval from the Attorney General's Office. Operational Agreements are available at http://h2o.enr.state.nc.us/ndpu/ndpuapps.html. Approval of flow to receiving sewers and WWTF? (i.e. P4 procedure, but now in-house!) ♦ Ensure that the receiving sewers and WWTF have adequate capacity available to accept the flow volume that is being requested, and that the WWTF has been in compliance with their treatment and disposal permit. Flow acceptance letter(s) from the owner of the WWTF and owner of any intermediate sewers (if different from WWTF owner and applicant)? 2H .0205(d)(3)(C) ♦ Required only if the applicant and the owner of the WWTF/intermediate sewers are not the same entity. ♦ Project specific flow acceptance letters are required. ♦ Ensure that the following items appear in the flow acceptance letter: applicant's name, project name, amount of wastewater flow accepted, date that the flow acceptance was granted, expiration date of the acceptance, and name/permit number of the receiving WWTF. Do not accept a flow acceptance letter that was issued more than one year prior to the receipt of the package. ♦ Ensure that the owner accepted the entire. volume of flow listed in application. Wastewater industrial or domestic in nature? ♦ Most projects will be for wastewater that is domestic in nature, however, if Item B.6 indicates that the wastewater is industrial in nature, notify the Regional. Office Pretreatment Coordinator or the WQ Pretreatment Unit Central Office to determine if a pretreatment permit is needed or if a program already in place and compliant. 2 FAST -TRACK Application Review Procedures 2003 Flow volume calculated correctly? 2H .0219(l) ♦ Ensure that the daily design flow in the application is based on the guidance provided in the regulations or existing flow, and that the explanation as to how this volume was determined is very specific (i.e., 22 three -bedroom homes, 50,000 s.f. of retail space, 18 employees, etc). This information will be included in the description of the system in the permit. Our regs say 120 gpd/bedroom for residential. Note that for one -bedroom the minimum they can. use is 240 gpd.. ♦ If daily design flow is not based on regulations, ensure that the applicant has an approved flow reduction of daily design flow rate on file with the Division. A list of approved flow reductions may be obtained from the DWQ Intranet or by contacting the NDPU. Flow reduction requests.are to be reviewed by the central office, and must be reviewed and approved before the application is accepted by the regional office for review. ♦ Ensure that the flows shown on the application match up to what is shown on the plans (if available for review). For example, if the application states that 100 lots are to be developed, ensure that there are 100 lots, and not 150 lots, shown on the plans. Plans are only required for review if the applicant is requesting a variance to the MDC or the .0200's. ♦ Do not approve "future" wastewater flows (i.e., that based on speculative development). These would be permitted in future wastewater collection system extensions. Adequate information provided regarding the proposed gravity sewer and/or force main (if applicable)? Note: An Environmental Assessment may be required if there are 3 miles of gravity sewer and the design capacity is 1 MGD or greater (15A NCAC 1 C .0100). Note that this criteria is currently under revision. Environmental Assessment projects can NOT go Fast -Track! Adequate information provided regarding the proposed pump station(s) (if applicable)? Note: An Environmental Assessment may be required if the pump station(s) have a design capacity greater than 1 MGD or greater (15A NCAC 1 C .0100). If there are any questions about whether an EA may be required, discuss with your supervisor or contact Todd Kennedy of the Planning Branch's Local Government Assistance Unit. ♦ Power reliability at the pump station provided in accordance with Section 5.04 of the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains document (i.e dual line feed, portable generator w/telemetry, permanent generator with automatic transfer switch, wet well storage if near Class C waters)? Project designed in accordance with 15A NCAC 2H .0200, the Gravity Sewer Minimum Design Criteria and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains document (as applicable)? If NO, forward one copy of the supporting documents to the Central Office for review, indicating the permit number, owner and protect name. The Central. Office will review the variance request, and if approvable, specific language regarding the variance will be forwarded to the Regional Office reviewer to incorporate into the permit. A copy of the variance letter provided by the central office should be kept with the application file. SECTION C — Watershed Classification Topographic map submitted? Watershed classification required? If YES, you are advised to "spot-check" the classification(s). If NO, ensure the applicant/engineer has indicated why one is not required. SECTION D —Certifications Signing Official's signature? 2H .0206(b) ♦ Ensure that the applicant's signature is the same person as that listed as the applicant's signing official on Page 1 of the application form. PE stamped, signed, and dated application, plans, specifications, and calculations (if applicable)? 2H . 0205(d) (1) (A) (M) FAST -TRACK Application Review Procedures 2003 v Ensure that the same engineer has signed, sealed, and dated the application and all the items, with the exception of items designed by specialty disciplines (i.e., architectural, structural, plumbing, and electrical plans). If not, an explanation and/or authorization is. required. Adequate information provided for the engineer/engineering firm? PE with active license in North Carolina? 2H .0205(d)(1)(A)(id) or 2H .0203(28) ♦ Ensure. that ALL pertinent P.E.s have active licenses by checking the NC Professional. Engineer's Board web site (www.ncbels.org - the PE number must be six digits, use leading 0 when needed). ♦ If the PE seal number does not show up on the web site database, call the PE Board for verification (919) 881-2293. Drafting a Permit ♦ In order to be consistent, use the most current version of the Fast -Track permit shell (see DWQ Intranet). This permit shell contains specific language with respect to the Minimum Design Criteria, regulations, and collection system permitting. The NDPU will notify you of any changes to this permit shell. ♦ Be. specific with respect the system description and information. Indicate the flow, what the project will be serving, length and size. of gravity sewer lines and force mains, etc. For projects involving pump stations, the size of the pump stations, as well as the reliability option and any additional info (telemetry, odor control system, etc) should be included. A sample permit is on the DWQ Intranet. ♦ Add or remove any special conditions, as necessary. Please call attention to any non-standard permit conditions in the cover letter of the permit and include the permit condition where necessary. See the Example Special Conditions document.. ♦ If the project is a modification, don't forget to include the system description from the previous permit and void the previous permit in the language!. Denying a Project ♦ If the Reviewer/Supervisor determines that an application package should be denied because it can not meet NC Statutes, rules or regulations, then a denial letter should be drafted. Special attention should be paid to the statutory deadline for permitting. If it is thought that a project might be denied, it is important to review it and draft the denial letter as soon as possible. There must be time allowed for the denial letter to be sent up to the Director and signed prior to the statutory date. ♦ The Reviewer should use the Application Denial Letter template to prepare a denial package for the Supervisor's review and submittal to the Director for signature. The letter should not be dated, but instead will be dated after the Director signs it. A memo to the Director should be attached to the top of the denial package summarizing the reasons for denial. This package must be singed off on by the reviewer, supervisor, Section Chief, and. Director. Distribute the letter as directed in "Issuing a Permit" below. Issuing a Permit ♦ Permits should be signed only by those delegated to sign for the Director. ♦ Permits should be distributed as follows (include the signed Operational Agreement if applicable): ✓ Original to the Permittee ✓ Copy to the consulting engineer ✓ Copy to the county health department ✓ Copy to the Mecklenburg County Department of Environmental Protection for all projects located in Mecklenburg County ✓ Copy(ies) to the owner of the WWTF and owner of the downstream sewers (if different than the Permittee) ✓ Electronic Copy and Hard Copy to the NDPU for our files ✓ Copy to Central Files (attach application package and any supporting documents) ✓ Save an electronic version named WQOOXXXXX.doc in a folder on your office shared drive or hard drive. Try to keep your drafts and issued files separate. 4 FAST -TRACK Application Review Procedures 2003 STATE OF NORTH CAROLINA DEPARTMENT OF TRANSPORTATION MICHAEL F. EASLEY GOVERNOR April 2, 2004 Mr. Jim Reid Division of Water Quality Asheville Regional Office 2090 US Highway 70 Swannanoa, North Carolina 28778 LYNDo TIPPETT SECRETARY REF: NCDOT Project 8.1731701 (R-4064) F.A. Project STP-321A(2) Sawmills — Intersection of US 321A and SR 1108 (Mission Rd) East of US 321A and SR 1130 (Cajah Mountain Rd) Caldwell County Dear Mr. Reid, Attached are one (1) original and one (1) copy of the completed application form for installation of the proposed waste water facility on the above highway project. This facility is owned by the Town of Sawmills and is to be constructed as part of the highway contract. We respectfully request your review and approval. Enclosed is a check in the amount of $400.00 for the permit application fee. If we can be any further assistance, please advise. RB W/vm Attachments MAILING ADDRESS: NC DEPARTMENT OF TRANSPORTATION DESIGN SERVICES UNIT 1591 MAIL SERVICE CENTER RALEIGH NC 27699-1591 S' erely, #B'Wilkins, PE Utilities Squad Leader TELEPHONE: 919-2504128 FAX: 919-250-4119 WEBSITE. WWW.DOH.DOT.STATE.NC.US LOCATION: CENTURY CENTER COMPLEX ENTRANCE B-2 1020 BIRCH RIDGE DRIVE RALEIGH NC 27610 FAST TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 1 OF W ATF9 State of North Carolina `0� QG Department of Environment and Natural Resources r Division of Water Quality o c FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS (Pressure sewers systems are not to be included as part of this application package) INSTRUCTIONS: Indicate that you have included the following list of required application package items by checking the space provided next to each item. Failure to submit all required items will lead to your application being returned as incomplete or additional processing and review time. This form may be photocopied for use as an original. [}2I. Application Form - Submit one original and one copy of the completed and appropriately executed application form. Any changes to this form will result in the application being returned. The Division of Water Quality (Division) will only accept application packages that have been fully completed with all applicable items addressed. You do not need to submit.detailed plans and specifications unless you respond NO to Item B(12). Wf II. Application Fee - Submit a check in the amount 'of $400 made payable to: North Carolina Department of Environment and Natural Resources (NCDENR). ❑ III. Certificates of Public Convenience and Necessity If the application is being submitted in the name of a privately -owned public utility, submit two copies of the Certificate of Public Convenience and Necessity (CPCN) which demonstrates that the public utility is authorized to hold the utility franchise for the area to be served by the sewer extension. If a CPCN has not been issued, provide two copies of a letter from the North Carolina Utilities Commission's Public Staff that states that an application for a franchise has been received, that the service area is contiguous to an existing franchised area; and/or that franchise approval is expected. The project name in the CPCN or letter must match that provided in Item A(2a) of this application. ❑ IV. Operational Agreements — Submit one original and two copies of a properly executed operational agreement if the sewer extension is permitted by a private applicant and will be serving residential or commercial lots (e.g., houses, condominiums, townhomes, outparcels, etc.) that will be sold to another entity. If the applicant is a homeowners' association, use .Form HOA 02/03. If the applicant is a developer, use Form DEV 02/03. EVEN IF THE PROJECT WILL BE TURNED OVER TO A MUNICIPALITY, FORM DEV 02/03 IS REQUIRED. ❑ V. Flow Acceptance Letters — If the owner of the downstream. sewers and/or WWTF is different from the applicant, submit two copies of a flow acceptance letter from the owner of the downstream sewers and WWTF, if different. Flow acceptance letters must contain the following minimum information: applicant and project name, amount of flow accepted, and name and permit number of the receiving sewers/WWTF. The flow acceptance must not expire prior to permit issuance and must be dated less than a year prior to the application date. Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific flow acceptance letter. E411. Map — Submit an.8.5-inch by 11-inch COLOR copy of the portion of a 7.5-minute USGS Topographic Map along with this form. The map should identify the entire project area location as well as the closest downslope surface waters as clearly as possible. Each map portion must be labeled with the map name and number, the identified location of the sewer line and pump stations, and be of clear and reproducible quality. For instance, if the project involves 4 miles of interceptor sewer that traverses over or near several different waterbodies (or counties, basins, etc.), the map should have location ID's shown for each different waterbody (where the sewer line is within 100 feet of such waterbody - see Instruction VII). This location ID is self chosen and used to cross reference the location in Section 'C of the permit application. ❑ `VII. Stream Classifications — Section C • If any portion of the project is within 100 feet of any down slope surface water, Section C must be completed for the pertinent sections. • If the entire project area is a minimum of 100 feet away from any down slope surface waters BUT there is a pump station involved where a history of power outage is to be used to provide adequate design storage instead of dual feed or permanent or portable generator, Section C must be completed to demonstrate that the closest down slope surface water is Class C (see 15A NCAC 2H .0219(h)(3)(D)). • Use the guidance document entitled, "Determining Watershed Classifications for Form FTA 02/03 (Fast -Track Sewer Systems)" available from http://h2o.enr.state.nc.us/ndpu or by contacting the appropriate regional office. TT A All in, T __. 1 n/ /n,) - 'FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 2 ❑ VIII. Environmental Assessments — If this project is subject to an Environmental Assessment (EA) [15A N.CAC 01C .0500],, this application can not be used. Send the project application on Form PSFMGSA.10/99 to the Non -Discharge Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617. Applications can not be processed until a Finding of No Significant Impact (FONSI) or Environmental Impact Statement (EIS) has been issued. A copy is to be submitted with that permit application. IX., Certifications — Section D The application must be certified by both the applicant and a North Carolina Registered Professional Engineer (PE). The applicant signature must match the signing. official listed in Item A(1b). The PE should NOT certify the application if he/she is unfamiliar with 15A NCAC 2H .0200, the Gravity Sewer Minimum Design Criteria (most recent version) and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (most recent version), as applicable to the project. Certification by a PE who is unfamiliar with these documents is subject to NC Board referral. THE COMPLETED FTA 02103 APPLICATION PACKAGE, INCLUDING ALL SUPPORTING DOCUMENTS AND $400 FEE, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE `.REGIONAL OFFICE ADDRESS COUNTIES SERVED Asheville Regional Office Avery, Buncombe, Burke, Caldwell, 59 Woodfin Place Cherokee, Clay, Graham, Haywood, Asheville, North Carolina 28801 Henderson, Jackson, Macon, (828) 251-6208 Madison, McDowell, Mitchell, Polk, (828) 251-6452 Fax Rutherford, Swain, Transylvania, Yancey Fayetteville Regional Office 225 Green Street Suite 714 Fayetteville, North Carolina 28301 Anson, Bladen, Cumberland, Harnett, (910) 486-1541 Hoke, Montgomery, Moore, Robeson, (910) 486-0707 Fax Richmond, Sampson, Scotland Mooresville Regional Office 919 N Main Street Mooresville, North Carolina 28115 Alexander, Cabarrus, Catawba, (704) 663-1699 Cleveland, Gaston, Iredell, Lincoln, (704) 663-6040 Fax Mecklenburg, Rowan, Stanly, Union Raleigh Regional Office 1628 Mail Service Center Chatham, Durham, Edgecombe, Raleigh, North Carolina 27699-1628 Franklin, Granville, Halifax, Johnston, (919) 571-4700 - Lee, Nash, Northampton, Orange, (919) 571-4718 Fax Person, Vance, Wake, Warren, Wilson Washington Regional Office Beaufort, Bertie, Camden, Chowan, 943 Washington Square Mall Craven, Currituck, Dare, Gates, Washington, North Carolina 27889 Greene, Hertford, Hyde, Jones, (252) 946-6481 Lenoir, Martin, Pamlico, Pasquotank, (252) 975-3716 Fax Perquimans, Pitt, Tyrrell, Washington, Wayne Wilmington Regional Office 127 Cardinal Drive Extension Wilmington, North Carolina 28405 Brunswick, Carteret,. Columbus, (910) 395-3900 Duplin, New Hanover, Onslow, (910) 350-2004 Fax Pender Winston-Salem Regional Office 585 Waughtown Street Alamance, Alleghany, Ashe, Caswell, Winston-Salem, North Carolina 27107 Davidson, Davie, Forsyth, Guilford, (336) 771-4600 Rockingham, Randolph, Stokes, (336) 771-4631 Fax Surry, Watauga, Wilkes, Yadkin For more information, visit our web site at: http.11h2o.enr.state.nc.us/ndpu/ rm a nn in' "_ 1 nc inn DESIGN SERVICES 9192504119 04/20 '04 13:37 N0.588 02/03 !FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 3 USE THE TAB KEY TO MOVE FROM FIELD TQ FIELDI Application Number.w =- . (to he corn leted b i 7 _ Owner..._------------t a y Dom` 9 GO s. Town of Sawmills-- —1— z 0 0 IL z 0 Ci CL J a O F_ IM 0 IL z H a M Full Legal (company, municipality►, I 1b. Mr. Robert A. FrVe. Jr. Town Administrator Signing Official Name and Title (Please review I SA NCAC 2H A2W(b) for '1c� The legal entity who will own this system is: �] Individual D Federal Municipality El StatelCounty Q Private Partnership Corporation Other (specify►): 1d. 4076 US Hwy 321A Ie: Granite Falls Street Address e _City 1f North Caroiina .1g. ___._._ state ---- _ Zip Code lb. 828 398 - 7903 Telephone Facsimile 2.Prvect (Faallfiy) Information: 28- NCDOT Pro act R-4064 fib, Brief Project Name (permit will refer to this name) 3 Contact Person. E-mail County Where Project is Located Name and Affiliation of Someone Who Can Answer Questions About this Appilcation 3b. (919).250 - 412a -'3o. rb�dot.st Phone Number E-mail 1. Projectis ]g New 0 Modification (of an existing permit) if' Modification, Permit No.: For modifications, attach a separate sheet Clearly explaining the reason for the modification (i.e. adding another phase, changing line sizetlength, etc.). Only include the modified information in this permit application - do not duplicate project information in B(7) and 0(10-11) that has already been Included in the original permit. 2. Owner is X Pubric (slip to ltem S(3)) ❑ Private (go to item 2(a)) -2a, if private, applicant will be: — __ __ 2b. Y If sold, faclities�owned byby.' (must choose r p Retaining Ownership (i.e. store, church, single office, eta) or 0 Leasing units (lots, townhomes, etc. - skip to !tarn 8(3)) ❑ Selling units (Iots, townhomes, etc. - go to item D(2b)) Owner of Wastewater Treatment Facility I 4a. Public Utility (Instruction 111) Homeowner ASsocJDeveloper pnstructiorr IV) Treating Wastewater From This Project Name of WWTF b. Owner of Downstream Sewer I Receiving Sewer Sae I R.—The origin of this wastewater is (check all that apply): WWTF Permit ❑ Residential Subdivision 0 Car wash 0 Apertments/Condominiums ❑ Institution ❑ Mobile Home Park ❑ Hospital ❑ school ❑ Church p Restaurant ❑ Nursing Home 11 Office Other (specify): Single Family Home 7. Volume of wastewater lq& permitted in this project: ,2,Q gallons per day. 8. If the permitted flow is zero, indi why: ❑ Interceptor line - Flow will be permitted is subsequent permits that ❑ Flow has already been allocated in Permit No. ❑ Rehabilitation or replacement of existing sewer with no new flow e) of downstream Sewer (if known) % DomestWCommerdal % industrial % Other (specify): iiine MAY 12 WATER QUALITY SECTION SHEVILLE REGIONAL OFFICE DESIGN SERVICES . 9192504119 04/20 '04 13:38 N0.588 03/03 FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS, PAGE 4 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2H -•-_— -02190) for Item B(7) or the design flow for line or pump station Sizing if zero flow in the space below. Values other than that in 1 5A NCAC 2H .0219(I)(.1-2) must be approved prior to submittal of this application. Submit a separate request to the Division of Water Quality, Non-Vischarge Permitting Unit.1617 Mail Service Center, Raleigh, NC 27%9-1617 in accordance with 15A NCAC 2H .0219(Q(3). 3 bedroom house 120 gallons per day per bedroom = 3W gallons per day (noted in item 7). 10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary) Size (inches) Length (feet) Gravity or Farce Main ---___�.---•__-• —___ • (use the pull doom menu) • $ • .. ...^.:_. ____...; _ .. 5� ... _____._• Gravity Ljj ENTER TOTAL LINE LENGTH IN MILE§ 0.11 Y 11. Summary Of Pump 3taffons to be Permitted (attach additional sheets as necessary) Location ID ; Powar Reliability Option — -- (self chosen - as shown on:! Design Flow; Operational Point ; (1- dual line feed; 2- permanent generator WATS; 3- LL plans for cross-npferertce) {MGD)--_; ©PM Q TOH porrabl� generator wltelemetry; 4-wet well *fora e LLI Dees the Sewer System comply with the Minimum Design criteria inr the Fasi Track Permitting of Pump Stations and Pone Im Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC 2H .0200 as applicable? j$ Yes ❑ No If no, please Mfemnce the pertinent minimum design criteria or regulation and indicate why a variance is requested: SUBMIT TWO COPIES OF PLANS, SPE-CIPICATIONS OIL CALCULATIONS PERTINENT TO THE VARIANCE WITH YOUR Have the submitted for Wetland/Stream Crouings - General Permit or401 Certification? Yes ❑ No p N/A Sedimentation and Erosion Control Plan? ❑ Yes [:) No ❑ N/A Stomwmter? [j Yes ❑ No ❑ N/A FAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 5 LU F— U) 0) Z F-- Q U_ Ll F— W V 1�, Use the Division's guidance document entitled, "DETERMINING STREAM CLASSIFICATIONS FOR FORM FTA 02/03 (FAST -TRACK SEWER SYSTEMS)" to collect and record the stream classification data below (attach additional sheets as necessary). This document is available from our web site or by contacting the appropriate Division of Water Quality regional office (see instructions for addresses) OR indicate the following: .._...__ _..... _........ ........ ........ __._..._...._...._._ ....... ....... _ ...... ._. _... _ .._. ....__.._.._._..._.......__ -- _..:. ........ __...._.. .... ._.... ....... ....... _... A Stream Classification is not needed because all parts of the project are at least 100 feet away from any down slope waterbody; AND, _. .. _ . . ...... . ..... .... _...... _ _ ...... _....... _... ...... _....... _.... _.. --.......... j A Stream Classification is not needed because the design does not depend on wet well storage as a power reliability option for any pump station near a Class C down slope waterbody. Location ID on Map (self chosen - as shown on Name of Waterbody Stream map for cross reference) Waterbody County River Basm Index 1. Applicant's Certification: Waterbody Classification 1, Robert A. Frye. Jr. , attest that this application for NCCOT Proiect R-4064 (Sawmills - Intersection of US 321A and SR 1108 (Mission Rd.) East of US 321A and SR 1130 (Caiah Mountain Road)) has been reviewed by me and is accurate and complete to the best of my knowledge. 1 understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143-215.6A and 143-2.15.6B, any person who knowingly makes any false statement representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10, 000 as well as civil penalties up to 1 a. A 1*11-� (--t- Signing Official Signature 2. Professional Engineer's Certification: I- a3—d Date ...... ... _. ....... 1 attest that this application for NCCOT Project R-4064 (Sawmills - Intersection of US 321A and SR 1108 (Mission Rd.) East of US 321A and SR 1130 (Caiah Mountain Road)) has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance. Although certain portions of this submittal package may have been developed by other professionals, inclusion of these materials undermy signature and seal signifies that 1 have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10, 000 as well as civil penalties up, to $25,000 per violation. 2a. Ronald B. Wilkins, PE Professional Engineer Name 2b. NCDOT / Desian Services / Utilities Engineering Firm 2c. 1020 Birch Ridge Drive Address 2d. Raleigh 2e. N.C. .2f. 27610 City State Zip 2g. (919) 250 - 4128 2h. (919) 250 - 4119 2i. rbwilkins@dot.state.nc.us Telephone Facsimile E-mail %g1111111111j," �/ of t Lp= r L - _ AAAIL-'7 .� & Date rme nn ins n__. i niin� - { `• 1'' I • ?C i Lf Iri74 i f-t Cam-✓ /+ •.'r.• �` C, t_ 4"w ;;a / 1. 1 ti r A .+ ,,.,..� _ _z ,♦ LV ,: V .,:. \ F .yi.`i�ya ' 1\ ;. �••/ °I!:\`� ..: j,.7'`""' .6 ,r ; } t { t`,' -' `7 krti �` :a.-. ` I Y I ..•. r.•�r J � • t vt�''tl }� `7 rr� r"I' � �4.: t� F-} � , l � �"...i•"�. +l. 3,-t'�•./d!i .�i !` it ,t l t. '. 7 � \� •''ti'\ - .. F • :: l., r -�s�-i. � 1 � ` k �{, ' ,,i `+. ` a` q F r`�r\� il`� i r'. i � \ �%, � �. o \ �`!:, , i_ • •.e t „ }. l I ; \ k r I' f :rr t {fi„J � L � "v ^+:..�`fr .+ 1 �.). r •i r\ 1 ` 1,� �+; t i /J.h; Gi£ f l `.,,.. :. t ;*' J+ ,'+. +. + 2 - 'r�sr r t \ �:. `� S- 1r Y.:t„ � Y ``�l (1�t��1•v� V'�Li dh a!•�' ""'\l1 l }�,I t �J,'!C � ,"".`- I.�t �\j ' � +I }�: , ;... 'r 1 .` Ir ,r f l.. _ "t.■ iyr' .,.r ,�1 SS p .= 1 4[ r t L �k r '1 �. t •' f �' �M 12 ; ( J'a '.. 4V"yfl' /r ♦ 11 All iL ��co _ } , *' � +s ''���it t t�.'� �f t ri ♦ '�� �A ���' !' ��1.!%` .� r � F-JS�"t IF,I �.,-� / T • \,.�•`"r t f 3� r� E _••II -� •,..;Ilj Luc \.1r fie, tt ti11,• ,r #'I � Ut s C' ') �. `$i� ;�.{ J•�\ I , ° t • Q };� a' e' a :iSik:l 1. fll t / t r r L� 't`.".. "''. yrry , ; ,{"} 1 r;1 .��.T 'f JT • \�, ��" \. i♦ �� �;-aY"Gi�v'Ar r .,r. 5 t' `+ii. r--•! tl� r "'�I V ' � {� S -.%'. � —_\ J L...,". >„1f .i:.V ' ,'` . �V 1E �� • Y�tit e �i L`�' ,' f' �.- -9� ^4 • % I \ ��`tr\ \ illy / �..f `� V� �;,.. \. yf t }i 5 r! t""- �.t'1 \ t\!\' r".' r S tj 4=.,s j�tl s s •d t I� �. r�1 `tj 4 I !� (• \ :''` �. f .,�,/.a i Es z_ •'4 t '�.. '•�;1 r % l•.� 5 r i I a t +f=, tV P • RtiG\, dam^ ' l `.-� i ";ti �,. �&� �'` � a � ^. � �V ��` > . i./ J I � • �. A. �� \ �} SJt \, � r t � a } I 1 /�' ,.,- 1 ....�� t . -- rt `+' } % S i � [� 1t 1 �/; e • I q ` I � . � p. t .-f" ' � � 9`c`�. �� t c�j N �4 �\Y � J'"l -� , .r_"V..-. � G:; 3 � �rf �'` 3 'C w.j �'sr•Ji:��� L: �`���'�� tA'�11�i1� t� f..i�:.� "� Ciyi/L v�° ,�I�Eya 1 �r r ��tL tt t rllr . '`,-.�i t ''� � ��^'•,.' 4 '�^� l`'t � �`,s ���t: ��tiS., • ,�;� t.. JT' r ll `- K % � � �, '?� ^ \jf �\'* t r �'�+�`\ l `�„� �` �r^�r ,;. . l � � �� �� `""' 7 .�I. �. "�'V + •l i J +�" jI +� x�Y/ �Vi �i•s':`.: v ``� ,'+ t t r -t i., � � _ _,� r ` ,. t•L I• �.�Il i '1V # N. �`�'\° ;/+ '' f: 4' ; (t��\fit f�'? ' e, �i 1• �.' • j� r\� F!'r r' u,}ir o J• i� M 'i� ' �' !.- i+• 5 ✓ f i S. l ..IY•-_-�..., - !'\ \ 1 � �, C •^_ _ y++' r i y �� a i _• �• � ntV �''`\. i I rr � t t Vl , .4! r ._r' Y+^^ ,rr / i.,^.. ; if, > tS �, r � ._/! -4-. `, _ \.. IS, r/ �I t! �-� 7 1 +GC.r V " 4 -,ti ... � t I } s_ }f'r,ryaF\ f •1'L0� +'.•�.� ._� t1`t ,11 )II ~ ' '' 7{. r t r a,\ k ,�\\.. J 1 4•'w r '' \ -w; i t rt`r_ r^f- "'° '`I C - I �r i \'\ ,1� Y� 4 / ,� v...: rtk\ L fr -. fi `"• \ �� ' I r' " !fir � � / r ♦ t `�. _. t �� 1y fir!\ lJt. i sl \ e r' i�r • 1,' tR' ~. + fi t l�\jai . 'As . ✓" ION { t �` ti k 7♦lir 1' f Iffc Ott �s ? 14v,�\' ytl` (cr! t5 ( it */ ? L I •e C I = 1 \ iQ t • . e7 + ,I c• _.-e' : r •"�, , s 1 ,� r - r ` t ��+ �'1:�� f'1 fr tr 'I {I,{ I v \.. \ r�:r_e X.s .-- •� !' `�. k f i 1 �;�` t -� . ` - r rr'+ D f V'. . s � <f :. r � '1 It f 1f •� Ir, , `t`4 =§ f J•` i' yA.. l••,, ...\ . • ; r r.""�fl +': w fir F,�:-^x'. `i � �. � � 1. - . 1t � y� 11. ,��•!�1 �a 9 r-.:. a , �\ \ 1 .., •' (,}� Syf r I'' ,5 l7r�r� IJ`; f! ! V ,� 7 f L r.'� �,Jr i �.\ ._l�f -t�tis,•.. 1 1 f � �: ,��.d ^"rt ., Fi7fS r yf �� I ;- ,r' f �'\� i i y. q j� S 41e i { •t•4•�( A . ( ,�y i J :U � i � ;' �,e e ;.f,/ F ,_ i{i � ,x, t ri I • r. If I - � rl ;1.. � �? ^. � \� ' "�` n�\3 1 {I ti� :«•. } r. ; r! � ,., I Lfw=•,. �e .t tier" .r''•y-ec 1 r • .1xr�. L:-. I. 4 \ r,--.i fl .S n , 1_<.. l . ♦,�� +r • i,l f. / Cp _. f °41 f JL♦,7 ! ( y.tltf' I ,; 3.... , lV+Y •/ ? r - f.it4 �f. <•�( 11 1 r'J'` 4 , tx �' � v�, it r c -.r F a �• `Ir �' .,•r i,t. i `a uV e;.-T v,lf'...'.\d��ti♦`S al S' ) ;.'\? ^`^- `.-',\ j'f of 11� m-� __ L \``a .:.^ l • � I.I ( li a t � r (!� ( Yt( If J ` +f' Lhr I� L"..?•�� �_s�� .' ����' \..t� �'� , [ r a I Yf t .,•..� �I �r�,.•. F i( ii�.af'"`•F. V � I �' i� �• -s tt•� . , '� ' � I �i� ° ;r T � I ' x W'. � � / r 3 1" ^� �� .� i v,`.. =�a�. .�.�.,r <e.!.,• �� 1 • •S • -jln J-/r J, y r t ti l� r :'4: $7.1 LJ�- R 7•S` h \� t ! F�,����T r -� j !'"' '\ `' 7 � � I ..i't � � �1 ti1�`e~ f .� J , b f ��t\•tt "`�e' a. L °�• t - tS�' v. f ,aJ il' — t`rr `.., eI u:u 2t Y 5 3 �r 7Ta a t lZion r'!.:! rj� y`rtJ�+ r r 1 d .^ •..,-.�j ;I + - '1 \. itGi' . V ' • fir.. ' • •, r !�''~ � i'� � . - ri � r A I ,..lF-y �: .., ji J I, ', `�I ` \I t � r' ,.d- { s ., qL.�l} 1 ,Ip t � �' e k.,,. :� f tt S '�r/ J -Y 16•ltl j'h''� t``% i_-_!I . 4S " $. 1 r ._� �' r� \L S a • J� `�C ; `'� ✓r `' Y, r • • 9 `j f:. 1^ ° '<t �; •.ki f�a ., L':' °i. i ' �-,..-.-..., f � ,r.- r � : I1t` ♦ t ,>,f r r !r"�; I �r IL . 'I r` �''I , ^f-1r I ♦ .t s t 7 �� \ '41�ty,\•Glk?l+l (�1Jr!-, }. f'� 't� \•.I. a ��y�_7���1 t�, t1S'� \4 yfY c9J ti F,' tl�►1 t#F ra' a{�IhI • I' -� E 'I a I.r k \ TYA t J/+,:... r .}. �a'•r#- Hal 17 `'t t, ( '..c;.ifr t t! t�. c"�".'` `a? �rl •t++.(� . KK"tt"" t 2 :` tii"+r tf: �.I^1�\ .\ J f�'r"; ° C'+1 +�,� r / 'n''1.� r '� '✓ , It r,l` 'i ;f\\..: \ t:jl .,---a.. I� �4 l !y 1 t;:; t '•.4 r 1 a '.11 t it t "" r '�, \ r iP V•\`` • : ! f$ n, r rt �1l\ �'t.' t •..,., 1, i' S I f 4 1 L 4., j I." _ �•'�. �, \ ~\f �' Y e - 41:1-,�'a!1 :u S ��. � • �4.. t I ! '+4�?i`�..�;..'�'trc•_ i \ I t f �.i451 t F m t rS .:I I ✓ ti� l A{! �j I•h. I � I ' _ ; •' ,rL, re F } a��1'.I(`}A. '.:r. I • •. ii` T'ni. t-+± y,,..4... + x : t3 �y ty. Tt '*, ti •y M1 r t I ti .. + r y�i'\ j) t�k o}I ' �.,i� 5fxl +,•Iltt' x, ( f'r' . > jt � 'f ' � '�I..,.%i ci.e�.:� e� h�liailfl�� 11 .r .r^.:t � t II Y+'. � . t ;�J; ".•t. r-i �`_- t` `r J c f } t, I! Y y` }• I t �m,.,- .� f '' �. f fit �• . 'r 't t _r•- : r- 4 fZ-\ ct" 4 +'. -. c- �` i`+ 1`iI. , ` 1 '�'.a t... .t i C k*--.,• r1�� A ��,'.. \ �2t.� u>,..G :l` >t;., \ t-w a u .,� ,h��`'"Z••x rr q, F,i ••..I 4.r:l rli fr h' -a ?, 1 I I !'IJjjjt !. � '' 'rt „/>,. } I V. r.. +.•��,M :�' �%I- � x ` I i i] /. {• � q c fir r..�'" lfri�. 7 �rf'�.:: .Ir, 11 5; ia+..,ti �jt .- -' :' '/�` S� � f I P,� i '• !1 J � ( �� /1i : � t ".@' �. \ I'• I � �r .r,t + � 'S7` �� � SQ. /V' ,aa,:i � /'* k:',r { .R., i1 1'_fj,\l lk:�'.y�Jr.- J((•i��T, r �t �, r, � r:; '-ef ji.� � f/ (. 1r '°,•• 1 k a �j _ f'�,��< �11^#,`r'r,,/yr�j r�y-`�•r-f"i''IIYI;j r I �,� t •.� a��. '� FY•i• �.� t 'r:--Z tf et f/ 3 i ' r �,.,V,• 1 � rq i /`t � y. '-^t, y i.�py ' 1 I I : ♦ I fir"'✓' d - 1 f -v-� r ♦ r^4 � I rrI i�sl , ^S- � �.rr� f+i �,� + ;.. r. f ��rY .,� '�+; ( f I, {���\' }�� :: � ,\ ..- ��7L t ,1"'1. A •`-` tiS.�. t 1'ti� \S. �' } ){� fJ+,_'r � � S � T;� F-�- •♦ � 1! 4 \\ _ F 4,t�� � r� r'•+t "'\ 'tt. 1,'-- cr J. x T 11 .I I•\ p\ a a I t z • t .; ,_ 5 r %,,_ =• 1! P. \ \ f. v I v "*r I I'�' r R a\.. # •'' i. '•r \lid \4 f , j • f iN \ %. w� a r %dJ i ! if? \ ��� \ .� ' �..1 `°/I 3' 1 y,1\* / :1 ti / '„Jii �iw 1^.",` rr / • `�. - 5) �_-r r % I t, t� •. I�• f2 ,ir ,,,,,r` N &'ems`--'` L � sly - �eJ r i � 'ti ^y S,I�I"� � '4 i .� �*''.aa. lr!.0 ry � - S',t`'��� `'f' a °�r� �`f 1 r '�, �' -"t" • � c 1� ��`. r yiir�^. �l �, � � I iti 't ` } � v 'u• } t .: ��I tly ei'tf* C�i'1 •t! �J SI i--.:r,-.����I r i,.rr 'i ` r 1 ,y'e ti's ,\ \. `'�,♦•,kn \: .y . rl • I r �, r. , �ti ON, • 1f of I' '%,fir y= t �J.7f13Ci'. I t l VL t,•'' .dr"''t •_ y �l 5,S„ 1 f \ C` 1 1 '� • • fr I'. J,': . •;' J +4 � � ,rtl ,,,,��I� (-' -_- ' vJ-, /f7 �♦r � •ti ��t4 � -.+s� t�r.� I Iti}�w f M``s�t\, L ..{! f� i 4 r♦ Id ,�. ry / re � l y r%~ � 'I �e: r. r �'< �.".... r, trf /.,'' J• ( \, `. �.�`L.. .,...\. � 4- ` I:�C �} �..~i - �:r r•. 3 'I r.... ��` r Granite Falls Quadrangle North Carolina 7.5 Minute USGS Topographic Map NCDOT Project: R-4064 3/25/04 lYC 'De m part ent of 7'r�►tsportatron 531 :e' ,.:1'514'i1�%Fail�,Servrce:Cer}ter � ' 1N.... 159,0 63 0 1 .,04, Vo d :after30neYear, Y J 1 PAY TO" a ORDER OF / 400 00 i II NC DEPT OF ENVIRONMENT AND i NATURAL RESOURCES..2AL,= i DIVISION OF, ENVIRONMENTAL MAN'AGEMEN }6T7 MAIL' SERVICE.CTR R/4LEIGH ,NC'' 27699=161.7' , t k t' ' I/ F � E O� WArF9 Michael F. Easley, Governor William G. Ross Jr., Secretary y North Carolina Department of Environment and Natural Resources > Alan W. Klimek, P.E., Director Coleen H. Sullins, Deputy Director Division of Water Quality Asheville May 18, 2004 Mr. Robert A. Frye, Jr., Town Administrator Town of Sawmills Au' iV_, fI fr (e-- 4076 US 321A Highway Granite Falls, North Carolina 28630 Subject: Permit No. WQ0023900 Town of Sawmills NCDOT Project 8.1731701(R-4064) Wastewater Collection System Extension Caldwell County Dear Mr. Frye: In accordance with your application received May 12, 2004, we are forwarding herewith Permit No. WQ0023900, dated May 18, 2004, to the Town of Sawmills for construction and operation of the subject wastewater collection system extension. This permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by reference. Please pay particular attention to Permit Condition 3 which requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2H .0227 or any individual system -wide collection system permit issued to the Permittee. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by the North Carolina -licensed Professional Engineer named in the application. It shall be the Permittee's responsibility to ensure that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. Asheville Regional Office 2090 US Highway 70, Swannanoa, NC 28778 Internet http://h2o.enr.state.nc.us/ Telephone (828) 296-4500 Fax (828) 299-7043 DENR Customer Service Center An Equal Opportunity Action Employer Telephone 1 800 623-7748 50% recycled/10% post -consumer paper f TOWN OF SAWMILLS MAY 18, 2004 Page 2 In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the Town of Sawmills for construction and operation of approximately 600 linear feet of eight -inch gravity sewer; as part of North Carolina Department of Transportation project number R- 4064, and the discharge of 360 gallons per day of collected domestic wastewater into the Town of Saw Mills's existing sewerage system, pursuant to the application received May 12, 2004 and in conformity with 15A NCAC 2H .0200; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting data subsequently filed and approved by the Department of Environment and Natural Resources and considered a part of this permit. The sewage and wastewater collected by this system shall be treated in the City of Lenoir's Gunpowder Wastewater Treatment Facility (Permit No. NC0023736) prior to being discharged into the receiving stream. This permit shall become voidable unless the agreement between the Town of Sawmills and City of Lenoir for collection and final treatment of wastewater is in full force and effect. If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Mr. James Reid at (828) 296-4500. Sincerely, for Alan W. Klimek, P.E. v cc: Caldwell County Health Department AsheuillePRegter Quality,Section (1N1NTF'Permit-No NC0023736-)' Bengie Thomas/West & Associates City of Lenoir Water Quality Central Files NDPU Files "aa NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES RALEIGH WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT WQ0023900 Town of Sawmills NC -DOT Project 8.1731101(R-4064) This permit shall be effective from the date of issuance until rescinded and shall be subject to the following specified conditions and limitations: 1. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. 2. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. 3. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2H .0227. If an individual permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2H .0227: a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and any contravention of the groundwater standards in 15A NCAC 2L .0200 or the surface water standards in 15A NCAC 2B .0200. b. A map of the sewer system shall be developed and shall be actively maintained. c. An operation and maintenance plan shall be developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. High -priority sewer lines shall be inspected at least once per every six-month period of time. f. A general observation of the entire sewer system shall be conducted at least once per year. g. Inspection and maintenance records shall be maintained for a period of at least three years. h. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1 C. PERMIT NO. W00023900. TOWN OF SAWMILLS, NCDOT PROJECT R-4064, CALDWELL COUNTY, 5/18/2004 4. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. 5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. 6. Upon completion of construction and prior to operation of these permitted facilities, a certification, a copy of the construction record drawings, as well as supporting design calculations for any pump stations permitted as part of this project shall be received from a North Carolina -licensed Professional Engineer certifying that the facilities have been installed in accordance with this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Main adopted June 1, 2000 as applicable; and other supporting materials. If this project is to be completed in phases and partially certified, you shall retain the responsibility to track further construction approved under the same permit, and shall provide a final certificate of completion once the entire project has been completed. A copy of the construction record drawings, indicating the facilities constructed in the. phase being certified, shall be submitted with each partial certification. Mail the Engineer's Certification, one copy of the "Construction Record Drawings," and one copy of the supporting design calculations to the Non -Discharge Permitting Unit, 1617 Mail Service Center, Raleigh, NC 27699-1617. 7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. 8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2H .0200; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143- 215.6A through §143-215.6C. 9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. 10. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A NCAC 2H .0500. 11. Noncompliance Notification: The Permittee shall report by telephone to a water quality staff member at the Asheville Regional Office, telephone number (828) 296-4500, as soon 'as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following: PERMIT NO. W00023900, TOWN OF SAWMILLS. NCDOT PROJECT R-4064, CALDWELL COUNTY. 5/18/2004 a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. Voice mail messages or faxed information is permissible but this shall not be considered as the initial verbal report. Overflows and spills occurring outside normal business hours may also be reported to the Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting any of the above occurrences shall file a spill report by completing Part I of Form CS-SSO (or the most current Division approved form), within five days following first knowledge of the occurrence. This report shall outline the actions taken or proposed to ensure that the problem does not recur. Per Condition 1(2), Part II of Form CS-SSO (or the most current Division approved form) can also be completed to show that the SSO was beyond control. Permit issued this the 18th Day of May, 2004 NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION for Alan W. Klimek, P.E., Director Division of Water Quality By Authority of the .Environmental Management Commission Permit Number WQ0023900 PERMIT NO W00023900 TOWN OF SAWMILLS NCDOT PROJECT R-4064 CALDWELL COUNTY 5/18/2004 ENGINEERING CERTIFICATION — POST CONSTRUCTION System Description: Permit No. WQ0023900 Town of Sawmills NCDOT Project 8.1731701(R-4064) Wastewater Collection System Extension Caldwell County Complete and submit this form to the Asheville regional office with the following: • One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection system extension • supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to the project should be clearly identified on the record drawings or in written summary form. Permit modifications are required for any changes resultinq in non-compliance with this permit, regulations or minimum design criteria. This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been received by the Division. Therefore, it is highly recommended that this certification be sent in a manner that provides.proof of receipt by the Division. ENGINEER'S CERTIFICATION ❑ Partial ❑ Final , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (❑ periodically, ❑ weekly, ❑ full time) the construction of the above referenced project for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS FORREST R. WESTALL WATER QUALITY SUPERVISOR ASHEVILLE REGIONAL OFFICE 2090 US HIGHWAY 70 SWANNANOA, NC 28778 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. doaSWEo STATE OF NORTH CAROLINA DEPARTMENT of TRANSPORTATION MICHAELF. EASLEY P.O. Box 25201, Raleigh, NC 27611-5201 LYNDo TIPPETT GovERNOR PHONE (919) 733-2520 SECRETARY December 9, 2004 PROJECT: 8.7131703 (R-4064) CONTRACT NO.: C200759 COUNTY: Caldwell DESCRIPTION: Intersections of US 321A and SR 1108 east of US 321A and SR 1130 west of US 3 2 1 A in Sawmills. Forrest R. Westall Water Quality Supervisor Asheville Regional Office 2090 US Highway 70 Swannanoa, NC 28778 SUBJECT: Engineering Certification — Post Construction Dear Mr. Westall: Attached is the Engineering Certification for the sanitary sewer installed as part of the above project. The subject sewer installation has been completed in accordance with the attached plan and profile sheets. If you have any questions, you can contact Trent Beaver, PE, Division Construction Engineer at 336-667-9111. Sincerely yours, M. A. Pettyjohn, Division Engineer — Djij MAP/GTB:tb n cc: David Poindexter U Kipp Turner, PE Eleventh Division Office P. O. Box 250, North Wilkesboro, NC 28659 Phone (336) 667-9111 Fax (336) 667-4549 DEC 1 WATER QUALITY SECTION c;HFVILLE REGIONAL OFFIC i m i a � a_c.i _ i L- "I r RUI"I • wn I 0MOG 70'100-) I U: 1J1 1J1''e__U4111i I . -'a bLM_QT F_aQJECT R-4064�CAt DWELL COUNTY 511A nj NGINEERIN TIVCelIPIT "-PCONSTRUCTION DSystem Description: Permit No. W00023900 DEC 1 3 2004 Town of Sawmills NCDOT Project 8.1731701(R-4064) Wastewater Collection System Extension WATER QUALITY SECTION Caldwell County ASHEVILLE REGIONAL OFFICE Complete and submit this form to the Asheville regional office with the following: • One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection system extension • supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest pest three year outage reliability option selected) for any pump stations permitted as part of this project s Changes to the project should be clearly identified on the record drawings or In written summary form. Permlt This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been roceived by the Division. Therefore, it is highly recommendod that this certification be sent in a manner that provides proof of receipt by the Division. ENGINEERS CERTIFICATION ❑ Partial ❑ Final as a duly registered Professional Engineer In the Stato of North Carolina, having been authorized to observe ([Z periodically, ❑ weekly, ❑ full time) the construction of the above referenced project for the Permittee hereby state that, to the best of my abilities. due care and diligence wasused in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2H .0200; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1. 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: ........................................... _...................... . .............................. I I f i.............. ......................... 1...1,,...,...................... ; SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS FORREST R. WESTALL WATER QUALITY SUPERVISOR ASHEVILLE REGIONAL OFFICE 2090 US HIGHWAY 70 SWANNANOA, NC 28778 The Permittee Is responsible for trackinq all partial cortlfications up until a final certification is rocoivod. Any wastewater flow mado tributary to the wastewater collection system oxtension prior to completion of this Engineer's Certification shall be considored a violation of the permit and shall subject the Permittee to appropriate enforcomont actions. \O�GOF WATF94Michael F. Easley, Governor William G. Ross Jr., Secretary 0 North Carolina Department of Environment and Natural Resources a Alan W. Klimek, P.E., Director Division of Water Quality March 30, 2006 Robert Frye, Town Manager Town of Sawmills 4076 US Hwy 321-A Granite Falls, NC 28630 SUBJECT Dear Permittee: EL 11— IC MAR 2 9 2006 Sawmills Town-Cdgb Project Permit No. WQ0015576 Wastewater Collection System Extension Final Engineering Certification Acknowledgement ---- Per 15A NCAC 2H .0220, the Division received a final engineering certification for the subject project on October 10, 2005. Enclosed is a copy of the certification page for your records. A full review of the certification materials may or may not be conducted. It is assumed that receipt of this certification indicates compliance with all regulations, design criteria and the permit. However, if a full technical review is conducted, you will be notified of any items of non-compliance. Note that the Division does not acknowledge partial certifications by letter. It is the Permittee's responsibility to track all submissions and receipt of partial certifications to the Division. Please be reminded that the Permittee is responsible for keeping a copy of the final record drawings for the life of the project. If you have not received such copy from your consultant, please contact them immediately to obtain a copy. Lastly, you are receiving this letter because the Division has you listed as the responsible party. If this permitted system is no longer owned by you or your company, please complete Form PNOCF-S as this permit is not automatically transferable. Form PNOCF-S can be downloaded from http://h2o.enr.state.nc.us/peres from the Collection Systems Applications page. If you have any questions concerning this document or the completion of Form PNOCF-S (if necessary), please contact me at the letterhead address or via E-mail at marie.doklovic@ncmail.net. Sincerely, K. Marie Doklovic, PE Environmental Engineer Enclosure Cc: Asheville -Regional Office, -Surface Water ProtectibtTSection (all documents) Benjie Thomas, PE, West & Associates (no enclosures) 405 S Sterling St, Morganton, NC 28655 Surface Water Protection Section Central Files (certification page only) One Pretreatment, Emergency Response and Collection Systems Unit Internet http://h2o.enr.nc.state.ustndpu NorthCarohna 1617 Mail Service Center, Raleigh, NC 27699-1617 An Equal Opportunity Action Employer Vidurally Telephone (919) 733-5083 Fax (919) 733-0059 50% recycled/10% post -consumer paper J ' Permit No. WQ0015576 November 25, 1998 ENGINEER'S CERTIFICATION Partial Final as a duly registered Professional Engineer in the State of North Carolina,_havibeen authorized to observe e io is , WE ekl , full time) th construction of the /ow�� Off` �'c3u)i�� 11s J 6-a /y�]►��ellt-�°ocLpi� project, t+j&le cya�ev- �d����� �v. F1 Sr.,S` rn�Y'a ; �, z/S . /V(', for the Project Name Location and County Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit, the certificate of coverage, the North Carolina Gravity Sewer Minimum Design Manual, and other supporting materials. Signature Date ®c91 x-tkA 1,m4'Q�f`'R SEAL Zulu i s 04 The above Engineer's Certification must b��ai���l,id submitted to the address below with one (1) ot copy of the "Record Drawings" (i.e., as -constructed plans) of the wastewater collection system This project shall not be considered complete and allowed to operate until this Engineer's Certification and the "Record Dra,,dings" plans have been submitted. Any wastewater flow made tributary to the wastewater collection system prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. Registration No. 7?�_­75 -17 W►� lV D SMT10N JANO'10 NORTH CAROLINA DIVISION OF WATER QUALITY WATER QUALITY SECTION PERMITS AND ENGINEERING UNIT POST OFFICE BOX 29535 RALEIGH, NORTH CAROLINA 27626-0535 I 3 WE ARE SENDING You, - X Attached Under• separate cover via the following items. >. Shop drawings Prints Plans Specifications Samples Copy of letter, Change order Other: COPIES DATE NUMBER DESCRIPTION 1 THESE ARE TRANSMITTED as checked below: For your approval For your use X As requested For review and comment FOR BIDS DUE/DATE: REMARKS As -Built Drawings Approved as submitted Resubmit copies for approval Approved as noted Submit copies for distribution Returned for corrections Return corrected prints Other PRINTS RETURNED AFTER LOAN TO US SIGNED & /& /,/ PRINTED IN U.S-A. A COPY TO If enclosures are not as noted, please notify us at once. PRODUCT 13127M USE WITH 771 ENVELOPE NEBS To Reorder. 1-800-225-6380 or www.nebs.com RE: Engineering Certification - WQ0015576 Subject: RE: Engineering Certification - WQ0015576 From: "Benjie Thomas" <benjiethomas@bellsouth.net> Date: Tue, 19 Jul 2005 18:36:0.8 -0400 To: "'Marie Doklovic"' <marie.doklovic@ncmail.net> Yes, we will send them. Benjamin (Benjie) B. Thomas, P.E. West Consultants, PLLC 405 S. Sterling Street Morganton, NC 28655 Phone: (828)433-5661 Fax: (828) 433-5662 e-mail: beniiethomas@bellsouth.net -----Original Message ----- From: Marie Doklovic fmailto:marie.doklovic@ncmail.net] Sent: Tuesday, July 19, 2005 6:05 PM To: beniiethomas@bellsouth.net Subject: Engineering Certification = WQ0015576 Hi Benjie, I hate to jog your memory like this but'the Division is sorting through some old engineering certifications for sewer projects that were set aside a while back'for questions/issues. You had submitted a certification for the Town of Sawmills CDBG Project permitted under WQ0015576 in January.2004. We had set that one aside because the plans associated with the certification refer to the Town of Glen Alpine CDBG Project and included a pump station and force main while the, subject permit was only for gravity sewer for the Town of Sawmills. I'm assuming this is the wrong set of plans for the project. Do you happen to have a set of record drawings for .the Town of Sawmills CDBG Project you could send' me? Thanks for your help, Marie Doklovic 1 of 1 7/19/2005 6:43 PM RE: Sawmills Plans Subject: RE: Sawmills Plans From: "Benjie Thomas" <benjiethomas@bellsouth.net> Date: Thu, 28 Jul 2005 12:03:27 -0400 To: "'Marie Doklovic"' <marie.doklovic@ncmail.net> CC: "'Kathy Jordan"' <kathyjordan@bellsouth.net> Okay. We will send them in. It may take about two weeks due to vacation schedules. Benjamin (Benjie) B. Thomas, P.E. West Consultants, PLLC 405 S. Sterling Street Morganton, NC 28655 Phone: (828)43 3-5661 Fax: (828) 433-5662 e-mail: benjiethomas@bellsouth.net -----Original Message ----- From: Marie Doklovic [mailto:marie.doklovic@ncmail.net] Sent: Thursday, July 28, 2005 11:37 AM To: Benjie Thomas Subject: Re: Sawmills Plans Benjie, Super old projects do not request the plans in the certification. Then we did our gravity sewer design criteria which is pseudo fast -track. Those certifications ask for record drawings. Then in 2000, we did our full fledged fast-track,which requests record drawings and pump station calcs as applicable. Although this project was permitted in 1998, the certification was received January 7, 2004. if it is not too much effort, we would appreciate the record drawings. Thanks, Marie Benjie Thomas wrote: That is a much older project. I thought it was before the Fast Track system, which means the plans would have been reviewed during the permitting process. However, if you need plans we can send them. Please confirm. Benjamin (Benjie) B. Thomas, P.E. West Consultants, PLLC 405 S. Sterling Street Morganton, NC 28655 Phone:(828)433-5661 Fax: (828) 433-5662 e-mail: benjiethomas@bellsouth.net -----Original Message ----- From: Marie Doklovic [mailto:marie.doklovic@ncmail.net] Sent: Thursday, July 28, 2005 11:23 AM . 1 of 2 7/29/2005 10:44 AM WE ARE SENDING YOU' X Attached Under separate cover via the following items., . Shop drawings Prints., Plans Specifications' Samples Copy of letter Change order Other: COPIES DATE NUMBER DESCRIPTION 1 As -Built Drawings THESE ARE TRANSMITTED as checked below: For your approval Approved as submitted Resubmit copies for approval For your use Approved as noted Submit copies for distribution X As requested Returned for corrections Return corrected prints For review and comment Other FP FOR BIDS DUE/DATE: '" " P"�""t='^^^RRIN S R T RN ASTER} OA�I TO, -US ig REMARKS DUHR - vafER CU.151_II+T'( PUiiiT SOURCE EIR,104CH io COPYTO �.<,.xx,.�». �, w°rr<1ri IG NNE . H enclosures are not as noted, please notify us at once. PRODUCT 13127M USE WITH 771 ENVELOPE NEBS To Reorder 1-800-225-6380 or www.nebS.com PRINTED IN U.SA A ,.,..•. A {r,, WE ARE SENDING YOU Shop drawings Copy of letter `- - Attached Under separate cover via — Prints — Plans Change order — Other: Specifications Engineer's Certification And As Built the following items. Samples THESE ARE TRANSMITTED as checked below: XFor your approval —Approved as submitted — Resubmit copies for approval For your use — Approved as noted — Submit - copies for distribution As requested- — Returned for corrections — Return corrected prints For review and comment — Other FOR BIDS DUE/DATE: _ PRINTS RETURNED AFTER LOAN TO US REMARKS SIGNED �iy���x�e-J ' onh FOLD AT (>) TO FIT COMPANION 771 DU•O-VUE ENVELOPE. PRINTED IN U.S.A. B • oe COPY TO . if enclosures are not as noted, please notify us at once. PRODUCT 13127T NC®ENR FOLD North Carolina Department of Environment and Natural Resources Pat McCrory Governor October 6, 2014 Seth Eckard, Town Administrator Town of Sawmills 4076 US HWY 321-A Granite Falls, NC 28630 Subject: Permit No. WQ0037381 Town of Sawmills Duff Drive Sanitary Sewer Project Wastewater Collection System Extension Caldwell County Dear Mr. Eckard: John E. Skvarla, III Secretary In accordance with your application received September 22, 2014,.we are forwarding herewith Permit No. WQ0037381 dated October 6, 2014, to Town of Sawmills"for the construction and operation of the subject wastewater collection system extension. This permit shall be effective from the date of issuance until rescinded, and shall be subject to the conditions and limitations as specified therein. This cover letter and supplement shall be considered a part of this permit and are therefore incorporated therein by reference. Please pay particular attention to the following conditions contained within this permit: Special Condition I. 1: I The Permittee shall designate the aerial creek crossing section of this project as a high priority sewer, and in accordance with 15A NCAC 02T.0403(a)(5), this section shall be inspected by the permittee or its representative at least once every six months and inspections shall be documented. Standard Condition 11.4: Requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2T .0403 or any individual system -wide collection system permit issued to the Permittee. It shall be responsibility of the Town of Sawmills to ensure that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement GAWRIW=aldwelflCollection SystemslSawmills Collection System1W00037381.Duff Dr Project.doc Water Quality Regional Operations — Asheville Regional Office 2090 U.S. Highway 70, Swannanoa, North Carolina 28778 Phone: 828-296-4500 FAX: 828-299-7043 Internet: http:#portal.ncdenr.orglweblwq An Equal -Opportunity 1 Affirmative Action Employer Town of Sawmills WQ0037381 wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Linda Wiggs at (828) 296-4500 or via e-mail at Linda.Wiggs@ncdenr.gov. Sincerely, for Thomas. A. Reeder Division of Water Resources cc: odd Poteet, West Consultants (e-copy) /Monty Wall, City of Lenoir (e-copy) ARO Files MSC 1�6117Central Files -Basement PERCS (e-copy) NCDENR STATE OF NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT In accordance with the. provisions of Article _21 of Chapter 143, General Statutes of North Carolina. as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted to the - Town of Sawmills Caldwell County for the construction and operation of approximately 9,593 linear feet of 8-inch gravity sewer to serve 70 3 bedroom. homes as part of the Duff Drive Sanitary Sewer Project, and the discharge of 25,200 gallons per day of collected domestic wastewater into the City of Lenoir existing sewerage system, pursuant to the application received September 22, 2014, and in conformity with 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design'Criteria for -the. Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other -supporting data subsequently filed and approved by -the Department of Environment and Natural Resources and considered apart of this, permit. ' This permit shall be effective from the date of issuance until rescinded and shall be subject to the specified conditions and limitations contained therein. Permit issued this 6th day of October, 2 L. for Thomas A. Reeder Division of Water Resources By Authority of The Environmental Management Commission Permit Number: WQ0037381 SUPPLEMENT TO PERMIT COVER SHEET Town of Sawmills is hereby authorized to: Construct, and then operate upon certification the aforementioned wastewater collection extension. The sewage and wastewater collected by this system shall be treated in the Gunpowder Wastewater Treatment Facility (NPDES Permit # NC0023736) prior to being discharged into the receiving stream. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. It shall be the Permittee'.s responsibility to ensure that the as -constructed project meets the appropriate design criteria and rules.. Construction and operation is contingent upon compliance with the Standard Conditions and any Special Conditions identified below. I. SPECIAL_ CONDITIONS_ 1 The. Permittee shall designate the aerial creek crossing section of this project as a high priority sewer, and in accordance with 15A NCAC 02T.0403(a)(5), this section shall be inspected by the permittee or its representative at least once every six months and inspections shall be documented. 2 This permit shall become voidable unless the agreement between Town of Sawmills and City of Lenoir for the collection and final treatment of wastewater is in full force and effect. II. STANDARD CONDITIONS 1. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered.on its merits and may or may not be approved. 2. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials unless specifically mentioned herein. 3. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. 4. The wastewater collection facilities shall be properly maintained and operated at all times. The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2T .0403. If an individual permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2T .0403: a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and to prevent any•contravention of groundwater standards -or surface water standards. b. A map of the sewer system shall be developed and shall be actively maintained. c. An operation and maintenance plan including pump station inspection frequency, preventative maintenance schedule, spare parts inventory and overflow response has been developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. • High -priority sewer lines shall be inspected at least once per every six -months and inspections are documented. f. A general observation of the entire sewer system shall be conducted at least once per year. g. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1C. h. A Grease Control Program is in place as follows: 1. For public owned collection systems, the Grease Control Program shall include at least biannual distribution of educational materials for both commercial and residential users and the legal means to require grease interceptors at.existing establishments. The plan shall also include legal means for inspections of the grease interceptors, enforcement for violators and the legal means to control grease entering the system from other public and private satellite sewer systems. 2. For privately owned collection systems, the Grease Control Program shall include at least bi-annual distribution of grease education materials to users of the collection system by the permittee or its representative. 3. Grease education materials shall be distributed more often than required in Parts (1) and (2) of this Subparagraph if necessary to prevent grease -related sanitary sewer overflows. Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment accessibility. j. Documentation shall be kept for Subparagraphs (a) through (i) of this Rule for a minimum of three years with exception of the map, which shall be maintained for the life of the system. 5.' Noncompliance Notification: The Permittee shall report by telephone to a water resources staff member at the Asheville Regional Office, telephone number 828-296-4500, as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of,the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or b. Any SSO and/or spill over 1,000 gallons; or c. Any SSO and/or spill, regardless of volume, that reaches surface water Voice mail messages or faxed information is permissible, but this shall not be considered as the initial verbal report. Overflows and spills occurring outside normal business hours may also be reported to the"Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting any of the above occurrences shall file a spill report by completing and submitting Part I of Form CS-SSO (or the most current Division approved form) within five days following first knowledge of the occurrence. This report must outline the actions taken or proposed to be taken to ensure that the problem does not recur. Part II of Form CS-SSO (or the most current Division approved form) can also be completed to show that the SSO was beyond control. 6. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. Per 15A NCAC 2T.0116, upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form attached to this permit shall be submitted with the required supporting documents to the address provided on the form. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. If the permit is issued to a private entity with an Operational Agreement, then a copy of the Articles of Incorporation, Declarations/Covenants/Restrictions, and Bylaws that have been appropriately filed with the applicable County's Register of Deeds office shall be submitted with the certification. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. Supporting documentation shall include the following: a. One copy of the project construction record drawings (plan & profile views of sewer lines & force mains) of the wastewater collection system extension. Final record drawings should be clear on the plans or on digital media (CD or DVD disk) and are defined as the design drawings that are marked up or annotated with after construction information and show required buffers, separation distances, material changes, etc. b. One copy of the supporting pump station design calculations (selected pumps, system curve, operating point, buoyancy calculations, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project. c. Changes to the project that do not result in non-compliance with this permit, regulations, or the Minimum Design Criteria should be clearly identified on the record drawings, on the certification in the space provided, or in written summary form. Prior to Certification (Final or Partial): Permit modifications are required for any changes resulting in non- compliance with this permit (including pipe length increases of 10% or greater, increased flow, pump station design capacity design increases of 5% or greater, and increases in the number/type of connections), regulations, or the Minimum Design Criteria. Requested modifications or variances to the Minimum Design Criteria will be reviewed on a case -by -case basis and each on its own merit. Please note that variances to the Minimum Design Criteria should be requested and approved during the permitting process prior to construction. After -construction requests are discouraged by the Division and may not be approved, thus requiring replacement or repair prior to certification & activation. 8. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an enforcement action by the Division, in accordance with North Carolina General Statutes §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. 10. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. 11. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A NCAC 213.0200 and 15A NCAC 2H .0500. FAST TRACK ENGINEERING CERTIFICATION Permittee: TOWN OF SAWMILLS Permit No. WQ0037381 Project: DUFF DRIVE SANITARY SEWER PROJECT Issue Date: 06/10/14 Complete and submit this form to the permit issuing regional office with the following: • One copy of the project record drawings (plan& profile views and detail drawings of sewer lines) of the wastewater collection system extension. Final record drawings should be clear on the plans or on digital media (CD or DVD disk) in pdf format. Record drawings should indicate the design and the marked up changes during construction. • Supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to the project should be clearly identified on the record drawings or in written summary form. Permit modifications are required for any changes resulting in non-compliance with this permit regulations or minimum design criteria. Modifications should be submitted prior to certification This project shall not be considered complete nor allowed to operate until the Division has received this Engineer's Certification and all required supporting documentation. Therefore, it is highly recommended that this certification be sent in a manner that provides proof of receipt by the Division PERMITTEE'S CERTIFICATION I, the undersigned agent for the Permittee, hereby state that this project has been constructed pursuant to the applicable standards & requirements, the Professional Engineer below has provided applicable design/construction information to the Permittee, and the Permittee is prepared to operate & maintain the wastewater collection system permitted herein or portions thereof. Printed Name, Title Signature Date ENGINEER'S CERTIFICATION ❑ Partial ❑ Final I, 1 1 , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (❑ periodically, ❑ weekly, ❑ full time) the construction of the subject project for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 02T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's Seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS WATER QUALITY REGIONAL OPERATIONS SUPERVISOR ASHEVILLE REGIONAL OFFICE 2090 U.S. HWY 70 Swannanoa, NC 28778 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. DWR Use Only: Flow from this project is tributary to: NCO023736 ' Division of Water Quality Fast Track Application (FTA 12.12) for Sewer Systems— Review Checklist Project Name: Du-4 )Y- v c A iL. a Sw'j2. ?-rz j . Preliminary Review Date: , V g y ! I �{ Project NumbergWQ0037381 G 3�3g Final Review Date: Reviewer; 1---;l� U ►a �;� S Application Pre -Review Project is located in a County currently covered by the regional office UYes []No Application and supporting documentation submitted in duplicate? Vres ❑No One Original and One Copy . Correct application fee submitted? G.S. 143-215.3D 2fes L No Ensure that a check for $480 is submitted and made out Application package is complete Current application version (FTA 12-12) L5 -- . J'es ❑No Briefproject narrative (per Section A ofFTA : "des []No Certification of Public Convenience and Neces `.. - rovWed �x ❑Yes ❑No (if applicable) Operational Agreements, signed an dated - Yes []No(if applicable) Flow Tracking / Acceptance Form 6- 3), signed fed '❑'ices' []No Flow Tracking / Acceptance Planning se �. ,Addendum []Yes ❑No (if applicable) Site Map and Street Le" l Map (per Sec F of 2) es ❑No Stream Classifica a. SCAS 03- igned,v d date es []No(must b , etti,.C. PE) s,.. PE Certificatio plioation fined, seal red by N. es ❑No Applicant Certifies" is signe dated (or on letter is provided) []Ws []No Permit Info ' t Mo Does the t require a pe the a Dyes ❑No See 'fling by Regul 05A 02T.0303) for projects deemed permitted Is the project eligi the Fast Tra, ogram? 2'es ❑No Project not permitte gh the fast ' program Requires an En ental p sment per 15A NCAC 01 C .0408 Is an alternative s o sure sewers, STEP systems, vacuum systems, etc.) Is funded through th cture Finance Section If the applicant is a private entity (private utility) ❑Yes []No Applicant has been designated as a public utility by the NC Utilities Commission Has submitted a Certificate of Public Convenience and Necessity (CPCN) or Letter from the Public Staff of the NC Utilities Commission (contact Central Office) If the applicant is a private entity (Developer) []Yes []No Has submitted an executed Operational Agreement (DEV 06-13) If the applicant is a Homeowner's or Property Owner's Association: ❑Yes []No Has submitted an executed Operational Agreement (HOA 06-13) and, Copy of the Articles of Incorporation, Declarations and By-laws Wastewater Flow Information Has the wastewater flow volume been calculated correctly (section B.9 of FTA 12-12)? Yes [:]No Flow is calculated per 15A NCAC 02T.0114 or If daily design flow is not based on regulations ensure that the applicant has an approved flow reduction of daily design flow rate on file with the Division. or If other than 2T.0114, values must be supported with flow data per 15A NCAC 02T.0114(fl (Contact Central Office) Has submitted Flow Tracking/Acceptance Form (FTSE 06-13) Yes ❑No Proper certification per 15A NCAC .0106 (b) -es [:]No Form is dated within one year of receipt of application package Yes ❑No Is FTSE Planning Assessment Addendum Required? ❑Yes ❑No Required only for projects where available pump station capacity is < 0. Contact Central Office if needed Additional forms (FTSE 06-13) required? ❑Yes ❑No Required only if the owner of downstream sewer different then owner of WWTF Design Information Has a Stream Classification form been submitted (WSCAS 03-12) iYes ❑No Required if any portion of project is within 100 feet of any surface water or wetlands If no, verify separation on submitted USGS. Topographic Map Note, 15A NCAC 02T .0305 (fl contains minimum separations required for sewer A variance is required if minimum separations cannot be avoided Has been signed, sealed, and dated by an N.C. PE 21yes [-]No Is Project design is in accordance with (see section B.13 of FTA 12-12) Yes ❑No 15A NCAC 02T Gravity Sewer Minimum Design Criteria (latest version) Minimum Design Criteria for Permittingof f Pump Stations and Force Mains (latest version) If no, a variance approval is required per the requirements of 15A NCAC 02T.0105(b) Applicant must submit TWO copies of the plans, specifications, and calculations Contact the Central Office to discuss the variance request to determine a course of action. Variance approvals are issued from the central office. If approved, the variance should be incorporated into the final permit Project contains high priority lines 05A NCAC 02T .0402(2)) �es [:]No Contact the Central Office Application Certification Has a N.C. PE stamped, signed, and dated the application? Yes ❑No PE with active license in North Carolina? Yes ❑No Check the NCBELS to ensure Engineer is currently registered to practice NCBELS License Lookup Applicant (Owner/Permittee) signature meets requirement of 15A NCAC .0106(b)? Yes ❑No If not, is a delegation letter provided, delegating authority? []Yes ❑No If the owner is a corporation, is the corporation registered in N.C.? ❑Yes ❑No N.C. Secretary of State (Corporation Search) WEST CONSULTANTS, PLLC Consulting Engineers and Surveyors 405 South Sterling Street Morganton, North Carolina 28655 Phone (828) 433-5661 Fax (828) 433-5662 TO NCDENR - Water Quality Section - 2090 US HWY 70 Swannanoa, NC 28778 LETTER OF TRANSMITTAL JOB NUMBERIPHONE DATE 11160.1 /19/2014 ATTENTION RE: Town of Sawmills, NC - Duff Drive Area Sanitary Sewer WE ARE SENDING YOU X Attached Under separate cover via Shop drawings Prints Plans Specifications Copy of letter Change order Other: the following items. Samples COPIES DATE NUMBER DESCRIPTION 2 Project Narrative 2 Application Form (1 Original And 1 Copy) 1 Application Fee ($480.00) Pd By Town Of Sawmills 2 Flow Tracking/Acceptance From City Of Lenoir 2 Flow Tracking/Acceptance From Sawmills 2 USGS Topography Quad Map 2 Watershed Classification Attachment ' RECEIVE® Division of Water Resourres SEP 2 2 2014 THESE ARE TRANSMITTED as checked below: Water Quality Regional OperationsAsheville Regional Office n For your approval For your use As requested For review and comment FOR BIDS DUE/DATE: REMARKS Approved as submitted Approved as noted Returned for corrections Other 9/17/2014 Resubmit copies for approval Submit copies for distribution Return corrected prints PRINTS RETURNED AFTER LOAN TO US COPY TO SIGNED) " If enclosures are not as noted, please notify us at once. PRODUCT 13127G USE WITH 771C ENVELOPE Deluxe For Business 1-800-225-6380 or www.nebs.com PRINTED IN U.SA. A man n • TOWN OF SAWMILLS DUFF DRIVE SANITARY SEWER PROJECT, CDBG SEDIMENTATION AND EROSION CONTROL PLAN CALDWELL COUNTY, NORTH CAROLINA Narrative The project will consist of the installation of 9,593 feet of 8-inch gravity sewer, valve replacement at the Stamey Road Pumping Station, 70 house connections, and appurtenances. The location is along Jay Street, Oxford Drive, Gatewood Drive, Maggie Lane and Duff Drive, in Sawmills. This area is inside the town limits in the northwest section of Sawmills. The project will provide public sanitary sewer service to 70 homes and abandon the existing septic tank systems. In the construction phase of the project both concrete and asphalt driveways will be disturbed and will need to be repaired. Other than repairing the disturbed driveways and any incidental damages to the streets, no street improvements are included in the proposed project. Resources SEP 2 2 2014 Water Quality Regional Operations _Asheville Regional Office REGEIVLv Division of Water Resources _WQ0037381 State of North Carolina S E P 2 2 2014 Depa meat of Environment and Natural Resources DWR n Division of Water Resources 6f� tons AST -TRACK APPLICATION (FTA 08-13) Division of Water ResourcesLa2uality Regton�l Op heville Re io C7�VIT SEWERS, PUMP STATIONS, AND FORCE MAINS General — When submitting this application, please use the following instructions as a checklist in order to ensure all required items are submitted. Adherence to these instructions and checking the provided boxes will help produce a quicker review time and reduce the amount of requested additional information. For more information, visit the Surface Water Section's Collection Systems website or; contact the Regional Office serving your county Unless otherwise noted, the Applicant shall submit one original and one copy of the application and supporting documentation to the appropriate Regional Office (see page 3). A. Cover Letter: Include a brief project'narrative describing the.final..des'ign (i.e,system'and/or pump station to ultimately serve.500 homes, but flow for only 100.hornes being, requested now),. For modifications, clearly explain the reason for the modification (i.e. adding another phase, changing line size, length, etc). B. Application Form (FTA 08-13): R( Submit the completed and appropriately executed Fast -Track (FTA 08-13) Application. Any unauthorized content changes to this form shall result in the application being returned. If necessary for clarity or due to, space restrictions, attachment to the application may be made, as long as the attachments are numbered to correspond to the section and item to which they refer. You do not need to submit detailed plans and specifications unless you respond NO to item 13(13) w The Professional Engineer's Certification of the application shall be signed, sealed and dated by a North Carolina licensed Professional Engineer. lid The Applicant's Certification of the application shall be signed in accordance with 15A NCAC 02T .0106(b). Per 15A NCAC 02T :0106(c), an alternate person may be designated as the signing official if a delegation letter is provided from a person who meets the criteria in 15A NCAC 02T .0106(b). C. 7psubmit lication Fee: a check in the amount of $480 to: North Carolina Department of Environment and Natural Resources (NCDENR). ➢ Checks shall be dated within 90 days of application submittal. D. Certificate of Public Convenience and Necessity (For Privately -Owned Public Utilities Only): ❑ Per 15A NCAC 02T .0115(a)(1), provide two copies of the Certificate of Public Convenience and �I P Necessity from the North Carolina Utilities Commission demonstrating the Applicant is authorized to 11 hold the utility franchise for the area to be served by the sewer extension, or ❑ Provide two copies of a letter from the North Carolina Utilities Commission's Water and Sewer Division Public Staff stating an application for a franchise has been received and that the service area is contiguous to an existing franchised area or that franchise approval is expected. ❑ The project name in the CPCN or letter must match that provided in Item A(2)a of this application. E. Operational Agreements (For Home/Property Owners' Associations and Developers of lots to be sold): ➢ Home/Property Owners' Associations I ❑ Per 15A NCAC 02T .0115(c), submit the properly executed Operational Agreement (HOA 08-13). ❑ Per 15A NCAC 02T .0115(c), submit a copy of the Articles of Incorporation, Declarations and By-laws. ➢ Developers of lots to be sold ❑ Per 15A NCAC 02T .0115(b), submit the properly executed 012erational Agreement DEV 08-13 . Even if the project may be turned over to a municipality upon completion, Form DEV 08-13 is required. INSTRUCTIONS FOR APPLICATION FTA 08-13 & SUPPORTING DOCUMENTATION Page 1 of 6 F. Do ,wnstream Sewer, WWTF Capacity and Flow Tracking/Acceptance Form (FTSE 08-13) Submit the completed and appropriately executed Flow Tracking/Acceptance for Sewer Extension Permit (FTSE 08-13) Form for all applications. ➢ The applicant (and owners of downstream sewers, pump stations and/or treatment facilities submitting form FTSE 08-13 certifies that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving treatment plant, and that the flow from this project will not cause capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving wastewater treatment plant. ➢ Where the applicant, is not the owner of the downstream sewer, submit two copies of form FTSE 08-13 from the owner of the downstream sewer and owner of the WWTF, if different. ➢ The flow acceptance indicated in form FTSE 08-13 must not expire prior to permit issuance and must be dated less than one year prior to the application date. ➢ Submittal of this application and form FTSE 08-13 indicates that -owner has adequate capacity and will not violate G.S. 143-215.67(a). ➢ Intergovernmental agreements or other contracts will not, be accepted in lieu of a project - specific FTSE 08-13. G. Site Map (All Application Packages): R( Submit;an 1.8 5=inch x.11-inch color,copy of�a USGS Topographic Map of sufficient;seale to identify.the ent re,project.area and closest surface'waters,. Each..map; must include.at a- min imum: ➢ The location of the sewer line and pump stations and be of reproducible quality. ➢ Downstream connection points and the permit number for the receiving sewer (if known) Pump Station Locations and the longitude and latitude for each pump station (if applicable) ❑ Include a_ street level map showing all relevant project areas. H. Stream Classification (WSCAS 08-13) if Submit the completed and appropriately executed Watershed Classification Attachment form (WSCAS 08-13) if any portion of the sewer system project is within 100 feet of any surface water or wetlands. ➢ A variance must be requested for encroachment within required setbacks or buffers pursuant to 15A NCAC 02T .0305(f) 1. Environmental Assessments (Projects subject to an Environmental Assessment (EA)): ➢ Projects involving an Environmental Assessment per 15A NCAC 01 C .0408, must be submitted for a full technical review and must be submitted to the PERCS Unit on application forms provided by the Division. J. Alternative Sewer Systems ➢ Projects involving low pressure sewer systems, vacuum sewer systems and other alternative sewer systems must be submitted for a full technical review and must be submitted to the PERCS Unit on. application forms provided by the Division. K. Flow Direction ➢ Many wastewater treatment systems are entering into agreements for regionalization efforts and emergency treatment capacity. Parts of the system are installed so that the wastewater flow can be directed to more than one treatment facility. If this is the case with the project, please indicate in B(12) and give the permit number of the second facility. L. Certifications — Section C ➢ The application must be' certified by both the applicant and the design engineer who is a North Carolina Registered Professional Engineer (PE). The applicant signature must match the signing official listed in Item A(1 b). The PE should NOT certify the application if he/she is unfamiliar with 15A NCAC Chapter 2T, The Gravity Sewer Minimum Design Criteria (most recent version) and the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (most recent version), as applicable to the project. INSTRUCTIONS FOR APPLICATION FTA 08-13 & SUPPORTING DOCUMENTATION Page 2 of 6 THE COMPLETED APPLICATION PACKAGE INCLDING ALL SUPPORTING INFORMATION AND MATERIALS, SHOULD BE SENT TO THE APPROPRIATE REGIONAL OFFICE: REGIONAL OFFICE ADDRESS COUNTIES SERVED Asheville Regional Office 2090 US Highway 70 Avery, Buncombe, Burke, Caldwell, Cherokee, Water Quality Section Swannanoa, North Carolina 28778 Clay, Graham, Haywood, Henderson, Jackson, (828) 296-4500 Macon, Madison, McDowell, Mitchell, Polk, (828) 299-7043 Fax Rutherford, Swain, Transylvania, Yancey Fayetteville Regional Office 225 Green Street Suite 714 Anson, Bladen, Cumberland, Harnett, Hoke, Water Quality Section Fayetteville, North Carolina 28301-5094 Montgomery, Moore, Robeson, Richmond, (910) 433-3300 Sampson, Scotland (910) 486-0707 Fax Mooresville Regional Office 610 E. Center Avenue Alexander, Cabarrus, Catawba, Cleveland, Water Quality Section Mooresville, North Carolina 28115 Gaston, Iredell, Lincoln, Mecklenburg, Rowan, (704) 663-1699 Stanly, Union (704) 663-6040 Fax Raleigh Regional Office 1628 Mail Service Center Chatham, Durham, Edgecombe, Franklin, Water Quality Section Raleigh, North Carolina 27699-1628 Granville, Halifax, Johnston, Lee, Nash, (919) 791-4200 Northampton, Orange, Person, Vance, Wake, (919) 788-7159 Fax Warren, Wilson Washington Regional Office 943 Washington Square Mall Beaufort, Bertie, Camden, Chowan, Craven, Water Quality Section Washington, North Carolina 27889 Currituck, Dare, Gates, Greene, Hertford, Hyde, (252) 946-6481 Jones, Lenoir, Martin, Pamlico, Pasquotank, (252) 975-3716 Fax Perquimans, Pitt, Tyrrell, Washington, Wayne Wilmington Regional Office 127 Cardinal Drive Extension Brunswick, Carteret, Columbus, Duplin, New Water Quality Section Wilmington, North Carolina 28405 Hanover, Onslow, Fender (910) 796-7215 (910) 350-2004 Fax Winston-Salem Regional Office 585 Waughtown Street Alamance, Alleghany, Ashe, Caswell, Davidson, Water Quality Section Winston-Salem, North Carolina 27107 Davie, Forsyth, Guilford, Rockingham, Randolph, (336) 771-5000 Stokes, Surry, Watauga, Wilkes, Yadkin (336) 771-4630 Fax INSTRUCTIONS FOR APPLICATION FTA 08-13 & SUPPORTING DOCUMENTATION Page 3 of 6 USE THE TAB KEY TO MOVE FROM FIELD TO FIELD Application Number:'- _WQ0037381 (to be completed by DWR} 1. Owner/Permittee: 3798( 1 a. � Q n of Sawmills Ful egal Name (company, municipality, HOA, utility, etc.) 0 ,1 b. Seth Eckard, Town Administrator Signing Official Name and Title (Please review 15A NCAC 2T .0106 (b) for authori ed signiiIDwa Vtu ter Resources ,1 c. The legal entity who will own this system is: El Individual ❑ Federal ® Municipality ElState/County El Private Partnership CorporatioF ] gther ((Wecify): c CC IIJJ 14 0 1d. 4076 US HWY 321-A 1e. Granite Fall LL Mailing Address City Z 1f. North Carolina Water Quality 1g. 28630 ;tyRegionatOperations Z State s Zip Code 0 lh. 828-396-7903 1i. 828-396-8955 1j. seckard@-townofsawmills.com QTelephone Facsimile E-mail V 2. Proiect (Facility) Information: J 2a. 2b. Caldwell Brief Project Name (permit will refer to this name) County Where Project is Located 3. Contact Person: - -- -- ,3a. Todd Poteet, West Consultants, PLLC Name and Affiliation of Someone Who Can Answer Questions About this Application 3b. 828-433-5661 3c. tpoteet@west-consultants.com Phone Number E-mail i1. Project is ® New ❑ Modification (of an existing permit) If Modification, Permit No.: Z 0 F— 0 LL Z H 2 It W a Ti 2. Owner is ® Public (skip to Item B(3)) ❑ Private (go to Item 2(a)) 2a. If private, applicant will be: 2b. If sold, facilities owned by a (must choose one ❑ Retaining Ownership (i.e. store, church, single office, etc.) or El Public Utility (Instruction D) ❑ Leasing units (lots, townhomes, etc. - skip to Item B(3)) ❑ Homeowner Assoc./Developer (Instruction E) ❑ Selling units (lots, townhomes, etc. - go to Item B(2b)) `3. City of Lenoir Owner of Wastewater Treatment Facility (WWTF) Treating Wastewater From This Project 4a" �G�rt le ek it 4b l Q02 7 6 Name of WWTF WWTF Permit No. '.5a. City of Lenoir 15b. 8" ® Gravity 5c. Unknown I Owner of Downstream Sewer IReceiving Sewer Size ❑ Force Main Permit # of Downstream Sewer (Instruction F) 6. The origin of this wastewater is (check all that apply): Residential Subdivision ❑ Retail (Stores, shopping centers)EL0°.7o Domestic/Commercial ❑ Apartments/Condominiums ❑ Institution % Industrial ❑ Mobile Home Park ❑ Hospital ❑ School ❑ Church (Attach Description) ❑ Restaurant ❑ Nursing Home % Other ❑ Office ❑ Other (specify): (Attach Description) 7. Volume of wastewater to be allocated or permitted for this particular proje t. 25.:�0 gallons per day *Do not include future flows or previously permitted allocations - 8. If the permitted flow is zero, indicate why: ❑ Pump Station, Outfall or Interceptor Line where flow will be permitted in subsequent permits that connect to this line ❑ Flow has already been allocated in Permit No. ❑ Rehabilitation or replacement of existing sewer with no new flow expected (see 15A NCAC 02T .0303 to determine if a permit is required) FTA 08-13 APPLICATION Page 4 of 6 9. Provide the wastewater flow calculations used in determining the permitted flow in accordance with 15A NCAC 2T .0114 for the value in Item B(7) AND/OR the design flow for line or pump station sizing if a reduced or zero flow is being requested in Item 13(7). Values other than that in 15A NCAC 2T .0114 (b) and (c) must be supported with actual water or wastewater use data in accordance with 15A NCAC 2T .0114 (f). 70 - 3 BDRM Res. (70X360) 2 �i+J', r 10. Summary of Sewer Lines to be Permitted (attach additional sheets if necessary) Size (inches) 490 Length (feet) New Gravity or Additional Force Main wIs f�'e . CI a.rifiy - LLI ; Z 11. Summary of Pump Stations w/ associated Force Mains to be Permitted (attach additional sheets as necessary) Z Pump Station Location ID: N/A (self chosen - as shown on plans/map for reference) 11-ongitude: Latitude: Z O H , Design Flow Operational Point Power Reliability Option Q (MGD) GPM @TDH 1 -permanent generator w/ATS; Force Main Size Force Main Length 2 - portable generator w/MTS o _ LL ? ;Pump Station Location ID: (self chosen - as shown on plans/map for reference) H :,Longitude: Latitude: Design Flow Power Reliability Option C' (MGD) ;Operational Point 1 -permanent generator w/ATS; Force Main Size Force Main Length GPM @TDH 2 - portable generator w/MTS '12. Will the wastewater flow in the proposed sewer lines or pump stations be able to be directed to another treatment facility? ❑ Yes ® No If Yes, permit number of 2"d treatment facility: (RO — if "yes" to 13,12 please contact the Central Office PERCS Unit) -13. Does the sewer system comply with the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC Chapter 2T as applicable? Yes ❑ No If No, please reference the pertinent minimum design criteria or regulation and indicate why a variance is requested. SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS PERTINENT TO THE VARIANCE WITH YOUR APPLICATION FTA 08-13 APPLICATION Page 5 of 6 14. Have the following permits/certifications been submitted for approval for the system or project to be served? Z O H Q 0 LLL H W U Wetland/Stream Crossings - General Permit or 401 Certification? N Yes ❑ No ❑ N/A Sedimentation and Erosion Control Plan? N Yes ❑ No ❑ N/A Trout Buffer Waiver? ❑ Yes ❑ No N N/A Stormwater? ❑ Yes ❑ No N N/A 15. Does this project include any high priority lines (15A NCAC 02T .0402 (2)) involve aerial lines, siphons, or interference manholes)? These lines will be considered high priority and must be checked once every six months Check if „ N� nd provide details aerial lines 1. Owner/Permittee's Certification: (Signature of Signing Official and Project Name) 1, Seth Eckard attest that this application for Duff Drive Area Sanitary Sewer Project has been reviewed by me and is accurate and complete to the best of my knowledge. / understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. Note: In accordance with North Carolina General Statutes 143- 215.6A and 143-215.68. any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation. Signing Official Signature /o Date ENGINEERING DESIGN DOCUMENTS MUST BE COMPLETED PRIOR TO SUBMITTAL OF THIS APPLICATION. THESE DOCUMENTS MUST INCLUDE PLAN AND PROFILE OF SEWERS, THEIR PROXIMITY TO OTHER UTILITIES, DESIGN CALCULATIONS, ETC. REFER TO 15A NCAC 02T .0305 2. Professional Engineer's Certification: (Signature of Design Engineer and Project Name) 1, Todd J. Poteet. PE attest that this application for Duff Drive Area Sanitary Sewer Project _ has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, and the Minimum Design Criteria for the Fast - Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance. Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that i have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC General Statutes 143-215.6A and 143-215.68 any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per 2a. Todd J. Poteet-- Professional Engineer Name 2b. West Consultants, PLLC ��do •'� i Engineering Firm 2c. 405 South Sterling Street M o Mailing Address.. NZII2d. Morganton 2e. NC 2f. 28655GJ��City State Zip ��01111)I I% 2g. 828-433-5661 2h. 828-433-5662 2i. tpoteet@west-consultatns.com Telephone Facsimile E-mail NC PE Seal Signature & Date FTA 08-13 APPLICATION Page 6 of 6 FORM WSCAS 08-13 WATERSHED CLASSIFICATION ATTACHMENT FOR SEWER SYSTEMS Divisiioon o WC I! Applicant Name na-lProject Name Asheville Re-fnQIonal n ffine Town,of Sawmills Duff Driue3Area,,. nitary,SewerrProje- Professional Engineer Name Engineering Firm Name [T6.dd;J,.Poteet PE West Consultants; P,LLC Location River Waterbody Stream Waterbody ID Name of Waterbody' County Basin Index No. Classification All UT to Freemason Creek Caldwell Catawba 11 47 (1} WS, (U " J,.s r FIX 7. ' If unnamed, indicate "unnamed tributary to X", where X is the named waterbody to which the unnamed tributary joins. I certify that as a Registered Professional Engineer in the State of North Carolina that / have diligently followed the Division's instructions for classifying waterbodies and that the above classifications are inclusive of the stated project, complete and correct to the best of my - - -knowledge-and belief----- ---- PE Seal, Signature and Date *** END OF FORM WSCAS 08-13 *** FORM: WSCAS 08-13 Page 1 of 1 State of North Carolina Department of Environment and Natural Resources Division of Water Resources Division of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications (FTSE 08-13) Project Applicant Name: Town of Sawmils Project Name for which flow is being requested: Duff Drive Area Sanitary Sewer Project More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for all pump stations along the route of the proposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: N/A b. WWTP Facility Permit #: All flows are in MGD c. WWTP facility's permitted flow d. Estimated obligated flow not yet tributary to the WWTP e. WWTP facility's actual avg. flow f. Total flow for this specific request g. Total actual and obligated flows to the facility h. Percent of permitted flow used H. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) (B) (C) (D)=(B+C) (E)=(A-D) Design Obligated, Pump Average Daily Approx. Not Yet Total Current Station Firm Flow** Current Avg. Tributary Flow Plus (Name or Capacity,* (Firm / pfl, Daily Flow, Daily Flow, Obligated Available Number) MGD MGD MGD MGD Flow Capacity*** stamey Road 0.29 0.12 0.01 0 0.01 0.11 S E p 2 2 2014 Asheville * The Firm Capacity of any pump station is defined as the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor (pf) not less than 2.5. ' *** A Planning Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Page 1 of 6 FTSE 08-13 III. Certification Statement: I Seth Eckard certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendums for which I am the responsible party. Signature of this form indicates acceptance of this wastewater flow. Signing Official Signature Page 2 of 6 FTSE 08-13 State of North Carolina Department of Environment and Natural Resources Division of Water Resources Division of Water Resources Flow Tracking/Acceptance for Sewer Extension Applications (FTSE 08-13) Project Applicant Name: City of Lenoir Project Name for which flow is being requested: Duff Drive Area Sanitary Sewer Project More than one FTSE may be required for a single project if the owner of the WWTP is not responsible for allpump stations along the route of the proposed wastewater flow. I. Complete this section only if you are the owner of the wastewater treatment plant. a. WWTP Facility Name: Gunpowder Creek WWTP b. WWTP Facility Permit #: NC0023736 All flows are in MGD c. WWTP facility's permitted flow )- . t9 d. Estimated obligated flow not yet tributary to the WWTP y e. WWTP facility's actual avg. flow f. Total flow for this specific request Z>2-SIZ- g. Total actual and obligated flows to the facility h. Percent of permitted flow used _ eZ 2 �? II. Complete this section for each pump station you are responsible for along the route of this proposed wastewater flow. List pump stations located between the project connection point and the WWTP: (A) (B) (C) (D)=(B+C) (E)=(A-D) Design Obligated, Pump Average Daily Approx. Not Yet Total Current Station Firm Flow** Current Avg. Tributary Flow Plus (Name or Capacity,* (Firm / pt), Daily Flow, Daily Flow, Obligated Available Number) MGD MGD MGD MGD Flow Capacity*** —1/Lr� * The Firm Capacity of any pump station is defined as the maximum pumped flow that can be achieved with the largest pump taken out of service. ** Design Average Daily Flow is the firm capacity of the pump station divided by a peaking factor (pf) not less than 2.5. *** A Planning Assessment Addendum shall be attached for each pump station located between the project connection point and the WWTP where the Available Capacity is < 0. Page 1 of 6 FTSE 08-13 III. Certification Statement: I ,g� L , &,01,xS certify to the best of my knowledge that the addition of the volume of wastewater to be permitted in this project has been evaluated along the route to the receiving wastewater treatment facility and that the flow from this project is not anticipated to cause any capacity related sanitary sewer overflows or overburden any downstream pump station en route to the receiving treatment plant under normal circumstances, given the implementation of the planned improvements identified in the planning assessment where applicable. This analysis has been performed in accordance with local established policies and procedures using the best available data. This certification applies to those items listed above in Sections I and II plus all attached planning assessment addendums for which I am the responsible party. Signature of this form indicates acceptance of this wastewater flow. Signature —9 —2-a Date Page 2 of 6 FTSE 08-13 ---,/ CAJAH MOUNTAIN1 7N PNES Q DR sw N L SZAMEY-�D el Alit a./ 1STj1A16 SEWER, L I OD, DR 00, "4p v� � EITH AVE TOWN OF SAWMILLS SAWMILLS, NC 2863cQustomer #: NCDENR-Water Quality Section 9/18/2014 Chk #: Total: $480.00 SF400160TT-1SA TO REORDER, CALL YOUR LOCAL SAFEGUARD DISTRIBUTOR AT 252-826-3841 . H51VIRW00010000 . L01SF022477 - TOWN -OF SAWMILLS SAWMILL$, NC28630 ' 22331 NUMBER_ DATE :'.AM>7'�'L�GI ir. �•� I�VC�I���11%IIIi Jeci9fE y/ ti/GU 14 A�GVT 1Z331 tit :.,. ' " 6/18/2014 $480:00 - 70f SA TOWN OF SAWMILLS 4076 US HWY 321A 396-7903' SAWMILLS, NC 28630 ' e /yc�gP0AA7E�19e �z Total '` $480 0 FIRST CrnZENS BANK CHECK NO: GRANITE FALLS, NC .28630 , 66-30/531 DATE 2 2-3 3.1 AMo331. 0 A _ I