August 11, 2022
David Burton
The Young Men's Christian Association of Greensboro, Inc.
4924 Tapawingo Trail
Greensboro, NC 27406
SUBJECT: Compliance Evaluation Inspection
Permit No. W00019782
YMCA Camp Weaver WWTP
Guilford County
Dear Mr. Burton:
On August 2, 2022, Division of Water Resources staff Caitlin Caudle completed a compliance
evaluation inspection. David Burton of YMCA Camp Weaver, Todd Robinson (ORC), Josh
Powers, Ron Wall, and David McDaniel of EnviroLink, Inc. were present during the inspection.
A review of records, treatment facility, storage pond, and irrigation zones was completed.
This review reflects compliance with the subject permit. The following item requires your
attention and action:
A. Ron Wall of EnviroLink has been operating as the Back Up ORC. Mr. Wall is not
designated as the Back Up ORC for this facility. Please complete the Operator
Designation Form and submit it as instructed to designate Mr. Wall as a Back Up ORC.
All affiliations can be checked at the first link on the following website:
https://deq.nc.gov/about/divisions/water-resources/water-quality-permitting/non-
discharge-permitting/useful-links.
Please refer to the enclosed inspection report for additional comments and observations. If
you have any questions please contact me or Caitlin Caudle at the letterhead address or
phone number, or by email at lon.snider(c�ncdenr.gov or caitlin.caudle@ncdenr.gov.
Sincerely,
DocuSiiggned by:<
%w, t . 5,..ac.4-
145B49E225C94 EA.
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ-WSRO
Enc: Inspection Report
Cc: Todd Robisnon, ORC (electronic copy)
Madelyn Mills, EnviroLink (electronic copy)
Guilford County Environmental Health (electronic copy)
Laserfiche File WQ0019782
WSRO Electronic Files
GDE
NORTH CAROLINA '
omm m� ep..of o�.iXks.
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
Compliance Inspection Report
Permit: WQ0019782 Effective: 10/01/20 Expiration:
SOC: Effective: Expiration:
County: Guilford
Region: Winston-Salem
Contact Person: Rhonda Anderson Title:
12/31/26 Owner : The Young Men's Christian Association of
Greensboro Inc
Facility: YMCA Camp Weaver WWTP
4924 Tapawingo Trl
Greensboro NC 27406
Phone:
Directions to Facility:
From 1-40 East/I-85 North take the Lee Street Exit #128. Turn Right (south) on Lee Street and follow until it ends. Right onto
Young's Mill Road and follow until it ends. Left onto Mill Point Road and follow for 3/4 mile. right on Tapawi
System Classifications: SI, WW2,
Primary ORC:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 08/02/2022
Primary Inspector: Caitlin Caudle
Secondary Inspector(s):
Entry Time 08:56AM
Reason for Inspection: Routine
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Certification:
Exit Time: 10:30AM
Phone:
Phone: 336-776-9699
Inspection Type: Compliance Evaluation
1. Treatment Flow Measurement -Effluent Treatment Flow Measurement -Influent
▪ Treatment Flow Measurement -Water
Use Records
▪ End Use -Irrigation Treatment Influent Pump Station
▪ Treatment Flow Measurement Storage
(See attachment summary)
Treatment
▪ Miscellaneous Questions
▪ Record Keeping
▪ Treatment Disinfection
▪ Standby Power
Page 1 of 6
Permit: WQ0019782 Owner - Facility:The Young Men's Christian Association of Greensboro Inc
Inspection Date: 08/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
On August 2, 2022, Division of Water Resources staff Caitlin Caudle completed a compliance evaluation inspection. David
Burton of YMCA Camp Weaver, Todd Robinson (ORC), Josh Powers, Ron Wall, and David McDaniel of EnviroLink, Inc. were
present during the inspection. A review of records, treatment facility, storage pond, and irrigation zones was completed. This
review reflects compliance with the subject permit.
The following item requires your attention and action:
A. Ron Wall of EnviroLink has been operating as the Back Up ORC. Mr. Wall is not designated as the Back Up ORC for
this facility. Please complete the Operator Designation Form and submit it as instructed to designate Mr. Wall as a Back
Up ORC. All affiliations can be checked at the first link on the following website:
https://deq.nc.gov/about/divisions/water-resources/water-quality-permitting/non-discharge-permitting/useful-links.
Other observations:
• A solenoid valve in Z3 was broken preventing irrigation in this zone. It has since been repaired and irrigation has
continued in this zone.
• A set of changing rooms and a bathroom has been built next to the lake. The bathroom is connected to the system.
• All irrigation zones were not inspected during irrigation due to vegetation and insects. Ms. Caudle walked the bottom of
Z3 and Z4 and saw no signs of runoff.
• The flood plain study has been completed. Once the forcemain path is finalized an application can be submitted to the
City of Greensboro.
• DWR can assist with decommissioning the system once the connection to city sewer is made.
• The flow meter was calibrated on 7/21/2022.
• No solids have been removed from the system since the last inspection other than the grease trap.
• Soil samples have not been collected for 2022 yet. The 2021 soil reports show no issues.
• A propane generator provides back up power for the lift station.
• All existing sewer lines for the camp enter a junction box at the treatment unit. Junction Box ❑ Septic Tank ❑ Microfast
Unit ❑ CCC ❑ Wet Well ❑ Storage pond
• Mr. Burton stated that the septic tank probably needs to be checked for solids build up.
• The flows reported on the NDMRs is based on the flowmeter on the irrigation pumps.
• No anti -foaming agents are used.
• Duckweed was covering the storage pond.
• There is no back up power at the irrigation pumps.
Page 2 of 6
Permit: WQ0019782 Owner - Facility:The Young Men's Christian Association of Greensboro Inc
Inspection Date: 08/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Reuse (Quality)
Infiltration System
Lagoon Spray, LR
Activated Sludge Spray, LR
Single Family Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Single Family Drip
Activated Sludge Drip, LR
Treatment
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Comment:
Treatment Influent Pump Station
Is the pump station free of bypass lines or structures?
Is the general housekeeping acceptable?
Are all pumps present?
Are all pumps operable?
Are floats/controls operable?
Are audio and visual alarms available?
Are audio and visual alarms operational?
# Are SCADA/Telemetry alarms required?
Are SCADA/Telemetry available?
Are SCADA/Telemetry operational?
Comment:
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement -Water Use Records
Yes No NA NE
IEI
IEI
IEI
IEI
•
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
Page 3 of 6
Permit: WQ0019782 Owner - Facility:The Young Men's Christian Association of Greensboro Inc
Inspection Date: 08/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Standby Power
Is automatically activated standby power available?
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
Comment: Generator for lift station.
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000-
If yes, then when was the RMP last updated?
Comment:
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ▪ ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Page 4 of 6
Permit: WQ0019782 Owner - Facility:The Young Men's Christian Association of Greensboro Inc
Inspection Date: 08/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Comment:
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑•❑
❑ ❑•❑
❑ ❑•❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
❑ ❑•❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑•
❑ ❑ ❑•
❑ ❑•❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 5 of 6
Permit: WQ0019782 Owner - Facility:The Young Men's Christian Association of Greensboro Inc
Inspection Date: 08/02/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
Comment:
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ • ❑
❑ ❑ • ❑
Page 6 of 6