HomeMy WebLinkAboutWQ0004967_CEI_20220705
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED
July 05, 2022
Kristina Armbrust
Alljuice Realty LLC
SUBJECT: Compliance Inspection Report
Alljuice WWTF
Non-discharge Permit No. WQ0004967
Henderson County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the AllJuice WWTF on
6/29/2022. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in Non-discharge Permit No. WQ0004967. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Please note that the Notice of Violation issued to AllJuice on October 10, 2017 and NOV-2021-PC-0157
are still open and will remain open until modifications are complete. No new violations are being issued
at this time.
If you should have any questions, please do not hesitate to contact Melanie Kemp with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4653 or via email at
Melanie.kemp@ncdenr.gov.
Sincerely,
Melanie Kemp
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Compliance Inspection Report
E.c.: LF
CC: Bob Barr – RBP Systems
Chuck Pippin – Anchor QEA of North Carolina, PLLC
DocuSign Envelope ID: 44196912-CE25-4FF9-931A-9BAB24A97A78
Compliance Inspection Report
Permit:WQ0004967 Effective:04/01/22 Expiration:04/30/28 Owner :Alljuice Realty LLC
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Henderson
Asheville
Kristina Armbrust
Effective:Expiration:Facility:Alljuice WWTF
352 Jet St
Hendersonville NC 28792
Title:Phone:Operations Manager
I-26 East to Hwy. 64 East (toward Bat Cave). Turn right at the first stop light onto Sugarloaf Road. Follow signs to Alljuice. Facility is
located approximately 3 miles on the left.
Secondary ORC(s):
828-251-1900Phone:24262Certification:Robert P BarrPrimary ORC:
SI,System Classifications:
On-Site Representative(s):
Related Permits:
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
06/29/2022 01:30PM 03:30PM
Mikal Willmer 828-296-4686
Melanie Kemp Phone :
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Wastewater Irrigation
Compliance Evaluation
Question Areas:
Miscellaneous Questions Treatment Lagoons
(See attachment summary)
Page 1 of 3
DocuSign Envelope ID: 44196912-CE25-4FF9-931A-9BAB24A97A78
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0004967
06/29/2022 Compliance Evaluation
Alljuice Realty LLC
Routine
Inspection Summary:
Mikal Willmer, Melanie Kemp, and Brett Laverty with the Asheville Regional Office were on site for a compliance evaluation
inspection of the AllJuice facility on 6/29/2022. The inspection was conducted to review site conditions and discuss permit
modifications per a 5/16/2022 modification application submitted by Anchor QEA. Bob Barr and Danielle Hunter with RBP
Systems, Chuck Pippin and Alexa Baratucci with Anchor QEA, and AllJuice representatives were present for the site visit.
Irrigation Field: The health of the cover crop, tall fescue, has been mentioned in the previous three inspections. To date,
general crop conditions have improved since the reestablishment of the cover crop and application of gypsum to improve soil
fertility and mitigate sodium levels. Some moisture-tolerant weeds and grasses are still present between spray heads and
should be managed moving forward. Please note that, while the permit does not specifically require the removal of a crop
from the field, the permittee is required by permit to maintain a good cover crop and subsequent soils to maximize the fields
assimilative capacity for long-term wastewater disposal without potential impacts to ground or surface waters. It is
recommended that a plan be established to remove the cut hay from the fields, in order to remove nutrient loads that may
affect assimilation in the fields.
Influent line: A report submitted to Mr. Laverty on September 9, 2020 indicated there was a potential issue with the
structural integrity of the influent line to the irrigation pond. The planned pond modifications includes the repair and rerouting
of this pipe in order to prevent further infiltration into surrounding soils before entering the wastewater lagoon.
Irrigation Pond: The wastewater pond is unlined based on historical facility documentation. Anchor QEA has proposed the a
wastewater lagoon redesign which includes removing the accumulated sludge on the bottom of the pond, removal of soils,
relining the pond, and construction of a stormwater basin that redirects ditch water. Any updates to these plans, including a
construction timeline, should be provided moving forward.
Groundwater Exceedances: The facility has seen increases in fecal coliform, iron, manganese, and ammonia at monitoring
well MW-3 since 2019, at levels exceeding state Groundwater Standards. Groundwater exceedances and associated
corrective actions will be addressed separately by the regional hydrogeologist.
Annual Soils Analysis: It was verified by contract operations that Pace Analytical Labs collects the composite samples for
soil fertility analysis from the spray fields. It is recommended that they collect separate composite samples for each
irrigation zone to have a more representative soils analysis, as inconsistencies have been noted in the past between
samples collected by Pace Analytical and Nutter & Associates.
Equipment Calibration: The facility’s permit renewed in 2021 with changes to meter calibration requirements. The new permit
now requires annual calibration of the effluent flow meter. Please note, the facility has until the end of 2022 to calibrate the
meter and maintain compliance. Also, the permit requires calibration/verification of irrigation equipment once per permit
cycle. State guidance on irrigation equipment verification is attached for reference.