HomeMy WebLinkAboutNCG030676_Monitoring Report_20220621NCDEQ Division of Energy, Mineral and Land Resources
Stormwater Discharge Monitoring Report (DMR) Form for NCG030000��
Metal Fabrication
icic or nuu ucu s lLjp< O�
Complete, sign, scan and submit the DMR via the Stormwater NPDES Permit Data Monitoring Report F63d form within
30 days of receiving sampling results. Mail the original, signed hard copy of the DMR to the appropriate DEM R�6al Office.
Certificate of Coverage No. NCG03 0676
Person Collecting Samples: Michael Kilpatrick (Pace)
Facility Name: Greenheck Fan Corporation- Kings Mountain
Laboratory Name: Pace Analytical Services, LLC.
Facility County: Cleveland
Laboratory Cert. No.: 329
Discharge during this period:
Yes ❑ No (if no, skip to signature and date)
Has your facility implemented mandatory Tier response actions this sample period for any benchmark exceedances? ❑ Yes F� No
If so, which Tier (I, II, or III)?
A copy of this DMR has been uploaded electronically via https://edocs.deg.nc.gov/Forms/SW-DMR Q Yes 0 No
Date Uploaded:
Analytical Monitoring Requirements for Outfalls with Industrial Activities — Benchmarks in (Red)
Parameter
Parameter
Outfall001
Outfall002
Outfall
Outfall
Outfall
Code
N/A
Receiving Stream Class
Class C
Class C
N/A
Date Sample Collected MM/DD/YYYY
08/17/2021
8/17/2021
46529
24-Hour Rainfall in inches
1.1 in.
1.1
C0530
TSS in mg/L (100 or 50*)
6100
94
00400
pH in standard units (6.0 — 9.0 FW,
6.2
6.4
6.8-8.5 SW)
Copper, total recoverable in mg/L
01119
(0.010 FW, 0.0058 SW)
<0.100
<0.050
Lead, total recoverable in mg/ L
01051
(0.075 FW, 0.22 SW)
0.450
<0.010
Zinc, total recoverable in mg/ L (0.126
01094
FW, 0.095 SW)
0.360
<0.050
Chemical Oxygen Demand (COD) in
00340
mg/L (120)
<20
<20
00552
Non -Polar Oil & Grease in mg/L (15)
<5.0
<5.0
* Outfalls to Outstanding Resource Waters (ORW), High Quality Waters (HQW), Trout Waters (Tr) and Primary Nursery Areas (PNA)
have a benchmark TSS limit of 50 mg/L. All other water classifications have a benchmark of 100 mg/L
FW (Freshwater) SW (Saltwater)
Notes (optional): We have a stormwater construction permit for the facility and have conducted a walk through inspection with the contractor.
"I certify by my signature below, under penalty of law, that this document and all attachments were prepared under my direction or supervision in
accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my
inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information
submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting
false inforr n,includingthe,Rossibili1roffinesandimprisonmentforknowingviolations."
Signature of P! T ittee or 9ejliebted A*horized Individual
derek.boyd@gree
Email Address
6-16- 2Z
Date
715.841.8366
Phone Number