HomeMy WebLinkAboutNC0028711_Compliance Evaluation Inspection_20220627 (2)ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
George M. Jones
Charlotte Mecklenburg Board of Education
3301 Stafford Drive
Charlotte, NC 28208
SUBJECT: Compliance Evaluation Inspection
Berryhill Elementary WWTP
NPDES Permit No. NC0028711
Mecklenburg County
Dear Mr. Jones:
NORTH CAROLINA
Environmental Quality
June 27, 2022
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on June 20, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge (ORC)
of our findings by forwarding the enclosed report.
As discussed in the inspection report, a new ORC was identified on the October 2021 monitoring report but has not been
officially designated by the School System as required by 15A North Carolina Administrative Code (NCAC) 08G .0201 and
subject NPDES Permit. This Office requests that the new ORC and any new Backup ORCs be designated on the approved
documentation and submitted to the Division within fourteen (14) days of letter receipt.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
DE
Sincerely,
1-DocuSigned by:
'-A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL I
21 1 1 1 1 1
NPDES yr/mo/day Inspection
3 I NC0028711 111 121 22/06/20 117
Type
18 i i
I I 1 1 1
Inspector Fac Type
191 S I 201
1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I2.0 I 70I4 I 71IN I 72 I N I 73I I 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Berryhill Elementary School WWTP
10501 Walkers Ferry Rd
Charlotte NC 28208
Entry Time/Date
09:15AM 22/06/20
Permit Effective Date
20/08/01
Exit Time/Date
11:15AM 22/06/20
Permit Expiration Date
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Dustin Kyle Metreyeon/ORC/704-506-4255/
Jeffery G Mitchell//980-343-8632 /
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
George M Jones,3301 Stafford Dr Charlotte NC 28208/Director of
Maintenance/704-343-6040/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signatu
Wes Bell
e(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
,-DocuSigned by:
1,0 , 3det DWR/MRO WQ/704-663-1699 Ext.2192/ 6/27/2022
-A61696D9OCC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
6/27/2022
Page# 1
"-A14CC681AF27425...
3I
NPDES yr/mo/day
N C0028711 111 121 22/06/20
17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
RECORD KEEPING SECTION cont'd:
The "new ORC box" was checked on the October 2021 eDMR; however, the ORC has not been
officially designated by the Permittee. Please be advised that the Permittee must properly designate
the ORC and any new Backup ORCs as required by 15A NCAC 08G .0201 and NPDES Permit.
Page# 2
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El • ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El El • El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff
on 9/27/2019.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 3
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge Monitoring Reports (eDMRs) were reviewed for the of May 2021 through
April 2022. A daily maximum effluent fecal coliform violation was reported in March
2022. The December 2021 and January through March 2022 eDMRs were submitted
late. The Division has previously addressed these violations through the issuances of
a Notice of Deficiency (NOD), Notice of Violation (NOV) and NOV/civil penalty
assessments.
The March 2022 eDMR did have the ORC/Backup ORC visitations documented after
3/19/22. In addition, the downstream temperatures and times were the same on the
January 2022 eDMR. Both eDMR will be revised and resubmitted. Several
transcription errors regarding sampling times (either not listed or on wrong day) were
noted during the eDMR review. The ORC and staff must ensure to thoroughly review
all eDMRs to ensure all sampling times are properly transcribed prior to future
submittals.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: On -site field analyses (dissolved oxygen, pH, temperature, total residual chlorine) are
performed either under Metwater's field lab certification #5615 or Charlotte Board of
Education/Berryhill Elementary's field lab certification #5512. K& W Laboratories has
been contracted to perform effluent analyses (all permit -required parameters except
field).
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ❑ ❑ • ❑
Is the tubing clean? El El • El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 El El • El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El ❑
representative)?
Comment: The subject permit requires effluent grab samples.
Upstream / Downstream Sampling Yes No NA NE
Page# 4
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, • ❑ ❑ ❑
and sampling location)?
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ME ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment facility appeared to be properly operated and well
maintained at the time of the inspection.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Comment: The equalization basin is equipped with a bypass pipe into the aeration basin. The
equalization basin is also equipped with a telemetry type alarm system (high water) that
operated properly during the on -site test.
Aeration Basins Yes No NA NE
Page# 5
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: Soda ash is added to the aeration basin on an as -needed basis to maintain
appropriate alkalinity/pH levels.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
Comment: The wastewater staff have been periodically removing algae accumulations/mats in the
clarifiers.
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 1
Is the level of chlorine residual acceptable? • ❑ El El
Is the contact chamber free of growth, or sludge buildup? • El El El
Is there chlorine residual prior to de -chlorination? • El ❑ ❑
Page# 6
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The flow meter is calibrated annually and was last calibrated on 10/11/21 by
Clearwater, Inc.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable solids or foam. The effluent is
discharged into the receiving stream via submerged outfall.
Yes No NA NE
Tablet
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑ •
❑ ❑ ❑ •
Aerobic Digester Yes No NA NE
Is the capacity adequate? • ❑ El El
Is the mixing adequate? ■ ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • ❑ ❑ ❑
# Is the odor acceptable? • ❑ ❑ ❑
# Is tankage available for properly waste sludge? • ❑ ❑ ❑
Page# 7
Permit: NC0028711
Inspection Date: 06/20/2022
Owner - Facility: Berryhill Elementary School WWTP
Inspection Type: Compliance Evaluation
Aerobic Digester Yes No NA NE
Comment: Greenway Waste Solutions is currently contracted to remove wastewater solids.
Page# 8