HomeMy WebLinkAboutWI0500156_Staff Report_20220606WATER QUALITY OPERATIONS REGIONAL STAFF REPORT
Date: June 6, 2022
To: WQ Regional Operations CO
CO Reviewer: Michael Rogers
Regional Office Inspector: Eric Rice
I. GENERAL INFORMATION
1. This application is (check all that apply): ❑ New ® Renewal
❑ Minor Modification ❑ Major Modification
E Surface Irrigation ❑ Reuse ❑ Recycle ❑ High Rate Infiltration ❑ Evaporation/Infiltration Lagoon
❑ Land Application of Residuals
❑ Distribution of Residuals
❑ Attachment B included
❑ Surface Disposal
❑ 503 regulated ❑ 503 exempt
0 Closed -loop Groundwater Remediation ® Geothermal Water Return
Was a site visit conducted in order to prepare this report? ® Yes or ❑ No.
a. Date of site visit: May 18, 2022
b. Person contacted and contact information: Kevin O'Dell
c. Site visit conducted by: E. Rice
d. Inspection Report Attached: ❑ Yes or ® No.
County: Chatham
Permittee: Kevin O'Dell
Project Name: Kevin O'Dell & Angela Burton SFR
Permit # WI0500156
2. Is the following information entered into the BIMS record for this application correct?
® Yes or ❑ No. If no, please complete the following or indicate that it is correct on the current application.
For Disposal and Infection Sites:
(If multiple sites either indicate which sites the information applies to, copy and paste a new section into the
document for each site, or attach additional pages for each site)
a.
b.
c.
d.
Location(s):
Driving Directions:
USGS Quadrangle Map name and number:
Latitude: Longitude:
II. INJECTION WELL PERMIT APPLICATIONS (Complete these two sections for all systems that use injection
wells, including closed -loop groundwater remediation effluent injection wells, in situ remediation injection wells, and heat
pump injection wells.)
Description of Well(S) And Facilities — New, Renewal, And Modification
1, Type of injection system:
® Heating/cooling water return flow
O Closed -loop heat pump system
❑ In situ remediation (5I)
Permit #: WI0500156 I
WATER QUALITY OPERATIONS REGIONAL STAFF REPORT
❑ Closed -loop groundwater remediation effluent injection (5LI"Non-Discharge")
❑ Other (Specify: _
2. Does system use same well for water source and injection? ® Yes ❑ No
3. Are there any potential pollution sources that may affect injection? 0 Yes ® No
What is/are the pollution source(s)? What is the distance of the injection weIl(s) from the
pollution source(s)?
4. Quality of drainage at site: ® Good ❑ Adequate ❑ Poor
5. Flooding potential of site: ® Low ❑ Moderate 0 High
V. EVALUATION AND RECOMMENDATIONS
1. Provide any additional narrative regarding your review of the application: One well geothermal system also
utilized as a water source. An influent and effluent sample was collected for chloride, metals, and nutrients.
Well tag present, grout was not inspected, sand noted at the surface around casing. .
2. Do you foresee any problems with issuance/renewal of this permit? ❑ Yes ® No. If yes, please explain
briefly.
3. List any items that you would like Central Office to obtain through an additional information request. Make
sure that you provide a reason for each item:
Item
Reason
4. List specific Permit conditions that you recommend to be removed from the permit when issued. Make sure
that you provide a reason for each condition:
Condition
Reason
5. List specific special conditions or compliance schedules that you recommend to be included in the permit when
issued. Make sure that you provide a reason for each special condition:
Condition
Reason
Permit #: WI0500156
WATER QUALITY OPERATIONS REGIONAL STAFF REPORT
6. Recommendation: ❑ Hold, pending receipt and review of additional information by regional office; ❑ Hold,
pending review of draft permit by regional office; ❑ Issue upon receipt of needed additional information; El
Issue- sample results pending; ❑ Deny. If deny, please state reasons: _
7. Signature of report preparer(s):
Signature of WQROS regional supervisor:
Date: 6/29/2022
Attachments:
-DocuSigned by:
BCDA9D825D4A46D...
Permit #: WI0500156 3