HomeMy WebLinkAboutNC0086169_Permit (Modification)_20001204NPDES DOCUHENT SCANNING: COVER SHEET
NPDES Permit:
NC0086169
Corning / Midland facility
Document Type:
Permit Issuance
Wasteload Allocation
Authorization to Construct (AtC)
Permit Modification
Complete File - Historical
Correspondence
Speculative Limits
Instream Assessment (67b)
Environmental Assessment (EA)
Permit
History
Document Date:
December 4, 2000
This document is printed on reuse paper - ignore any
content on the reirerse side
State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Bill Holman, Secretary
Kerr T. Stevens, Director
December 4, 2000
Ms. Christy Hannan
Corning, Inc.
Telecommunications Products Division
P.O. Box 1700
Concord, North Carolina 28026-1700
A7rA
NCDENR
NORTH CAROLINA DEPARTMENT OF
ENVIRONMENT AND NATURAL RESOURCES
Subject:NPDES Permit Modification
Permit NC0086169
Midland Fiber Facility
Cabarrus County
Dear Ms. Hannan:
On July 10, 2000, the Division received your request to modify permit NC0086169.
Correspondingly, we are forwarding herewith the modifications to the subject permit, which are to be found
on the effluent limitations pages. In accordance with your request, the date on which the permitted flow
increases from 0.0274 MGD to 0.107 MGD will be changed from March 1, 2001 to January 1, 2001.
Please find enclosed the revised permit pages. The revised permit pages should be inserted into your
permit. The old pages may then be discarded. All other terms and conditions contained in the original
permit remain unchanged and in full effect. This permit modification is issued under the requirements of
North Carolina General Statutes 143-215.1 and the Memorandum of Agreement between North Carolina and
the U.S. Environmental Protection Agency.
If any parts, measurement frequencies or sampling requirements contained in this permit are
unacceptable to you, you have the right to an adjudicatory hearing upon written request within thirty (30)
days following receipt of this letter. This request must be in the form of a written petition, conforming to
Chapter 150B of the North Carolina General Statutes, and filed with the Office of Administrative Hearings
(6714 Mail Service Center, Raleigh, North Carolina 27699-6714). Unless such demand is made, this decision
shall be final and binding.
If you have any questions concerning this permit, please contact Natalie Sierra at telephone number
(919) 733-5083, extension 551.
cc: Central Files
Mooresville Regional Office/Water Quality Section
NPDES Unit
Point Source Compliance Enforcement Unit
1617 Mail Service Center, Raleigh, North Carolina 27699-1617
An Equal Opportunity Affirmative Action Employer
Sincerely,
;1,Irr T. Stevens
Telephone (919) 733-5083 FAX (919) 733-0719
VISIT us ON THE INTERNET @ http://h2o.enr.state.nc.us/NPDES
A(2). EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS - FINAL
Permit No. NC0086169 ° v
During the period beginning on the effective date of the permit and lasting until January 1, 2001, the Permittee is authorized to discharge from outfall serial number 003
Industrial Process Wastewater, Non -contact Cooling Water, and Carbon Filter Backwash. Such discharges shall be limited and monitored by the Permittee
as specified below:
EFFLUENT CHARACTERISTICS
LIMITS
MONITORING REQUIREMENTS
Monthly
Average
Weekly
Average
Daily
Maximum
' Measurement
Freckuency
Sample
Type
Sample Location
Flow (MGD)
0.0274
Continuous
Estimate
Effluent'
Total Suspended Solids
30.0 mg/L
45.0 mg/L
Weekly
Composite
Ettluent
Chloride
2/Week
Composite
Ettluent
Total Residual Chlorine
28 µg/L
2/Week
Grab
Ettluent
Temperature2
°
Weekly
Grab
Ettluent
Iron
2/Week
Composite
Ettluent
'Total Phosphorus
Quarterly
Composite
Ettluent
Chronic Toxicity3
Quarterly
Composite
Ettluent
pH4
Weekly
Grab
Effluent
Pollutant Analysis]
'
'
Effluent
Notes:
The compliance point for flow shall be upstream of the non -contact cooling water and boiler blowdown internal outfall. The compliance point for all other parameters
shall be at the Rocky River discharge location.
2 The temperature of the effluent will be regulated so that the temperature of the receiving stream does not increase more than 2.8°C above the natural water temperature.
Receiving water temperature will not exceed a maximum of 32°C.
3 Chronic Toxicity (Ceriodaphnia) at 0.31%; January, April, July and October; See Item A(4) of the Supplement to Effluent Limitations and Monitoring Requirements.
4 The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units.
S See Item A(4) of the Supplement to Effluent Limitations and Monitoring Regiiirelnents.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
A(3). EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS - FINAL
Permit No. NC0086169
During the period beginning on January 1, 2001 and lasting until permit expiration, the Permittee is authorized to discharge from outfall serial number 003 — Industrial
Process Wastewater, Non -contact Cooling Water, and Carbon Filter Backwash. Such discharges shall be limited and monitored by the Permittee as specified
below:
EFFLUENT CHARACTERISTICS
LIMITS
i
MONITORING REQUIREMENTS
Monthly
Average
Weekly
Average
Daily
Maximum
Measurement
Frequency
Sample
Type
Sample Location
Flow (MGD)
0.107
Continuous
Estimate
Effluent'
'total Suspended Solids
30.0 mg/L
45.0 mg/L
Weekly
Composite
Ettluent
Chloride
2/Week
Composite
Ettluent
Total Residual Chlorine
28 µg/L
2/Week
Grab
Ettluent
Temperature)
Weekly
Grab
Effluent
Iron
2/Week
Composite
Ettluent
"Total Phosphorus
Quarterly
Composite
Ettluent
Chronic Toxicity]
Quarterly
Composite
Ettluent
pH4
Weekly
Grab
Ettluent
Pollutant Analysis'
'
Ettluent
Notes:
The compliance point for flow shall be upstream of the non -contact cooling water and boiler blowdown internal outfall. The compliance point for all other parameters
shall be at the Rocky River discharge location.
2 The temperature of the effluent will be regulated so that the temperature of the receiving stream does not increase more than 2.8°C above the natural water temperature.
Receiving water temperature will not exceed a maximum of 32°C.
3 Chronic Toxicity (Ceriodaphnia) P/F at 1.0%; January, April, July and October; See Item A(5) of the Supplement to Effluent Limitations and Monitoring Requirements.
4 The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units.
See Item A(6) of the Supplement to Effluent Limitations and Monitoring Requirements.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
0
Corning Incorporated
Telecommunications Products Division
P.O. Box 1700
Concord, North Carolina 28026-1700
704-569-6000
July 5, 2000
Mr. Dave Goodrich
NC Dept. of Environment, Health 8_ Natural Resources
Division of Water Quality
1617 Mail Service Center
Raleigh, North Carolina 27699-1617
Dear Mr. Goodrich:
e 4-1
/j
CORNING
v t r:' %fin s
c_ C re' . .
iit�n rc (G ( c/ It "` G
0,1
/144e /14. (c--
ZL�
As indicated in our NPDES Permit, No. NC0086169 and per our request, effluent
limitations for the proposed flow of 0.017 MGD become effective on March 1, 2001.
Based on current construction progress, we are requesting that the March 1, 2001 date be
changed to January 1, 2001. At that time, the permitted flow will increase from 0.0274
MGD to 0.107 MGD and the chronic toxicity concentration will increase from 0.31% to
1.0% per the permit.
Please feel free to contact me if you have any questions concerning the above request. I
can be reached at phone number (704) 569-6268
Sincerely,
).
Christy L. Hannan
Environmental Control Engineer
Coming, Inc.
Concord Plant