Subject: Compliance Evaluation Inspection
Goldston Collection System
Collection System Permit No: WQCSD0580
Chatham County
Dear Mr. Cunnup:
On March 18, 2022, Cheng Zhang of the Raleigh Regional Office (RRO) Division of Water Resources
conducted a Compliance Evaluation Inspection of the subject facility. Your assistance and cooperation
were very helpful and appreciated. A checklist of items is enclosed with this letter. During the inspection
the following items were noted:
1.) Town of Goldston holds a deemed sewer collection system permit for the facility located in Goldston,
Chatham County. There has been no reportable sanitary sewage overflow (SSO) incidents from the
collection system since the last inspection.
2.) The collection system includes gravity sewer line, force main, and three duplex stations. Wastewater
from the facility is pumped into City of Sanford's sewer main. The system does not have high -
priority lines.
3.) A system map was available for review at the time of inspection. The facility needs to add pipe
sizes, materials, flow direction, approximate pipe age, force main air release valve location,
pump station location and capacity onto the map.
4.) The facility needs to develop a spill response action plan, which at minimum, should include
24-hour contact number, response time, equipment list and spare parts inventory, and access
to contractors. The plan also needs to include procedure to report sanitary sewer overflow
(SSO) incidents (see enclosed State Regulation 15A NCAC 02B .0506).
5.) All three pump stations were visited during the inspection. Visual/audible alarms and telemetry were
found operable. Pump stations were inspected weekly as required. The Town needs to post 24-
hour notification signs at the Main Pump Station and Ball Park Pump Station, the signs need
to include owner name, pump station identifier, address, instructions for notification, and 24-
hour emergency contact numbers.
NORTH DE
o.y,ror.m or Environmental ou.i�
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office I 3800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: 7243D3C4-CDOB-4D44-AD82-E09E4D8A0162
6.) The Town has adopted a Sewer Use Ordinance on September 4, 2012, which requires all users
involved in the preparation of food for commercial purposes shall provide and maintain
oil/grease interceptors or traps. The Town need to inspect grease traps/interceptors at the two
restraints on a regular basis. The Town also needs to distribute grease/sewer educational
material to all customers at least twice per year. The Town needs to document distribution
of grease/sewer educational material and grease trap inspections.
Please response in writing to RRO within 30 days regarding issues listed in Items 3, 4, 5, and 6. If
you have any questions regarding the attached report or any of the findings, please contact Cheng Zhang
at: (919) 791-4200 (or email: cheng.zhang@ncdenr.gov).
Attachments: Compliance Inspection Report
15A NCAC 02T .0403
15A NCAC 02B .0506
Cc: Laserfiche
Raleigh Regional Office w/attachment
D_E
NORTH CARCLINA
gaparhnanl of Environmental quality
Sincerely,
DocuSigned by:
/aun t,SSa. f. 6441A.utl,
B2916E6AB32144F...
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources
North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11611 Mail Service Center I Raleigh, North Carolina 27699-1611
919.707.9000
Compliance Inspection Report
Permit: WQCSD0580 Effective: 03/01/00 Expiration: Owner : Town of Goldston
SOC: Effective: Expiration: Facility: Goldston Wastewater Collection System
County: Chatham 40 Coral Ave
Region: Raleigh
Goldston NC 27252
Contact Person: Jeremy Preston McLeod Title: Phone: 919-898-2239
Directions to Facility:
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
On -site representative Steve Cunnup 919-898-4343
Related Permits:
Inspection Date: 03/18/2022
Primary Inspector: Cheng Zhang
Secondary Inspector(s):
Entry Time 10:00AM Exit Time: 12:00PM
DocuSigned by:
6/20/2022 Phone: 919-791-4200
D6171508E1 EC41 F...
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
▪ Miscellaneous Questions
II Spills/Response Plan
▪ Pump Stations
(See attachment summary)
▪ General
▪ Inspections
▪ Grease Control
▪ Lines
Page 1 of 6
Permit: WQCSD0580 Owner - Facility:Town of Goldston
Inspection Date: 03/18/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
The subject collection system is one of the satelite systems of City of Sanford Collection System.
Construction of collection system was completed in August 2017. The Town has a map for the collection system which
lacks many required items, the information about these items is availabe, and needs to be added to the map.
Grease/sewer educational material has not been distributed to customers as required.
Two restraunts with grease traps need to be inspected on a regular basis.
There have been no SSOs in the past three years.
The Town needs to develop a Spill Response Action Plan.
Colonial Ave. Outfall was visited, the outfall was maintained. A small tree was found around a manhole which needs to be
removed.
Easement is maintained by a contractor.
Main Pump Station, Vernie Phillips Pump Station, and Ball Park Pump Station were visited during the inspection.
Visual/audible alarms and telemetry were found operable. Signs were missing at Main and Ball Park pump station.
Page 2 of 6
Permit: WQCSD0580 Owner - Facility:Town of Goldston
Inspection Date: 03/18/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General
# Is this system a satellite system?
# If Yes, what is system name or permit number?
Is there a overall sewer system map?
Does the map include:
Pipe sizes
Pipe materials (PVC, DIP, etc)
Pipe location
# Flow direction
# Approximate pipe age
# Pump station ID, location and capacity
# Force main air release valve location & type
# Location of satellite connections
Are system maintenance records maintained?
Comment: Construction of collection system was
needs to be added to the map.
Yes No NA NE
• ❑ ❑ ❑
NC0024147 and
WQCS00047
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ ❑ ❑
completed in August 2017. Information is available and
Grease Control
Is grease/sewer education program documented with req'd customer distribution?
# Are other types of education tools used like websites, booths, special meetings, etc?
If Yes, what are they? (This can reduce mailing to annual.)
For public systems, is there a Grease Control Program via an ordinance/agreement?
If Yes, does it require grease control devices at applicable locations?
Is the Grease Control Program enforced via periodic inspections/records review?
Is action taken against violators?
Comment: Grease/sewer educational material has not been distributed to customers as required.
Two restraunts with grease traps need to be inspected on a regular basis.
Spills and Response Action Plan
# Is system free of known points of bypass?
If No, describe type of bypass and location
# Have there been any sewer spills in the past 3 years?
If Yes, were they reported to the Division if meeting the reportable criteria?
If applicable, is there documentation of press releases and public notices issued?
Are all spills or sewer related issues/complaints documented?
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
# If Yes, is there a corrective action plan?
Yes No NA NE
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
❑ ❑ • ❑
Yes No NA NE
❑ • ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Page 3 of 6
Permit: WQCSD0580 Owner - Facility:Town of Goldston
Inspection Date: 03/18/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Is a Spill Response Action Plan available?
Is a Spill Response Action Plan available for all personnel?
Does the plan include:
# 24-hour contact numbers
# Response time
# Equipment list and spare parts inventory
# Access to cleaning equipment
# Access to construction crews, contractors, and/or engineers
# Source of emergency funds
# Site sanitation and cleanup materials
# Post-overflow/spill assessment
Comment: There have been no SSOs in the past three years.
The Town needs to develop a Spill Response Action Plan.
Inspections
Are adequate maintenance records maintained?
Are pump stations being inspected at the required frequency?
Is at least one complete functionality test conducted weekly per pump station?
Is there a system or plan in place to observe the entire system annually?
Is the annual inspection documented?
# Does the system have any high -priority lines/locations?
Are inspections of HPL documented at least every 6 months?
Are new lines being added to the HPL list when found or created?
Comment: Annual inspection has not been documented.
The system does not have high -priority lines.
Lines/Right-of-Ways/Aerial Lines
Please list the Lines/Right of Ways/Aerial Lines Inspected:
Colonial Ave. Outfall, the outfall was maintained. A small tree was found around a manhole which needs to be
removed.
Are right-of-ways and easements maintained for the full width for access?
If No, give details on temporary access:
Is maintenance documented?
Were all areas/lines inspected free of issues?
Comment: Easement is maintained by a contractor.
Pump Stations
Please list the Pump Stations Inspected:
Main Pump Station, Vernie Phillips Pump Station, and Ball Park Pump Station
# Number of duplex or larger pump stations in system
❑ • ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
❑ • ❑ ❑
❑ ❑ • ❑
Yes No NA NE
3
Page 4 of 6
Permit: WQCSD0580 Owner - Facility:Town of Goldston
Inspection Date: 03/18/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
# Number of vacuum stations in system
# Number of simplex pump stations in system
# Number of simplex pump stations in system serving more than one building
How many pump/vacuum stations have:
# A two-way "auto polling" communication system (SCADA) installed?
# A simple one-way telemetry/communication system (auto -dialer) installed?
For pump stations inspected:
Are they secure with restricted access?
Were they free of by-pass structures/pipes?
Were wet wells free of excessive grease/debris?
# Do they all have telemetry installed?
Is the telemetry system functional?
Is a 24-hour notification sign posted ?
Does the sign include:
Owner Name?
Pump station identifier?
# Address?
Instructions for notification?
24-hour emergency contact numbers?
Are audio and visual alarms present?
Are audio and visual alarms operable?
# Is there a backup generator or bypass pump connected?
If tested during inspection, did it function properly?
Is the back-up system tested at least bi-annually under normal operating conditions?
# Does it have a dedicated connection for a portable generator?
# Is the owner relying on portable units in the event of a power outage?
# If Yes, is there a distribution plan?
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
# Does Permittee have the approved percentage of replacement simplex pumps?
Is recordkeeping of pump station inspection and maintenance program adequate?
Do pump station logs include at a minimum:
Inside and outside cleaning and debris removal?
Inspecting and exercising all valves?
Inspecting and lubricating pumps and other equipment?
Inspecting alarms, telemetry and auxiliary equipment?
0
0
0
0
3
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Signs were missing at Main and Ball Park pump station. Ball Park Pump station does not have
standby generator.
Page 5 of 6
Permit: WQCSD0580 Owner - Facility:Town of Goldston
Inspection Date: 03/18/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Page 6 of 6