HomeMy WebLinkAboutSW6220401_Design Calculations_20220621 (6)OUTLET PROTECTION DESIGN PHASE DESIGN PRELIM PROJECT NAME PROJECT NO CONSTR / X / Cameron Commercial 1766 REVISION RECORD LOCATION BY Harnett County, North Carolina CSB OTHER (SPECIFY) CHECKED BY 0 Storm Outlet Structure FES No.= PO-7 Pipe Dia= 24 in Q10 = 10.51 cfs Qfull = 44.53 cfs Vfull = 14.16 fps From Fig. 8.06.b.1: From Fig. 8.06.b.2: s Length Storm Outlet Structure FES No.= FES-9 Pipe Dia= 18 in Q10 = 3.33 cfs Qfull = 18.36 cfs Vfull = 10.38 fps From Fig. 8.06.b.1: From Fig. 8.06.b.2: Zone D5o DMAX Riprap Class Apron Thickness Apron Length Apron Width @ Outlet Apron Width @ End Zone D5o DMAX Riprap Class Apron Thickness Apron Length Apron Width @ Outlet Apron Width @ End Q10/Qfull = 0.24 V/Vfu I = 0.81 V = 11.4 fps = 2 = 8 in = 12 in = B = 18 in = 12.0 ft = 6 ft = 14.0 ft Q1 o/Qfu I = 0.18 V/Vfu11 = 0.75 V = 7.8 fps = 2 = 8 in = 12 in = B = 18 in = 9.0 ft = 4.5 ft = 10.5 ft 1766-Storm Drainage.xls LATEST REVISION: 6/21/2022 7:10 AM PAGE 1 OF 1