Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Schneider National Operating Facility
2420 Starita Rd
Charlotte NC 28269
Entry Time/Date
09:45AM 22/06/07
Permit Effective Date
21/03/01
Exit Time/Date
12:30PM 22/06/07
Permit Expiration Date
25/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Gary Lord, //704-496-3523/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Edward Watson�Docusignedby:
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
DWR/MRO WQ/ - - /
�R.rd 6/8/2022
"-CA4CEBF8F85F415...
Signature of Mapagtgemtgra,PbVeviewer
Agency/Office/Phone and Fax Numbers Date
144•4114w H Pa44.4 6/8/2022
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NCG510513 111 121 22/06/07
I17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On June 7, 2022, MRO-DWR staff performed a Compliance Inspection of the groundwater
remediation system at Schneider Trucking under permit NCG510513. MRO staff met with James
Welton and Matt Brundage of S&ME.
During the site visit, MRO staff also met with Gary Lord and John Medina of Schneider Trucking.
During the site visit, MRO staff requested that reports being sent to DWM for the treatment system be
copied to DWR. This information will be helpful for DWR staff in maintaining a record of the effluent
data from the treatment system.
The system is currently using 12 of the 24 RWs for the treatment system. The RWs not being used
are in areas where product remediation has been completed and S&ME has received permission
from DWM to take the wells in the cleaned areas offline.
The system has two activated carbon vessels providing primary treatment of the GW. The site plume
has reduced and the system appears to be effectively performing its' function. This is evident by the
low values being reported in the laboratory analytical data. Information on the extent of the GW
contamination is provided in the Corrective Action Performance Report of 12-2021. The impacted
area has been reduced from 8,200 sq. ft in March/April 2021 to 6,400 sq. ft. in December of 2021.
MRO staff also requested information regarding Waste Manifests for spent Carbon and records for
the collection of the fluid from the oil and water separator and free product collection tank.
Bacteria growth continues to be present in the wells and is being collected in the treatment system.
The bacteria tend to clog the bag filters requiring more frequent changing of the bag filters. The
MRO has suggested trying some treatment to kill the bacteria. However, approval for this treatment
has to be approved by DWM.
The system has an alarm. However, the alarm is visual only and is not connected to any SCADA
notification system. The contractor is completely reliant on staff working and the trucking facility to
notify them if the visual alarm is on. Contact from the facility is by telephone call to the system
operator.
Page# 2
Permit: NCG510513
Inspection Date: 06/07/2022
Owner - Facility: Schneider National Operating Facility
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El El
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: A copy of the current permit was present during the site visit. The facility is as
described in the permit.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El • El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: O&M records were viewed from January 2021 through May 2022. The records appear
to be in order. A mention was made that the Change -out of the Effluent flow meter and
the disposal records for the Oil and Water separator should be added to the O&M
records.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
El El El
Comment: The effluent had to be viewed through the sample collection port in the treatment
trailer. The access to the outfall is overgrown and not being maintained.
Page# 3